[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-law-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-消防法規概要-017","fire-107-1-fire-law-017",107,1,17,"依各類場所消防安全設備檢修及申報作業基準之規定，瓦斯漏氣檢知器的設置位置，當瓦斯對空氣之比重未滿 1 時，檢知器下端，應裝設在天花板下方 a 公分範圍內；瓦斯對空氣之比重大於 1 時，檢知器上端，應裝設在距樓地板面 b 公分範圍內。a、b 各為何值？",{"A":16,"B":17,"C":18,"D":19},"a=20；b=30","a=30；b=30","a=30；b=20","a=20；b=20","B",null,[],false,"本題考點：瓦斯漏氣檢知器的裝置高度，是以「瓦斯比空氣輕或重」決定裝在天花板側還是樓地板側，兩個數值都是三十公分。\n【正解理由】依《各類場所消防安全設備設置標準》第 141 條及《各類場所消防安全設備檢修及申報作業基準》瓦斯漏氣火警自動警報設備之外觀檢查，瓦斯對空氣之比重未滿一時，瓦斯會往上積聚，檢知器「下端」應裝設在天花板下方三十公分範圍內；比重大於一時，瓦斯沉降至地面，檢知器「上端」應裝設在距樓地板面三十公分範圍內。故 a=30、b=30，故選 B。\n【逐項排除】\n(A) a=20 錯誤，輕質瓦斯（如天然氣）之檢知器下端限制值為天花板下方三十公分，並非二十公分；b=30 雖對，整組仍不成立。\n(B) 正確，兩種比重情形的限制值同為三十公分，且分別管制檢知器的下端與上端，與條文一致。\n(C) a=30 正確但 b=20 錯誤，重質瓦斯（如液化石油氣）之檢知器上端限制值為距樓地板面三十公分，非二十公分。\n(D) a、b 皆誤植為二十公分，兩個數值均與條文不符。\n【記憶點】瓦斯漏氣檢知器「輕的貼天花板、重的貼地板，兩邊都是三十公分」。","瓦斯漏氣火警自動警報設備的檢知器設置規定，核心邏輯來自氣體擴散行為：天然氣主成分甲烷分子量約 16，對空氣（平均分子量約 29）之比重約 0.55，外洩後迅速上升至天花板面下形成可燃層；液化石油氣主成分丙烷分子量約 44、丁烷約 58，比重大於一，外洩後沿地面流動並積聚於低窪處。因此條文不是把檢知器一律裝在同一高度，而是要求「檢知器最靠近積聚面的那一端」進入積聚層三十公分內，輕瓦斯管末端（下端）、重瓦斯管上端，管制端點不同是本題最常被忽略的細節，也是命題者拿來設陷阱之處。\n配套規定同樣常考：檢知器與瓦斯燃燒器具或導管貫穿部之水平距離應在八公尺以內；設有樓板挑高或天花板有淨高六十公分以上樑時，輕瓦斯之檢知器應設於瓦斯燃燒器具側之樑外；檢知器不得設在出入口附近有外部空氣流通處、換氣口一點五公尺範圍內，以免氣流稀釋而延遲動作。動作時間亦有上限，檢知器由檢知至發出警報之時間不得超過六十秒，警報裝置音壓在一公尺處應在七十分貝以上。\n易混淆對照：瓦斯漏氣檢知器屬「氣體濃度感應」，探測器則屬火警自動警報設備的熱、煙感應元件，兩者設置高度依據完全不同——定溫式、差動式探測器裝設高度以樓板高度與探測區域劃分決定，偵煙式另有走廊步行距離規定，切勿把三十公分的規則套到探測器上。檢修申報時，瓦斯漏氣檢知器的外觀檢查即逐一核對上述位置與距離，性能檢查則以加瓦斯試驗器確認動作時間與警報連動。\n※ 條號請以現行法規為準，數值部分歷年未變動。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-law-016","依各類場所消防安全設備檢修及申報作業基準之規定，進行二氧化碳滅火設備音響警報檢查判定的標準，是一防護區域或防護對象物之警報系統應正確，且距警報裝置 1 公尺處之音量應在多少分貝以上？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-law-018","依各類場所消防安全設備檢修及申報作業基準之規定，供第四類公共危險物品之顯著滅火困難場所之冷卻撒水設備的加壓送水裝置，除非設有保壓措施，否則，啟動後 a 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 b 公尺以下。a、b 各為何值？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-law-015","依各類場所消防安全設備檢修及申報作業基準之規定，進行密閉式撒水設備綜合檢查時，當以幫浦方式作為加壓送水裝置時，末端查驗管之放水壓力應在 a kgf／cm2 以上、b kgf／cm2 以下。a、b 各為何值？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-law-019","依各類場所消防安全設備檢修及申報作業基準之規定，有關室內消防栓加壓送水裝置的減壓措施性能檢查，若公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之消防栓，其放水壓力應在 a kgf\u002Fcm2 以上、b kgf\u002Fcm2 以下。a、b 各為何值？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-law-014","依各類場所消防安全設備檢修及申報作業基準之規定，滅火器本體上端與樓地板面之距離，若滅火器未滿 18 公斤者應在多少公尺以下？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-law-020","依各類場所消防安全設備設置標準之規定，特別安全梯或緊急昇降機間排煙室之排煙設備，其排煙機、進風機之排煙量、進風量應在每秒 a 立方公尺（兼用時，每秒 b 立方公尺）以上，且可隨排煙口、進風口開啟而自動啟動。a、b 各為何值？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-017",114,"依消防安全設備及必要檢修項目檢修基準規定，針對性能檢查完成後之滅火器應張貼標示，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-017",113,"依消防法規定，無故撥打主管機關報案電話，或謊報火警、災害、人命救助、緊急救護情事，處罰鍰額度為下列何者？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-017",112,"依各類場所消防安全設備設置標準之規定，不適用偵煙式或熱煙複合式局限型探測器之處所得選設探測器的種類，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-017",111,"下列那一處公共危險物品之場所屬於一般滅火困難場所？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-017",110,"某甲苯儲槽之內容積為 5000 公升，其儲槽上部未設有固定式滅火設備，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，該儲槽最大容量為多少公升？",1785129970536]