[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-021","fire-107-1-alarm-evacuation-021",107,1,21,"依各類場所消防安全設備設置標準規定，緊急照明設備除內置蓄電池外，應連接緊急電源，其蓄電池容量應能使其持續動作 a 分鐘以上。但採蓄電池設備與緊急發電機併設方式時，其容量應能使其持續動作分別為 b 分鐘及 c 分鐘以上，請問下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"a = 10","b = 30","c = 10","a+b+c = 70","D",null,[],false,"本題考點：緊急照明設備緊急電源之蓄電池容量，以及採「蓄電池設備與緊急發電機併設」時兩段時間的分配。\n【正解理由】依《各類場所消防安全設備設置標準》第 177 條，緊急照明設備應連接緊急電源，該緊急電源應使用蓄電池設備，「其容量應能使其持續動作三十分鐘以上。但採蓄電池設備與緊急發電機併設方式時，其容量應能使其持續動作分別為十分鐘及三十分鐘以上」。故 a＝30、b＝10、c＝30，合計 30＋10＋30＝70，故選 D。\n【逐項排除】\n(A) a＝10 不符：單獨以蓄電池供電時，法定為持續動作 30 分鐘以上，10 分鐘是併設方式中蓄電池那一段的值。\n(B) b＝30 不符：併設時前段（蓄電池設備）為 10 分鐘以上，30 分鐘屬後段。\n(C) c＝10 不符：併設時後段（緊急發電機）為 30 分鐘以上，本項把前後兩段的值倒置。\n(D) a＋b＋c＝30＋10＋30＝70，與條文所定三個時間值完全相符。\n【記憶點】緊急照明「單靠電池撐 30 分，併設就 10＋30」，三數相加得 70。","第 177 條的兩段式規定，反映緊急電源的可靠度分工：蓄電池設備在常用電源中斷的瞬間即可無間斷供電，但容量受體積與成本限制；緊急發電機容量大、可長時間供電，卻需數十秒才能起動並穩定輸出。因此法規允許併設時把蓄電池的持續動作時間降為十分鐘以上，由發電機接手負擔三十分鐘以上，兩者接力後的總保障時間反而優於單靠蓄電池的三十分鐘，而非放寬標準。\n配線面應與第 176 條合看：緊急照明設備除內置蓄電池式外，照明器具直接連接於分路配線，不得裝置插座或開關等——避免有人誤切開關而使避難照明在火災時失效；緊急照明燈之電源回路應依耐燃保護規定施作，但天花板及其底材使用不燃材料時，得施予耐熱保護，屬少見的條件式降級。\n免設處所見第 179 條共六款：在避難層由居室任一點至通往屋外出口之步行距離在三十公尺以下之居室、具有效採光且直接面向室外之通道或走廊、集合住宅之居室、保齡球館球道以防煙區劃之部分、工作場所中設有固定機械或裝置之部分、洗手間浴室盥洗室儲藏室或機械室。共通邏輯是「本來就看得見出口」或「本來就無人滯留」。\n緊急電源時間值建議整批背：火警自動警報設備（第 128 條）蓄電池有效動作十分鐘；瓦斯漏氣火警自動警報設備（第 145 條）二回路有效動作十分鐘、其他回路監視十分鐘；出口標示燈及避難方向指示燈（第 155 條）二十分鐘，特定大規模場所之主要避難路徑六十分鐘；緊急照明設備三十分鐘；二氧化碳滅火設備全區及局部放射方式（第 95 條）一小時。時間愈長者，對應的通常是「人員需持續依賴」或「放射動作須完整完成」的設備。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-020","依各類場所消防安全設備設置標準規定，瓦斯漏氣警報裝置之檢知器所能檢知瓦斯漏氣之區域內，該檢知器動作時，該區域內之檢知區域警報裝置能發出警報音響，其音壓在距 1 公尺處應有多少分貝以上？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-022","依各類場所消防安全設備設置標準規定，火警自動警報設備之緊急電源，應使用蓄電池設備，其容量能使其有效動作多少分鐘以上？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-019","在設置避難器具時，皆必須考慮其開口部保有必要開口面積、無操作障礙之面積、下降空間及下降空地等因素，試問於設置避難器具為緩降機時，下列敘述何者錯誤？",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-023","自居室任一點易於觀察識別其主要出入口，且與主要出入口之步行距離符合規定者，得免設出口標示燈、避難方向指示燈或避難指標，試問下列何者不得免設？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-018","依各類場所消防安全設備設置標準規定，每一火警分區，依規定設置火警發信機，其標示燈應平時保持明亮，其透明罩為圓弧形，裝置後突出牆面，標示燈與裝置面應成幾度角？",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-024","P 型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，依各類場所消防安全設備設置標準規定，不得超過多少個？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-021",113,"一棟防火構造建築物，其中展覽室長 20 公尺、寬 20 公尺、高 6 公尺，天花板具有一個 50 公分的樑，將其平均分為兩個區域，試問使用補償式局限型一種探測器時，最少應設置幾顆探測器於該區域當中？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-021",112,"依各類場所消防安全設備設置標準之規定，裝設於樓梯 L 級揚聲器，距揚聲器 1 公尺處所測得之音壓規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-021",111,"依各類場所消防安全設備設置標準規定，下列有關出口標示燈及避難方向指示燈之敘述，何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-021",110,"下列有關免設火警探測器之場所，何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-021",109,"有關應設置火警自動警報設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",1785129965168]