[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-007":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-007","fire-107-1-water-chemical-007",107,1,7,"自動撒水設備應裝置適當之流水檢知裝置，有關流水檢知裝置之設置規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"各樓層之樓地板面積在 5,000 平方公尺以下者，裝設一套","上下二層，設有火警自動警報設備者，得二層共用","無隔間之樓層內，樓地板面積在 10,000 平方公尺以下者，裝設一套","附設制水閥，其高度距離樓地板面在 1 公尺以下","C",null,[],false,"本題考點：自動撒水設備流水檢知裝置的設置套數門檻，以及制水閥的裝設高度。\n【正解理由】依《各類場所消防安全設備設置標準》第 51 條第二款，無隔間之樓層內，前款所定三千平方公尺得增為一萬平方公尺，亦即無隔間樓層樓地板面積在一萬平方公尺以下者裝設一套。放寬的理由在於無隔間空間並無區劃阻隔，水流與警報的辨識範圍不受限制，檢知區域得以擴大。選項 C 與條文相符，故選 C。\n【逐項排除】\n(A) 錯誤。第 51 條第一款規定各樓層之樓地板面積在三千平方公尺以下者裝設一套，超過三千平方公尺者裝設二套，門檻是三千而非五千平方公尺。\n(B) 錯誤。上下二層得共用一套，除設有火警自動警報設備外，尚須符合各層撒水頭數量在十個以下之要件，選項漏列撒水頭數量門檻，條件不完整。\n(C) 正確。無隔間之樓層由三千平方公尺增為一萬平方公尺。\n(D) 錯誤。第 51 條第四款規定附設之制水閥，其高度距離樓地板面在一點五公尺以下零點八公尺以上，並於附近明顯易見處設置標明制水閥字樣之標識；選項既寫錯數值，也漏掉下限。\n【記憶點】流水檢知裝置：一般三千、無隔間一萬；二層共用要「撒水頭十個以下＋有火警自動警報設備」；制水閥零點八至一點五公尺。","流水檢知裝置是自動撒水設備的「發報點」：撒水頭或一齊開放閥開啟放水時，二次側水流通過即推動閥板或壓力開關動作，據以發出警報並指出是哪一個檢知區域在放水。第 51 條第三款把這件事寫成明文要求——撒水頭或一齊開放閥開啟放水時，即發出警報。理解這個功能，就能明白面積門檻的意義：一套裝置對應一個檢知區域，區域劃得愈大，警報所能指示的位置就愈模糊，因此原則以三千平方公尺為界；無隔間樓層因為一眼可望穿、現場人員容易目視確認放水位置，才放寬到一萬平方公尺。同理，上下二層共用的但書要同時滿足撒水頭數量在十個以下與設有火警自動警報設備，前者限制共用規模，後者保證另有獨立的探測與報知管道。\n制水閥的高度限在零點八至一點五公尺，並須設標明字樣的標識，屬於「人可辨識、可觸及」的一般性要求，設置標準中同類的高度規定還有補助撒水栓開關閥設在距地板面一點五公尺以下、連結送水管出水口距樓地板面零點五至一點五公尺。這組數字常被互換出題，記憶時可統整為「操作性元件多落在零點八至一點五公尺區間」。\n配管面的延伸考點在第 44 條：自動撒水設備之配管、配件及屋頂水箱除準用第 32 條第一款、第二款規定外，密閉乾式或預動式之流水檢知裝置二次側配管須施予鍍鋅等防腐蝕處理，一齊開放閥二次側配管亦同；為有效排水，支管每十公尺傾斜四公分、主管每十公尺傾斜二公分，並於明顯易見處設排水閥標明字樣；立管連接屋頂水箱時，屋頂水箱之容量在一立方公尺以上。乾式與預動式之所以要防腐與洩水，正因為二次側平時無水而有空氣，殘水易造成腐蝕與結凍。\n數值連結：第 59 條的自動撒水送水口同樣以三千平方公尺為級距，樓地板面積三千平方公尺以下至少設雙口形送水口一個，每超過三千平方公尺增設一個，超過三個時以三個計。三千這個數字在自動撒水這一節反覆出現，可與流水檢知裝置一併記憶。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-006","泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",6,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-008","水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",8,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-005","泡沫滅火設備使用泡沫噴頭時，每一放射區域之樓地板面積規定應為何？",5,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-009","某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",9,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-004","移動式泡沫滅火設備之水源容量，依規定為 2 具泡沫瞄子同時放水多少分鐘之水量以上？",4,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-010","第一種室內消防栓採用消防幫浦做為加壓送水裝置時，假設水帶摩擦損失水頭為 3 m，配管磨擦損失水頭為 7 m，落差為 30 m，則依規定，幫浦的全揚程應為多少公尺？",10,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-007",113,"消防水帶用快速接頭之構造，依據消防水帶用快速接頭認可基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-007",112,"有關水系統滅火設備之放射（水）區域，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-007",111,"下列有關撒水頭設置之敘述，何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-007",110,"依密閉式撒水頭認可基準規定，其中之耐洩漏試驗，係將撒水頭施予多少之靜水壓力，保持 5 分鐘不得有漏水現象？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-007",109,"下列何者非為消防機關辦理建築物消防安全設備審查及查驗作業基準規定，申請消防專用蓄水池查驗應檢附安裝施工測試佐證資料？",1785129973136]