[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-031","fire-107-1-alarm-evacuation-031",107,1,31,"依各類場所消防安全設備設置標準規定，公共危險物品製造場所及一般處理場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"A":16,"B":17,"C":18,"D":19},"300 平方公尺","400 平方公尺","500 平方公尺","600 平方公尺","C",null,[],false,"本題考點：公共危險物品製造場所及一般處理場所應設火警自動警報設備的樓地板面積門檻。\n【正解理由】依《各類場所消防安全設備設置標準》第 205 條第一款第一目，公共危險物品製造場所及一般處理場所「總樓地板面積在五百平方公尺以上者」應設置火警自動警報設備；同款第二目另以室內儲存或處理數量達管制量一百倍以上為門檻，第三目則以建築物尚供其他用途者為門檻。本題問的是面積門檻，故選 C。\n【逐項排除】\n(A) 三百平方公尺並非第 205 條第一款所定數值，該面積級距屬一般用途建築物警報設備之門檻，與公共危險物品場所無涉。\n(B) 四百平方公尺在第 205 條各款均未出現，純屬干擾數值，記憶時最容易與五百平方公尺互換。\n(C) 五百平方公尺與第 205 條第一款第一目所定「總樓地板面積在五百平方公尺以上者」完全一致，為本題應選者。\n(D) 六百平方公尺未見於第 205 條，係其他條文對場所分級所用之面積級距，不得作為警報設備之設置門檻。\n【記憶點】製造與一般處理場所：面積五百、管制量一百倍，有一即設火警自動警報設備。","公共危險物品場所的消防安全設備自成一章，門檻與一般場所分別規定，第 205 條即為這類場所火警自動警報設備的專條。第一款把製造場所及一般處理場所拆成三個獨立門檻：總樓地板面積五百平方公尺以上；室內儲存或處理公共危險物品數量達管制量一百倍以上（處理操作溫度未滿攝氏一百度之高閃火點物品者除外）；建築物除供一般處理場所使用外尚供其他用途者（以無開口且具一小時以上防火時效之牆壁、樓地板區劃分隔者除外）。三者符合其一即應設置，不必同時成立。\n第二款是室內儲存場所，門檻為管制量一百倍以上、總樓地板面積一百五十平方公尺以上、建築物之一部分供作室內儲存場所使用，或高度在六公尺以上之一層建築物；第三款、第四款則分別為達顯著滅火困難之室內儲槽場所，與一面開放或上方有其他用途樓層之室內加油站。\n第 205 條第二項另設一道低標：前項以外之公共危險物品製造、儲存或處理場所，儲存、處理數量達管制量十倍以上者，應設置手動報警設備或具同等功能之緊急通報裝置，平日無作業人員者不在此限。「一百倍設自動、十倍設手動」是本條最密集的考點。\n易混淆的是第 21 條瓦斯漏氣火警自動警報設備，門檻改以地下層或地下建築物之樓地板面積一千平方公尺計算，保護的危害型態不同，數值不可互換。滅火端則見第 202 條，一般滅火困難場所之製造及一般處理場所設第四種及第五種滅火設備，第五種之滅火效能值在該場所所核算最低滅火效能值五分之一以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-030","偵煙式探測器除光電式分離型外，下列裝置規定何者錯誤？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-032","依各類場所消防安全設備設置標準規定，下列何者非屬消防搶救上之必要設備種類？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-029","依各類場所消防安全設備設置標準規定，有關標示設備之敘述，何者正確？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-033","依各類場所消防安全設備檢修及申報作業基準規定，檢查檢知器時，使用「加瓦斯試驗器」進行加瓦斯測試，對空氣之比重未滿一者應使用何種物質？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-028","依各類場所消防安全設備檢修及申報作業基準規定，對火警自動警報設備進行二信號性能檢查時，有關判定方法，下列敘述何者錯誤？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-034","依各類場所消防安全設備檢修及申報作業基準規定，緊急照明設備在建築物總樓地板面積為 5000 平方公尺時，檢查緊急電源容量能否持續 30 分鐘之檢查數量應在多少個以上？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-031",113,"避難器具於竣工查驗時，針對固定架或支固器具使用螺栓固定實施性能試驗，為確認螺栓對拉出之耐力，進行拉拔強度試驗。今使用直徑 10 毫米錨定螺栓，設計拉拔荷重（試驗荷重）為 960 公斤力（kgf），使用扭力扳手作為測定拉拔荷重之器具時，則鎖緊扭力應為多少公斤力-公分（kgf．cm）？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-031",112,"依消防安全設備及必要檢修項目檢修基準，執行緊急廣播設備性能檢查時，對啟動裝置狀態於檢查後判定方法，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-031",111,"設置 119 火災通報裝置的主要功能為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-031",110,"一一九火災通報裝置，下列規定何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-031",109,"有關緊急照明設備性能檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",1785129965236]