[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-002","fire-107-1-water-chemical-002",107,1,2,"有關連結送水管之送水口設置規定，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"設於消防車易於接近，且無送水障礙處，每棟大樓至少設一組","送水口為雙口形，接裝口徑 63 毫米陰式快速接頭","送水口距基地地面之高度在 1 公尺以下 0.5 公尺以上，且標明連結送水管送水口字樣","送水口在其附近便於檢查確認處，裝設逆止閥及止水閥","A",null,[],false,"本題考點：連結送水管送水口的法定設置要件，關鍵在「數量」的計算基準。\n【正解理由】依《各類場所消防安全設備設置標準》第 180 條第四款，送水口設於消防車易於接近，且無送水障礙處，「其數量在立管數以上」。條文是以立管支數作為送水口數量的下限，而非以建築物棟數計；一棟建築物設有數支立管時，送水口即須同步增設，否則消防車無法同時對各立管加壓送水。選項 A 把法定數量基準寫成每棟大樓至少設一組，與條文不符。題目問錯誤者，故選 A。\n【逐項排除】\n(A) 敘述錯誤，即為本題答案。設置位置部分固然與條文相符，但數量下限應為在立管數以上。\n(B) 敘述正確。第 180 條第五款明定送水口為雙口形，接裝口徑六十三毫米陰式快速接頭。\n(C) 敘述正確。同款規定送水口距基地地面之高度在一公尺以下零點五公尺以上，且標明連結送水管送水口字樣。\n(D) 敘述正確。第 180 條第六款明定送水口在其附近便於檢查確認處，裝設逆止閥及止水閥。\n【記憶點】連結送水管送水口：雙口形、六十三毫米陰式接頭、高度零點五至一公尺、逆止閥加止水閥，數量看立管數。","連結送水管與其他滅火設備最大的不同，在於它平時不會自己動作，而是消防人員到場後把消防車的水送進大樓、再由各層出水口取用的中繼管路，屬於消防搶救上的必要設備。理解這個定位，第 180 條的每一款就都有了道理：送水口要在消防車易於接近且無送水障礙處，是為了讓水車能靠上去；高度限在零點五至一公尺，是配合水帶接裝的操作高度；裝逆止閥防止送入的水倒流回消防車，裝止水閥則供區隔管路；接頭統一為六十三毫米陰式快速接頭，是為了與消防機關的水帶器材相容。而「數量在立管數以上」這句話則直接對應搶救戰術：立管有幾支，就代表大樓內有幾個獨立的送水管系，每一系都必須有自己的入口。\n出水口端的規定同樣是常考點。第 180 條第一款規定出水口設於地下建築物各層或建築物第三層以上各層樓梯間或緊急升降機間等（含該處五公尺以內之處所），各層任一點至出水口之水平距離在五十公尺以下；第二款規定出水口為雙口形、接裝口徑六十三毫米快速接頭，距樓地板面高度在零點五公尺以上一點五公尺以下，並設於厚度一點六毫米以上鋼板或同等性能不燃材料製箱內，箱面短邊四十公分以上、長邊五十公分以上，標明出水口字樣，每字二十平方公分以上，但設於第十層以下之樓層得用單口形；第三款並要求屋頂上適當位置至少設置一個測試用出水口。\n易混淆對照：自動撒水設備的送水口依第 59 條，同樣是六十三毫米、雙口形、陰式快速接頭、高度一公尺以下零點五公尺以上、附近裝逆止閥及止水閥，但數量改以樓地板面積三千平方公尺設一個、每超過三千平方公尺增設一個、超過三個時以三個計。另外送水口接陰式接頭、消防專用蓄水池採水口依第 186 條接六十三毫米陽式快接頭，陰陽之分是送水與取水方向不同所致，勿背反。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-107-1-water-chemical-001","撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-107-1-water-chemical-003","水霧滅火設備之水源容量規定，下列何者正確？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-106-1-water-chemical-040","有一長 15 公尺、寬 12 公尺及高 3 公尺之密閉空間裝置二氧化碳滅火設備，假設空氣中氧氣之體積百分率濃度為 21%，在溫度壓力固定下，欲使氧氣濃度降至 15%以下，需注入多少立方公尺之二氧化碳？",40,106,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-004","移動式泡沫滅火設備之水源容量，依規定為 2 具泡沫瞄子同時放水多少分鐘之水量以上？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-106-1-water-chemical-039","泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-005","泡沫滅火設備使用泡沫噴頭時，每一放射區域之樓地板面積規定應為何？",5,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-002",113,"室內停車空間設置水霧滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-002",112,"依公共危險物品等場所設置之滅火設備分類，自動撒水設備係屬下列何種滅火設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-002",111,"有關室外消防栓與室內消防栓之瞄子放水壓力之敘述，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-002",110,"連結送水管之中繼幫浦放水測試時，應從送水口以送水設計壓力送水，並以口徑 21 公厘瞄子在最頂層測試，其放水壓力不得小於 X kgf\u002Fcm2，且放水量不得小於 Y L\u002Fmin。X、Y 分別為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-002",109,"某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",1785129973102]