[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-law-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-消防法規概要-034","fire-107-1-fire-law-034",107,1,34,"依各類場所消防安全設備設置標準之規定，下列何者非屬甲類場所？",{"A":16,"B":17,"C":18,"D":19},"集會堂","資訊休閒場所","產後護理機構","日間型精神復健機構","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 12 條各類場所之分類，題目問何者「非屬」甲類場所。\n【正解理由】依《各類場所消防安全設備設置標準》第 12 條，甲類場所係供公眾使用且用火用電頻繁、人員密集或避難弱者聚集之場所；日間型精神復健機構因僅於日間提供服務、使用者夜間不留宿，避難風險較住宿型為低，於第 12 條被列為乙類場所而非甲類。四個選項中唯一不屬甲類者為 D,故選 D。\n【逐項排除】\n(A) 集會堂屬甲類場所。其特徵是人員一次性大量聚集、座席密集，避難時易發生瓶頸，依第 12 條列於甲類。\n(B) 資訊休閒場所屬甲類場所。隔間多、視聽設備用電密集、內部照度低，顧客對逃生路線不熟悉，避難條件不利，依第 12 條列於甲類。\n(C) 產後護理機構屬甲類場所。收容產婦與新生兒，屬典型的避難弱者且需他人協助避難，依第 12 條與其他醫療照護場所同列甲類。\n(D) 日間型精神復健機構非屬甲類。因不提供夜間住宿，依第 12 條歸為乙類場所，是本題答案。\n【記憶點】看有沒有「夜間住宿」:住宿型照護、產後護理入甲類，日間型精神復健機構退到乙類。","設置標準第 12 條的場所分類，是整部法規的總開關：一旦分類確定，後續各章的自動撒水設備、火警自動警報設備、緊急廣播設備、標示設備等應設門檻就跟著改變，因此這一條的分類錯誤會連鎖導致整份設計判斷全錯，也是考選部年年出題的原因。\n\n分類邏輯可以歸納為兩個變數：人員的避難能力與場所的火災風險。甲類場所是兩者都不利的組合——人員密集或屬避難弱者，且多有用火用電頻繁、可燃裝修多、夜間有人留宿等情形，例如飲食店、酒家、視聽歌唱場所、旅館、醫院、長期照顧住宿式服務機構、產後護理機構等。乙類則是風險略降一階的場所，如學校、圖書館、辦公室，以及本題的日間型精神復健機構。丙類、丁類、戊類分別對應工廠倉庫、停車空間與其他複合用途，危險性依序遞減或另有專屬規範。\n\n近年修法的重點在長照與身心障礙服務體系的細分。隨著《長期照顧服務法》施行，設置標準把「長期照顧服務機構」依住宿式、日間照顧、家庭托顧等型態拆開歸類，核心判準始終是「有無夜間住宿」與「使用者能否自行避難」。夜間人力薄弱、使用者臥床或行動不便者從嚴列甲類，並連帶要求較低門檻即應設自動撒水設備與火警自動警報設備；日間型服務因有工作人員在場且使用者清醒，得以列入乙類。\n\n答題技巧：遇到照護、安養、復健類機構名稱，先在腦中問三個問題——有沒有過夜？使用者能不能自己走出去？人力密度如何？三題中有兩題答「不利」,幾乎就是甲類。這個判準比死背條文列舉的目次更耐用，因為條文的目次編號會隨修法變動，但分類的立法思維穩定不變。undefined",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-law-033","依各類場所消防安全設備設置標準之規定，防災中心樓地板面積應在多少平方公尺以上？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-law-035","依各類場所消防安全設備檢修及申報作業基準之規定，有關瓦斯漏氣火警自動警報設備性能檢查，下列何者錯誤？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-law-032","依各類場所消防安全設備設置標準之規定，有關無線電通信輔助設備，下列敘述何者錯誤？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-law-036","依防火牆及防火水幕設置基準之規定，防火水幕設備之水源應連結加壓送水裝置，下列敘述何者錯誤？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-law-031","依各類場所消防安全設備設置標準之規定，有關緊急電源插座，下列敘述何者正確？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-law-037","依防火牆及防火水幕設置基準之規定，有一儲槽其水平剖面最大半徑為 5 公尺，內裝有公共危險物品，該公共危險物品之閃火點為攝氏八十度，則假想火面高度為多少公尺？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-034",114,"依消防法施行細則規定，下列何者非屬消防防災計畫應包括事項？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-034",113,"有關防火牆及防火水幕設置基準規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-034",112,"避難器具支固器具以直接裝置在建築物主要構造部之施工方法，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-034",111,"依消防安全設備及必要檢修項目檢修基準規定，對二氧化碳滅火器進行重量檢查時，如失重超過多少比例以上或壓力表示值在綠色範圍外時，應予以更新，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-034",110,"依消防安全設備及必要檢修項目檢修基準規定，室內消防栓設備水帶製造年份超過 10 年應使用耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。X＋Y 為多少？",1785129970654]