[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-036","fire-107-1-alarm-evacuation-036",107,1,36,"依各類場所消防安全設備設置標準規定，下列處所何者不得免設緊急照明設備？",{"A":16,"B":17,"C":18,"D":19},"在避難層，由居室任一點至通往屋外出口之步行距離在 30 公尺以下之居室","具有效採光，且直接面向室外之通道或走廊","集合住宅之居室","工作場所中，未設有固定機械或裝置之部分","D",null,[],false,"本題考點：得免設緊急照明設備之處所，關鍵在工作場所是「設有」還是「未設有」固定機械或裝置。\n【正解理由】依《各類場所消防安全設備設置標準》第 179 條，得免設緊急照明設備者共六款，其中第五款為「工作場所中，設有固定機械或裝置之部分」，理由是該部分已被固定機械占據、平時不供人員滯留。反之，未設有固定機械或裝置之部分仍是人員可能通行、停留的空間，不在免設之列，故選 D。\n【逐項排除】\n(A) 屬第 179 條第一款，在避難層由居室任一點至通往屋外出口之步行距離在三十公尺以下之居室，得免設。\n(B) 屬第二款，具有效採光且直接面向室外之通道或走廊，停電時仍有自然光可辨識方向，得免設。\n(C) 屬第三款，集合住宅之居室因住戶熟悉自宅動線且面積有限，條文明列得免設。\n(D) 第五款之免設對象限於設有固定機械或裝置之部分，未設有者反而應依規定設置，為本題應選者。\n【記憶點】免設六款記「三十公尺、有採光、集合住宅、球道、有機械、廁所機械室」；沒有機械的工作場所仍要設。","緊急照明設備的規範必須「應設」與「得免設」兩條並讀。第 24 條列出應設場所：各款所列場所使用之居室、特定場所之居室、總樓地板面積在一千平方公尺以上建築物之居室（學校教室除外）、有效採光面積未達該居室樓地板面積百分之五者，以及供前四款使用之場所自居室通達避難層所須經過之走廊、樓梯間、通道及其他平時依賴人工照明部分；末項並授權經中央主管機關認可為容易避難逃生或具有效採光之場所得免設。\n第 179 條的六款免設處所，背後其實只有三種理由：其一是逃生距離短且位於避難層，停電後憑記憶與外部光線即可離開（第一款三十公尺以下之居室）；其二是本身有自然採光或使用者對環境熟悉（第二款具有效採光且直接面向室外之通道或走廊、第三款集合住宅之居室）；其三是空間性質特殊、平時不供人員滯留（第四款保齡球館球道以防煙區劃之部分、第五款工作場所中設有固定機械或裝置之部分、第六款洗手間、浴室、盥洗室、儲藏室或機械室）。把六款歸成三類，就不必逐條死記。\n本題把第五款的要件反過來寫，是這一條最常見的命題手法。相同手法也出現在第 146 條免設標示設備的規定：自居室任一點易於觀察識別主要出入口者，避難層步行距離二十公尺以下得免設出口標示燈、四十公尺以下得免設避難方向指示燈、三十公尺以下得免設避難指標，數字只要對調就成陷阱。\n答題順序也不能顛倒：先以第 24 條判斷該場所、該居室是否落入應設範圍，確定要設之後，才輪到第 179 條逐處扣除得免設的部分。若一開始就從免設條文出發，遇到「不得免設」這種雙重否定的問法極易誤判。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-035","依各類場所消防安全設備檢修及申報作業基準規定，緊急電源插座為單相交流 110 V 者，應用額定 150 V， X 安培之接地型插座。三相交流 220 V 者則適用額定 250 V，Y 安培接地型插座，並確認應無變形、損傷、顯著腐蝕或異物阻塞等，下列何者正確？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-037","設置避難器具時，標示其設置位置、使用方法並設置指標，下列規定何者錯誤？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-034","依各類場所消防安全設備檢修及申報作業基準規定，緊急照明設備在建築物總樓地板面積為 5000 平方公尺時，檢查緊急電源容量能否持續 30 分鐘之檢查數量應在多少個以上？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，差動式分布型及偵煙式探測器之探測區域，指探測器裝置面之四周以淨高多少公分以上之樑或類似構造體區劃包圍者？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-033","依各類場所消防安全設備檢修及申報作業基準規定，檢查檢知器時，使用「加瓦斯試驗器」進行加瓦斯測試，對空氣之比重未滿一者應使用何種物質？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，緊急廣播設備之啟動裝置應符合 CNS 10522 之規定，且設在距樓地板高度 X 公尺以上 Y 公尺以下範圍內，下列何者正確？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-036",113,"依住宅用火災警報器設置辦法規定，住宅用火災警報器應安裝於寢室、廚房、樓梯。若非屬前三類處所且任一樓層有超過 X 平方公尺之居室達 Y 間以上者，則設於走廊。則 X、Y 分別為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-036",112,"依消防安全設備及必要檢修項目檢修基準，有關火警自動警報設備偵煙探測器局限型，其性能檢查的敘述，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-036",111,"探測器安裝與天花板冷氣出風口應保持適當之距離，與火警探測器認可基準之下列何者有關？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-036",110,"某場所第五層需設置排煙設備，樓地板面積為 1200 平方公尺並區分為 450、400 及 350 平方公尺等三個防煙區劃，試問該層排煙機之排煙量最少應為每分鐘多少立方公尺？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-036",109,"有關定溫式感知線型探測器之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",1785129965265]