[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-015","fire-107-1-alarm-evacuation-015",107,1,15,"有關緊急供電系統之電源，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"蓄電池設備充電電源之配線設專用回路，其開關上應有明顯之標示","裝設發電機及蓄電池之處所為防火構造。但設於屋外時，設有不受積水及雨水侵襲之防水措施者，不在此限","緊急電源裝置切換開關，於常用電源切斷時自動切換供應電源至緊急用電器具，並於常用電源恢復時，手動恢復由常用電源供應","發電機裝設適當開關或連鎖機件，以防止向正常供電線路逆向電力","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 237 條緊急供電系統之電源規定，題目要挑出敘述錯誤者。\n【正解理由】第 237 條第 2 款明定「緊急電源裝置切換開關，於常用電源切斷時自動切換供應電源至緊急用電器具，並於常用電源恢復時，自動恢復由常用電源供應」，(C) 把回復方式寫成「手動恢復」，與條文之「自動恢復」不符，故選 C。\n【逐項排除】\n(A) 與第 237 條第 5 款相符：蓄電池設備充電電源之配線設專用回路，其開關上應有明顯之標示。\n(B) 與第 237 條第 4 款相符：裝設發電機及蓄電池之處所為防火構造，設於屋外並設有不受積水及雨水侵襲之防水措施者，不在此限。\n(C) 條文所定為常用電源恢復時「自動」恢復由常用電源供應，敘述與條文相反，即為應選之錯誤選項。\n(D) 與第 237 條第 3 款相符：發電機裝設適當開關或連鎖機件，以防止向正常供電線路逆向電力。\n【記憶點】緊急電源切換「去也自動、回也自動」，看到手動恢復就是錯。","《各類場所消防安全設備設置標準》第 237 條把緊急供電系統的電源要求濃縮成五款：第 1 款要求緊急電源使用符合 CNS 一○二○四規定之發電機設備、一○二○五規定之蓄電池設備或具有相同效果之設備，容量計算由中央消防機關另定；第 2 款是自動切換與自動恢復；第 3 款是防止逆向電力；第 4 款是裝設處所為防火構造；第 5 款是充電電源專用回路與開關標示。\n為什麼「恢復」也必須自動：常用電源復電後若須有人到場手動切回，緊急電源會持續放電；蓄電池設備的容量是以有效動作一定時間的等級設計，長時間放電將使其在下一次停電時無法達到規定動作時間。自動恢復同時讓蓄電池立即回到充電狀態，這也是第 5 款要求充電電源設專用回路的理由——避免一般回路跳脫時連帶讓充電中斷而無人察覺，故開關上須有明顯標示。\n為什麼要防逆向電力：市電停電時，若發電機的電力逆流回正常供電線路，會使外部線路意外帶電，對搶救與復電作業形成重大危險，故以適當開關或連鎖機件（互鎖）阻斷。\n易混淆對照：「專用回路」的概念在本章反覆出現但目的不同——第 191 條規定緊急電源插座應從主配電盤設專用回路，各層至少設二回路以上之供電線路，每一回路之連接插座數在十個以下，該專用回路不得設漏電斷路器，且緊急用電源插座應連接至緊急供電系統。本條第 5 款的專用回路則是保障蓄電池的充電不中斷。一個保供電、一個保充電。\n易混淆對照：緊急電源與緊急電源插座是兩件事。前者講的是「電從哪裡來」，即本條所定之發電機設備或蓄電池設備。後者是消防人員搶救時取電的插座：第 191 條定其電流供應容量為交流單相一百一十伏特（或一百二十伏特）十五安培，其容量約為一點五瓩以上，裝設於樓梯間或緊急昇降機間等消防人員易於施行救火處，且每一層任何一處至插座之水平距離在五十公尺以下，並在保護箱上方設紅色表示燈。考題常把兩者的規格值互相調換，判讀時先確認問的是電源本體還是插座。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-016","避難器具之設置數量與場所之收容人數有很大的關係，依各類場所消防安全設備設置標準規定，有關醫療機構（醫院、診所）候診室之收容人數之計算，應以各候診室之樓地板面積和除多少平方公尺所得之數，做為候診室之收容人數？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-013","依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-017","供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，若使用螺栓固定時，下列何者錯誤？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-012","有關光電式分離型探測器光軸，下列設置規定何者正確？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-018","依各類場所消防安全設備設置標準規定，每一火警分區，依規定設置火警發信機，其標示燈應平時保持明亮，其透明罩為圓弧形，裝置後突出牆面，標示燈與裝置面應成幾度角？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-015",113,"瓦斯洩漏時檢知器設置位置將會影響其探測性能，依據消防安全設備及必要檢修項目檢修基準之規定，來判定瓦斯漏氣檢知器設置場所及設置位置，下列何者為適合的設置場所？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-015",112,"有關消防安全設備緊急電源容量，依據各類場所消防安全設備設置標準，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-015",111,"依各類場所消防安全設備設置標準規定，為確保排煙設備動作時，不受空調等通風換氣裝置影響排煙效果，下列何項排煙設備元件動作時應連動停止空氣調節及通風設備運轉？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-015",110,"對空氣管式之差動式分布型探測器進行空氣注入之性能檢查時，下列何種試驗無須量測探測器導通與否？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-015",109,"有關排煙設備之設置規定，下列敘述何者錯誤？",1785129965127]