[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-040","fire-107-1-alarm-evacuation-040",107,1,40,"依各類場所消防安全設備檢修及申報作業基準規定，緩降機應以測量下降距離及下降時間，計算出下降速度，最大下降速度應在每秒多少公分以內？",{"A":16,"B":17,"C":18,"D":19},"100","120","150","180","C",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》避難器具章綜合檢查中，緩降機「下降」項目的判定方法——平均降落速度與最大下降速度是兩個並列的判定值，題目問的是後者。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第十八章避難器具「三、綜合檢查」之緩降機下降判定方法，明載「測量下降距離及下降時間，計算出下降速度，應在規定的下降速度範圍內」，並於括號內列出兩個判定值：平均降落速度應在每秒80至100公分，最大下降速度應在每秒150公分以內。題目問的是最大下降速度的上限，取150，故選 C。\n【逐項排除】\n(A) 100 是「平均降落速度」容許範圍的上限值，管的是常態下降快慢，並非最大下降速度所定之上限，兩個判定值不可互換。\n(B) 120 落在平均上限100與最大上限150之間，判定方法列出的兩組數值都沒有這個數字，屬純干擾選項。\n(C) 150 正是判定方法括號內對最大下降速度所定「每秒150公分以內」，與題目所問完全一致，為本題應選者。\n(D) 180 已超出判定方法所定之最大下降速度上限，實測若達此值即屬不符判定，不得用來當作容許上限。\n【記憶點】緩降機速度兩個數：平均80～100，最快不過150，問平均還是問最大要先看清楚。","檢修基準把緩降機的下降速度拆成兩個判定值，是因為緩降機靠調速器的摩擦制動限速，實際快慢會受使用者體重、繩索捲繞狀態與環境影響：平均降落速度每秒80至100公分反映整體制動性能是否落在設計區間，過慢代表制動過緊、避難效率不足，過快代表制動力衰減；最大下降速度每秒150公分以內則是安全上限，防止瞬間加速造成著地衝擊傷害。一個管常態、一個管極值，命題者最愛拿平均值的上限100當誘答。\n綜合檢查的體例是「下降準備→下降→收藏」三段，每段各有檢查方法與判定方法。下降準備階段判定連結部（掛鉤等）之環扣應能完全安裝在支固器具，繩子展開時應無纏繞而能成直線垂下，且繩子長端應能到達地面；下降階段除速度判定外，還要求下降完畢後回頭實施性能檢查，器具本體、支固器具等應無異常；收藏階段則判定各部分應無變形且能順暢恢復原狀。\n題幹提到「測量下降距離及下降時間，計算出下降速度」並非贅述：避難器具檢查表明定，避難器具為緩降機者應加填附表，逐具記錄樓層別、設置位置、下降距離（公分）、下降時間（秒）與下降速度（公分／秒），速度由前兩者換算而得，這正是本項判定的紀錄形式。\n易混淆對照：同章救助袋的綜合檢查只判定「下降應順暢」「下降速度應適當正常」「下降時之衝擊應緩慢」，避難橋則判定各部應無翹曲、明顯變形，搭架長度不得有變化，兩者都沒有給具體數字；帶明確公分／秒判定值的只有緩降機，這是辨識本考點的特徵。\n延伸考點：同章外觀檢查看的是周圍狀況（設置地點、操作面積、開口部、下降空間、避難空地）與標示，性能檢查看器具本體、支固器具（固定架）及固定部與收藏狀況，唯有綜合檢查會實際下降並產生量測數值，數值型考點多半出自此段。\n※ 本基準線上可得的最早版本為109年8月21日，晚於107年6月3日之本場考試，其最大下降速度判定值與本題官方答案一致。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，緊急廣播設備之啟動裝置應符合 CNS 10522 之規定，且設在距樓地板高度 X 公尺以上 Y 公尺以下範圍內，下列何者正確？",39,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-108-1-alarm-evacuation-001","某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",108,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，差動式分布型及偵煙式探測器之探測區域，指探測器裝置面之四周以淨高多少公分以上之樑或類似構造體區劃包圍者？",38,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-108-1-alarm-evacuation-002","特別安全梯的安全梯與緊急昇降機兼用時，其排煙機、進風機之排煙量、進風量須在每秒多少立方公尺以上？",2,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-037","設置避難器具時，標示其設置位置、使用方法並設置指標，下列規定何者錯誤？",37,{"webId":49,"stem":50,"number":51,"year":35,"session":12},"fire-108-1-alarm-evacuation-003","用途為補習班，居室樓地板面積 300 平方公尺，採用有效通風方式檢討，其排煙口設於天花板下方 80 公分內，試問有效通風面積最少須要多少平方公尺以上方可符合規定？",3,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-040",113,"依據火警探測器認可基準，對於差動式探測器直線上升的動作試驗，自室溫狀態下以平均每分鐘 T℃直線升溫速度之水平氣流吹向時，應在 M 分鐘以內動作，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-040",112,"依各類場所消防安全設備設置標準，醫院熱水室之場所適用選擇設置下列何種探測器？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-040",111,"光電式分離型探測器進行外觀試驗，以目視確認探測器光軸應平行牆壁距離 X 公分以上，且探測器之光軸高度應在天花板等高度 Y%以上之位置。而使用減光罩進行動作試驗，非蓄積型探測器之動作時間應在 Z 秒內。則 X、Y、Z 值，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-040",110,"避難器具之裝設規定，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-040",109,"有關火警自動警報設備受信總機周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",1785129965291]