[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-003":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-003","fire-107-1-water-chemical-003",107,1,3,"水霧滅火設備之水源容量規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"應在最大放射區域放射 20 分鐘之水量以上","應在兩個放射區域放射 15 分鐘之水量以上","應在 40 立方公尺以上","應在 20 立方公尺以上，但兩個放射區域以上者，應在 40 立方公尺以上","D",null,[],false,"本題考點：水霧滅火設備水源容量的立法方式，係直接規定體積而非以放水時間核算。\n【正解理由】依《各類場所消防安全設備設置標準》第 64 條，水霧滅火設備之水源容量，應保持二十立方公尺以上；但放射區域在二區域以上者，應保持四十立方公尺以上。條文採「定額水量」的體例，先給單一放射區域的基準值二十立方公尺，再對二區域以上者加倍為四十立方公尺，理由是二區域以上時可能同時放射，水源必須同步倍增。選項 D 完整涵蓋原則與但書兩層，故選 D。\n【逐項排除】\n(A) 錯誤。以最大放射區域放射二十分鐘之水量表述者，是以時間乘放水量核算的體例，並非一般場所水霧設備水源容量的規定方式。\n(B) 錯誤。兩個放射區域放射十五分鐘亦非水霧規定；十五分鐘之數值見於第 76 條第三款移動式泡沫滅火設備，以二具泡沫瞄子同時放水十五分鐘之水量計。\n(C) 錯誤。四十立方公尺僅為放射區域在二區域以上時的加重值，逕以四十立方公尺為一律基準，會漏掉單一放射區域為二十立方公尺的原則規定。\n(D) 正確。原則二十立方公尺，二區域以上四十立方公尺，與條文逐字相符。\n【記憶點】水霧水源「一區二十、二區以上四十」，單位是立方公尺不是分鐘。","水霧滅火設備的滅火機制是四合一：水霧粒徑小、比表面積大，汽化吸熱快而具冷卻效果；汽化後體積膨脹約一千七百倍，可稀釋燃燒區氧濃度而窒息；對重質油品另有乳化作用，於油面形成不易燃的乳化層；對水溶性液體則有稀釋作用。也因為水霧是不連續的細水粒而非連續水柱，導電性低，才得以用於變壓器室等電氣場所。理解這一點，就能明白為何水霧的水源訂得比自動撒水設備小——它靠的是效率而不是水量。\n水源容量的體例差異是本題的真正陷阱。第 64 條給的是體積定額，而同標準對室外消防栓設備於第 41 條規定水源容量應在二具室外消防栓同時放水三十分鐘之水量以上，泡沫滅火設備於第 76 條第一款規定使用泡沫頭時以最大一個泡沫放射區域繼續放射二十分鐘以上、第三款移動式者以二具泡沫瞄子同時放水十五分鐘之水量以上——這些都是「支數或區域數乘以時間」的體例。考題最愛把兩種體例互換選項，只要記得水霧是少數直接給立方公尺的設備，即可一眼識破。\n另一組必背的對照是公共危險物品場所。依第 212 條，水霧滅火設備之放射區域每一區域在一百五十平方公尺以上，防護對象面積未滿者以實際面積計；水源容量在最大放射區域，全部水霧噴頭繼續放水三十分鐘之水量以上，放射區域每平方公尺每分鐘放水量在二十公升以上；最大放射區域水霧噴頭同時放水時，各噴頭放射壓力在每平方公分三點五公斤以上或 0.35MPa 以上；緊急電源供電容量應供有效動作四十五分鐘以上。同一種設備在一般場所與公共危險物品場所有兩套數值，作答前務必先看題幹落在哪一章。\n單位換算提醒：一立方公尺等於一千公升，二十立方公尺即兩萬公升，換算時常與每分鐘放水量的公升數混用，宜先統一單位再比較。",true,[28,32,36,39,43,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-002","有關連結送水管之送水口設置規定，下列何者錯誤？",2,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-004","移動式泡沫滅火設備之水源容量，依規定為 2 具泡沫瞄子同時放水多少分鐘之水量以上？",4,{"webId":37,"stem":38,"number":12,"year":11,"session":12},"fire-107-1-water-chemical-001","撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",{"webId":40,"stem":41,"number":42,"year":11,"session":12},"fire-107-1-water-chemical-005","泡沫滅火設備使用泡沫噴頭時，每一放射區域之樓地板面積規定應為何？",5,{"webId":44,"stem":45,"number":46,"year":47,"session":12},"fire-106-1-water-chemical-040","有一長 15 公尺、寬 12 公尺及高 3 公尺之密閉空間裝置二氧化碳滅火設備，假設空氣中氧氣之體積百分率濃度為 21%，在溫度壓力固定下，欲使氧氣濃度降至 15%以下，需注入多少立方公尺之二氧化碳？",40,106,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-006","泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",6,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-003",113,"公共危險物品場所設置泡沫滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-003",112,"室外儲槽儲存閃火點在 70℃以下第四類公共危險物品之顯著滅火困難場所，依規定設置冷卻撒水設備，其加壓送水裝置應設置手動啟動裝置及遠隔啟動裝置。但送水區域距加壓送水裝置在多少公尺以內者，得免設遠隔啟動裝置？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-003",111,"某公共危險物品場所設置室外消防栓設備，在裝置全部消防栓數量 5 支時，其所需之水源容量至少應為多少立方公尺以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-003",110,"公共危險物品等場所消防設計及消防安全設備，顯著滅火困難場所之室外儲槽場所，儲存硫磺，應設置何種滅火設備？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-003",109,"某建築物之室內、外消防栓、自動撒水及水霧滅火等設備配管採連通設計並共用消防幫浦，其共用消防幫浦之出水量和全揚程之要求標準為何？",1785129973104]