[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-science-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-火災學概要-016","fire-107-1-fire-science-016",107,1,16,"下列何者為海龍替代品滅火藥劑 FE-13 之分子式？",{"A":16,"B":17,"C":18,"D":19},"CF3Br","CHF3","CFBr3","CF3Cl","B",null,[],false,"本題考點：海龍替代滅火藥劑的化學組成，考 FE-13 對應分子式的辨識。\n【正解理由】海龍被淘汰的原因是分子中的溴在平流層裂解後大量破壞臭氧，因此替代藥劑的設計原則是拿掉溴與氯、只保留氫氟碳骨架。FE-13 即三氟甲烷，屬 HFC-23,分子式為 CHF3,一個碳連接三個氟與一個氫，不含溴也不含氯，臭氧破壞潛勢為零，主要以吸熱冷卻與稀釋氧濃度的物理作用滅火，故選 B。\n【逐項排除】\n(A) CF3Br 正是海龍 1301 本身，含溴而破壞臭氧，屬被列管淘汰的藥劑，不可能是自己的替代品。\n(B) CHF3 即 FE-13(HFC-23),分子中只有碳、氫、氟三種元素，符合替代藥劑無溴無氯的條件，為正解。\n(C) CFBr3 含有三個溴原子，溴含量比海龍 1301 更高，對臭氧的破壞能力更強，不可能作為替代藥劑。\n(D) CF3Cl 為含氯的化合物，氯同樣會破壞臭氧層，屬蒙特婁議定書列管物質，不符替代品條件。\n【記憶點】替代品的鐵律是「無溴無氯」;FE-13 就是把海龍 1301 的 Br 換成 H,得到 CHF3。","海龍之所以被淘汰，是因為分子中的溴在平流層受紫外線裂解後生成溴自由基，對臭氧的破壞效率是氯的數十倍，蒙特婁議定書因而將其列管，海龍 1301(CF₃Br)與海龍 1211(CF₂ClBr)在多數用途上停產。替代藥劑的發展方向就是「拿掉溴與氯、保留碳氟骨架」,於是有了 HFC 系列:FE-13 即 HFC-23(CHF₃)、FM-200 即 HFC-227ea(C₃HF₇)、FE-36 即 HFC-236fa。另一條路線則完全不用碳氟化合物，改以氮氣、氬氣搭配少量二氧化碳的混合氣體，靠稀釋氧濃度滅火。\n海龍的四位數編號規則值得背：數字依序代表碳、氟、氯、溴的原子數。1301 就是 1 個碳、3 個氟、0 個氯、1 個溴，正好是 CF₃Br;1211 則是 1 個碳、2 個氟、1 個氯、1 個溴，即 CF₂ClBr。學會這個規則，選項中的 CFBr₃ 與 CF₃Cl 可以當場判掉——前者溴更多，後者含氯，兩者都與替代品的方向背道而馳。\n滅火機制對照：海龍靠溴自由基捕捉燃燒連鎖反應中的氫與氫氧自由基，屬化學抑制，所需濃度很低;HFC 類雖仍保有部分自由基抑制能力，但以物理性吸熱為主，所需濃度較高，且高溫分解會產生氟化氫，放射後區域須充分換氣。FE-13 沸點極低，自身蒸氣壓高，適合低溫環境與較長配管的系統，這是它相對於 FM-200 的特色。\n相關考點：常見問法有「何者不含溴」「何者臭氧破壞潛勢為零」「由海龍編號寫出分子式」,以及全球暖化潛勢議題下 HFC 逐步被惰性氣體或新型藥劑取代的趨勢。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-science-015","有一火場之消光係數為 2 m-1，請問發光物體之能見度為多少公尺？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-science-017","有關地下建築物火災之敘述，下列何者錯誤？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-science-014","我國在 106 年實施 A1、A2、A3 新式火災認定方式，下列有關 A2 火災認定之敘述，何者錯誤？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-science-018","已知木造倉庫高 6 公尺，如延燒係數為 0.15，依木造建築物火災溫度標準曲線，其鄰棟建築物之理論安全距離應在多少公尺以上？",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-science-013","假設大氣中氧氣容積為 21%，現在一密閉空間（體積為 V）內，有三分之一體積（V\u002F3）為惰性氣體時（壓力仍為一大氣壓），該空間內氧氣濃度為多少%？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-science-019","電線因火災燒熔而短路所形成之熔珠，稱為下列何者？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-science-016",113,"依國家標準 CNS15030「化學品分類及標示」規定混合物中含致癌物質超過 0.1%即屬致癌混合物。目前內政部消防署決議限制滅火器藥劑以下那一類物質含量不得超過 0.1%？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-science-016",112,"假設空氣中的氧占整體重量的 23%，欲使 1 公斤的丁烷完全燃燒時，需要多少理論空氣量？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-science-016",111,"比較積污導電與金原現象之差異，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-science-016",110,"市面上販售的 ABC 乾粉滅火器內充填的乾粉滅火藥劑主要成分為：",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-science-016",109,"假設建築物外部風速為 10 m\u002Fs，風壓係數為 0.6，空氣密度為 1.0 kg\u002Fm3，其對迎風面建築物所產生的風壓約為？",1785129967793]