[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-020":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-020","fire-107-1-alarm-evacuation-020",107,1,20,"依各類場所消防安全設備設置標準規定，瓦斯漏氣警報裝置之檢知器所能檢知瓦斯漏氣之區域內，該檢知器動作時，該區域內之檢知區域警報裝置能發出警報音響，其音壓在距 1 公尺處應有多少分貝以上？",{"A":16,"B":17,"C":18,"D":19},"60 分貝","70 分貝","80 分貝","90 分貝","B",null,[],false,"本題考點：瓦斯漏氣火警自動警報設備中，檢知區域警報裝置的法定音壓下限與其量測位置。\n【正解理由】依《各類場所消防安全設備設置標準》第 143 條第二款，檢知器所能檢知瓦斯漏氣之區域內，該檢知器動作時，該區域內之檢知區域警報裝置能發出警報音響，條文明定「其音壓在距一公尺處應有七十分貝以上」，即 70 分貝，故選 B。\n【逐項排除】\n(A) 60 分貝低於條文所定之 70 分貝，於距 1 公尺處量得此值即不符規定。\n(B) 70 分貝正是條文明列的法定下限，與題目所問「應有多少分貝以上」相符。\n(C) 80 分貝已高於法定下限，屬加嚴值；本題問的是條文門檻本身，非設備實際可達之音壓。\n(D) 90 分貝屬緊急廣播設備 L 級揚聲器（92 分貝以上）的量級，與檢知區域警報裝置之規定無關。\n【演算步驟】法定門檻 P₀＝70 分貝（測點距警報裝置 1 公尺）；判定式：選項值－P₀。A：60－70＝－10 分貝（不足）；B：70－70＝0 分貝（恰達下限）；C：80－70＝＋10 分貝；D：90－70＝＋20 分貝。題目求下限值本身，取差值為 0 者，得 70 分貝。\n【記憶點】檢知區域警報「距一公尺、七十分貝」，比 L 級揚聲器 92 分貝低一級。","瓦斯漏氣火警自動警報設備由「檢知器—瓦斯漏氣受信總機—警報裝置」三段組成，第 143 條規範的正是最末端的警報段，分為兩款。第一款瓦斯漏氣表示燈，設有檢知器之居室面向通路時，設於該面向通路部分之出入口附近，距樓地板面之高度在四點五公尺以下，亮度須在表示燈前方三公尺處能明確識別，並於附近標明瓦斯漏氣表示燈字樣；一警報分區僅一室時得免設。第二款即本題的檢知區域警報裝置，距一公尺處七十分貝以上，並設三項但書：檢知器本身具發出警報功能者、設於機械室等常時無人場所者、設於瓦斯導管貫穿牆壁處者，均不在此限——無人常駐處鳴響無受眾，而貫穿部之檢知器是為攔截導管洩漏，其報知統一由受信總機承擔。\n音壓類數值宜整批記：檢知區域警報裝置距一公尺 70 分貝以上；緊急廣播設備（第 133 條）距揚聲器一公尺處，L 級 92 分貝以上、M 級 87 分貝以上未滿 92 分貝、S 級 84 分貝以上未滿 87 分貝。分貝是對數尺度，70 與 92 的差距在聽感上相當懸殊，正反映兩者用途分工：一個要求「在檢知區域內叫得到人」，一個要求「全棟廣播讓人聽得懂」。\n易混淆的是三種「會亮或會叫」的裝置：瓦斯漏氣表示燈只亮不叫；檢知區域警報裝置在檢知區域內發出音響；瓦斯漏氣受信總機（第 142 條）則裝置於值日室等平時有人之處所，設有防災中心時設於該中心，其主音響裝置之音色及音壓應有別於其他警報音響，操作開關距樓地板面高度須在零點八公尺以上（座式操作者為零點六公尺）一點五公尺以下。緊急電源見第 145 條：應使用蓄電池設備，容量能使二回路有效動作十分鐘以上、其他回路能監視十分鐘以上——「有效動作」與「監視」是兩種狀態，常被合併誤記。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-019","在設置避難器具時，皆必須考慮其開口部保有必要開口面積、無操作障礙之面積、下降空間及下降空地等因素，試問於設置避難器具為緩降機時，下列敘述何者錯誤？",19,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-021","依各類場所消防安全設備設置標準規定，緊急照明設備除內置蓄電池外，應連接緊急電源，其蓄電池容量應能使其持續動作 a 分鐘以上。但採蓄電池設備與緊急發電機併設方式時，其容量應能使其持續動作分別為 b 分鐘及 c 分鐘以上，請問下列何者正確？",21,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-018","依各類場所消防安全設備設置標準規定，每一火警分區，依規定設置火警發信機，其標示燈應平時保持明亮，其透明罩為圓弧形，裝置後突出牆面，標示燈與裝置面應成幾度角？",18,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-022","依各類場所消防安全設備設置標準規定，火警自動警報設備之緊急電源，應使用蓄電池設備，其容量能使其有效動作多少分鐘以上？",22,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-017","供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，若使用螺栓固定時，下列何者錯誤？",17,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-023","自居室任一點易於觀察識別其主要出入口，且與主要出入口之步行距離符合規定者，得免設出口標示燈、避難方向指示燈或避難指標，試問下列何者不得免設？",23,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-020",113,"一棟建築物擁有地下 2 層以及地上 8 層，B1F, B2F 各層面積均為 400 平方公尺，1F, 2F 面積皆為 350 平方公尺，3~8F 皆為 280 平方公尺，依據各類場所消防安全設備設置標準之規定，下列何者正確？（1F 為地面層，BF 代表地下層，B1F 為地下 1 層，依此類推）",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-020",112,"依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-020",111,"依消防安全設備及必要檢修項目檢修基準，實施緊急照明設備性能檢查，檢查數量下列之敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-020",110,"有關辦公大樓排煙設備之啟動裝置在消防安全設備及必要檢修項目檢修基準之性能及綜合檢查的檢查及判定方法，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-020",109,"B 級出口標示燈且有顯示避難方向符號者，其有效距離係指步行至該燈多少公尺之距離？",1785129965160]