[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-law-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-消防法規概要-015","fire-107-1-fire-law-015",107,1,15,"依各類場所消防安全設備檢修及申報作業基準之規定，進行密閉式撒水設備綜合檢查時，當以幫浦方式作為加壓送水裝置時，末端查驗管之放水壓力應在 a kgf／cm2 以上、b kgf／cm2 以下。a、b 各為何值？",{"A":16,"B":17,"C":18,"D":19},"a=2；b=15","a=0.5；b=5","a=3；b=12","a=1；b=10","D",null,[],false,"本題考點：密閉式自動撒水設備綜合檢查時，以幫浦作為加壓送水裝置者，末端查驗管放水壓力之上下限判定值，見《各類場所消防安全設備檢修及申報作業基準》自動撒水設備綜合檢查判定要領。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》關於自動撒水設備綜合檢查之規定，密閉式撒水設備以幫浦方式作為加壓送水裝置時，應打開末端查驗管，確認幫浦是否確實啟動，並判定其放水壓力應在 1 kgf／cm² 以上、10 kgf／cm² 以下；同時放水量應在該系統設計值以上。此上下限與《各類場所消防安全設備設置標準》第 51 條所定撒水頭放水壓力 1 kgf／cm² 以上、10 kgf／cm² 以下相互呼應，故選 D。\n【逐項排除】\n(A) a=2；b=15 之下限與上限均遭放大，15 kgf／cm² 已逼近配管與撒水頭之耐壓考量，非判定值。\n(B) a=0.5；b=5 之下限低於能使撒水頭形成有效撒水分布所需之最低壓力，上限亦過低。\n(C) a=3；b=12 兩個數值皆非作業基準所列，屬把區間整體上移的干擾組合。\n(D) a=1；b=10 正是作業基準所定之放水壓力判定區間，與設置標準之撒水頭壓力範圍一致。\n【記憶點】末端查驗管一到十：壓力 1 kgf／cm² 起跳、10 kgf／cm² 封頂。","末端查驗管（末端試驗閥）設在系統水力上最不利點的配管末端，其功能是模擬「最遠、最高那一顆撒水頭動作」的情境，用一個與撒水頭放水口徑相同的節流孔排水，藉此同時驗證三件事：壓力開關能否感知壓力下降並自動啟動幫浦、流水檢知裝置能否動作並發出警報、以及最不利點是否仍具備足夠壓力。因此判定值的下限 1 kgf／cm² 並非隨意訂定，而是撒水頭要能把水打散成設計中的傘狀水粒分布、涵蓋防護半徑所需的最低壓力；低於此值水柱會呈條狀落下，撲滅效果大幅下降。\n上限 10 kgf／cm² 的意義則相反，是防止壓力過高：壓力過大時水粒過細、動量不足以穿透火羽流抵達燃燒面，反而在上升熱氣流中被吹散，同時也增加配管、接頭與撒水頭承壓負擔。設計上若最不利點與最有利點高低差過大，就必須以中繼幫浦、減壓閥或分區配管處理，這正是命題者從「上限」延伸出去的常見考法。\n單位換算是本類題目的另一個關卡：1 kgf／cm² ≒ 0.0981 MPa ≒ 10 公尺水頭，因此 1 kgf／cm² 約等於 10 公尺揚程、10 kgf／cm² 約等於 100 公尺水頭，換算後也很好記。近年條文與題目常改以 MPa 表示（0.1 MPa 以上、1 MPa 以下），看到 MPa 版本要能立刻對回 kgf／cm² 版本。\n易混淆的鄰近數值包括：室內消防栓第一種放水壓力 1.7 kgf／cm² 以上、7 kgf／cm² 以下且放水量每分鐘 130 公升以上；水霧噴頭放水壓力 3.5 kgf／cm² 以上、放水量每分鐘 50 公升以上。三組數字若不分開記憶極易互相污染，建議以「撒水一到十、室內栓一點七到七、水霧三點五」串成口訣。※ 現行條文多已改以 MPa 表述，適用請以最新公布之作業基準與設置標準為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-law-014","依各類場所消防安全設備檢修及申報作業基準之規定，滅火器本體上端與樓地板面之距離，若滅火器未滿 18 公斤者應在多少公尺以下？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-law-016","依各類場所消防安全設備檢修及申報作業基準之規定，進行二氧化碳滅火設備音響警報檢查判定的標準，是一防護區域或防護對象物之警報系統應正確，且距警報裝置 1 公尺處之音量應在多少分貝以上？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-law-013","依各類場所消防安全設備檢修及申報作業基準之規定，各類場所之管理權人應於檢修完成後幾日內，分別填具消防安全設備檢修申報表及檢附消防安全設備檢修報告書，向當地消防機關申報？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-law-017","依各類場所消防安全設備檢修及申報作業基準之規定，瓦斯漏氣檢知器的設置位置，當瓦斯對空氣之比重未滿 1 時，檢知器下端，應裝設在天花板下方 a 公分範圍內；瓦斯對空氣之比重大於 1 時，檢知器上端，應裝設在距樓地板面 b 公分範圍內。a、b 各為何值？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-law-012","依建築技術規則建築設計施工編之規定，經中央主管建築機關認定符合耐燃二級之材料，屬於下列何種建築材料？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-law-018","依各類場所消防安全設備檢修及申報作業基準之規定，供第四類公共危險物品之顯著滅火困難場所之冷卻撒水設備的加壓送水裝置，除非設有保壓措施，否則，啟動後 a 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 b 公尺以下。a、b 各為何值？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-015",114,"依消防安全設備及必要檢修項目檢修基準規定，有關連結送水管性能，水帶箱水帶的檢查及判定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-015",113,"依消防法施行細則規定，施工中消防防護計畫不包括下列那一事項？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-015",112,"依防火牆及防火水幕設置基準之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-015",111,"某一百貨商場為地上八層、地下三層，總樓地板面積 3 千平方公尺。其火警自動警報設備之鳴動方式何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-015",110,"某自助洗衣店使用液化石油氣作為動力來源，其容器串接使用量為 100 公斤，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定之安全設施，下列何者應設置？①滅火器 ②氣體漏氣警報器 ③自動緊急遮斷裝置 ④標示板標示緊急聯絡人姓名及電話",1785129970525]