[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-017","fire-107-1-alarm-evacuation-017",107,1,17,"供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，若使用螺栓固定時，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"使用錨定螺栓","當螺紋標稱為 M10×1.5 時，螺栓埋入混凝土內不含灰漿部分之深度應為 45 mm 以上","當螺紋標稱為 M10×1.5 時，螺栓埋入混凝土內不含灰漿部分之轉矩值應為 150-250 kgf-cm 以上","當螺紋標稱為 M12×1.75 時，螺栓埋入混凝土內不含灰漿部分之深度應為 70 mm 以上","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 174 條固定架及支固器具以螺栓固定時之埋入深度與轉矩值。\n【正解理由】第 174 條第 2 款附表明定：螺紋標稱 M10×1.5 者埋入深度四十五毫米以上、轉矩值一百五十至二百五十 kgf-cm；M12×1.75 者埋入深度六十毫米以上、轉矩值三百至四百五十 kgf-cm；M16×2 者埋入深度七十毫米以上。(D) 把 M16×2 的七十毫米安到 M12×1.75 上，與表列不符，故選 D。\n【逐項排除】\n(A) 與第 174 條第 1 款相符，固定時應使用錨定螺栓，敘述正確。\n(B) M10×1.5 之埋入深度為 45 mm 以上，與表列一致，敘述正確。\n(C) M10×1.5 之轉矩值為 150 至 250 kgf-cm，與表列一致，敘述正確。\n(D) M12×1.75 之表列埋入深度為 60 mm 以上，70 mm 係 M16×2 的數值，張冠李戴，為應選之錯誤選項。\n【記憶點】深度「四五、六十、七十」，轉矩「150-250、300-450、600-850」，隨 M10、M12、M16 遞增。","《各類場所消防安全設備設置標準》第 174 條附表屬純記憶型考點，三組數值須整組背牢：M10×1.5 為埋入深度四十五毫米以上、轉矩值一百五十至二百五十 kgf-cm；M12×1.75 為六十毫米以上、三百至四百五十 kgf-cm；M16×2 為七十毫米以上、六百至八百五十 kgf-cm。深度序列「45、60、70」與轉矩下限序列「150、300、600」恰為倍增節奏，可記成「螺栓愈粗，埋愈深、鎖愈緊」。命題者最常用的手法就是把相鄰兩列數值互換，本題即把 M16 的七十毫米安到 M12 上。\n為什麼深度與轉矩要一起管：錨定螺栓靠與混凝土的摩擦及機械咬合承載，埋入深度不足時，受力會以錐形破壞的方式把周邊混凝土整塊拉出；轉矩值則是預緊力的間接控制指標，過低螺栓易鬆動，過高則可能使錨栓套筒滑移或混凝土開裂，故訂的是上下限區間而非單一下限。條文特別載明「不含灰漿部分」，因為表面粉刷層不具承載能力，把粉刷厚度算進埋入深度等於虛報。\n同組條文的前後脈絡：第 173 條規定供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，應使用符合 CNS 二四七三、四四三五規定或具有同等以上強度及耐久性之材料，並應施予耐腐蝕加工處理；第 170 條規定救助袋支固器具以螺栓、熔接或其他堅固方法，裝置在使用場所之柱、地板、樑或其他構造上堅固或加強部分。\n相關考點連結：第 25 條列舉之避難器具種類（滑臺、避難梯、避難橋、救助袋、緩降機、避難繩索、滑杆）常與本條併考，先問器具種類、再問固定方式與數值。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-016","避難器具之設置數量與場所之收容人數有很大的關係，依各類場所消防安全設備設置標準規定，有關醫療機構（醫院、診所）候診室之收容人數之計算，應以各候診室之樓地板面積和除多少平方公尺所得之數，做為候診室之收容人數？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-018","依各類場所消防安全設備設置標準規定，每一火警分區，依規定設置火警發信機，其標示燈應平時保持明亮，其透明罩為圓弧形，裝置後突出牆面，標示燈與裝置面應成幾度角？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-015","有關緊急供電系統之電源，下列何者錯誤？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-019","在設置避難器具時，皆必須考慮其開口部保有必要開口面積、無操作障礙之面積、下降空間及下降空地等因素，試問於設置避難器具為緩降機時，下列敘述何者錯誤？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-020","依各類場所消防安全設備設置標準規定，瓦斯漏氣警報裝置之檢知器所能檢知瓦斯漏氣之區域內，該檢知器動作時，該區域內之檢知區域警報裝置能發出警報音響，其音壓在距 1 公尺處應有多少分貝以上？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-017",113,"電子工業廠房潔淨區，因潔淨環境及構造特殊，特訂定潔淨區消防安全設備設置要點，對於潔淨室設置吸氣式偵煙探測系統時，依據此設置要點，下列說明何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-017",112,"有一地下建築物總樓地板面積超過 1 千平方公尺，依據各類場所消防安全設備設置標準，下列何者非依法應設之消防安全設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-017",111,"下列何者非各類場所消防安全設備設置標準明定應設置防災監控系統綜合操作裝置之場所？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-017",110,"下列那二種避難器具在性能檢查時，均須對其下降空地附近之支持或固定裝置進行判定？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-017",109,"一一九火災通報裝置之設置規定，下列敘述何者錯誤？",1785129965140]