[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-014","fire-107-1-alarm-evacuation-014",107,1,14,"依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",{"A":16,"B":17,"C":18,"D":19},"在 0.5 公尺以上 1.5 公尺以下","在 0.8 公尺以上 1.8 公尺以下","在 0.8 公尺以上 1.5 公尺以下","在 0.5 公尺以上 1.8 公尺以下","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 126 條火警受信總機之位置規定中，壁掛型操作開關之裝設高度。\n【正解理由】第 126 條第 4 款明定「壁掛型總機操作開關距離樓地板面之高度，在零點八公尺（座式操作者，為零點六公尺）以上一點五公尺以下」，題目問壁掛型，取 0.8 公尺至 1.5 公尺，故選 C。\n【逐項排除】\n(A) 0.5 公尺以上 1.5 公尺以下：上限雖與條文相符，但下限法定為 0.8 公尺，0.5 公尺過低。\n(B) 0.8 公尺以上 1.8 公尺以下：下限正確，惟上限法定為 1.5 公尺，1.8 公尺已超出便於判讀與操作之範圍。\n(C) 0.8 公尺以上 1.5 公尺以下：與條文逐字相符，為正確設置範圍。\n(D) 0.5 公尺以上 1.8 公尺以下：上下限均與條文不合，是把兩個錯誤數值湊在一起的干擾項。\n【記憶點】壁掛型受信總機開關「零點八到一點五」，改為座式操作時下限降到零點六。","高度規定的一致性：《各類場所消防安全設備設置標準》第 126 條第 4 款的零點八至一點五公尺，是依站立者手部自然操作範圍訂定；座式操作因坐姿手部位置較低，下限才降為零點六公尺。同一組高度在警報設備章節反覆出現——第 138 條規定擴音機及操作裝置之操作開關距樓地板面之高度，在零點八公尺以上（座式操作者，為零點六公尺）一點五公尺以下；第 142 條規定瓦斯漏氣受信總機之操作開關距樓地板面之高度，須在零點八公尺以上（座式操作者為零點六公尺）一點五公尺以下。三者可整組記成「總機與操作裝置 0.8～1.5、座式下限 0.6」。\n第 126 條其餘三款同屬常考點：裝置於值日室等經常有人之處所，設有防災中心時設於該中心（確保有人即時判讀分區）；裝置於日光不直接照射之位置（避免面板反光與器材老化）；避免傾斜裝置，其外殼應接地（防止感電與雜訊誤動作）。\n易混淆對照：不同設備的裝設高度並不相同。第 191 條規定緊急電源插座為接地型，裝設高度距離樓地板一公尺以上一點五公尺以下，且裝設二個於崁裝式保護箱，保護箱長邊及短邊分別為二十五公分及二十公分以上。把「受信總機 0.8～1.5」與「緊急電源插座 1.0～1.5」分開記，是高度題不失分的關鍵。\n相關考點連結：第 142 條的瓦斯漏氣受信總機除高度外，另要求裝置於值日室等平時有人之處所（設有防災中心時設於該中心）、具有標示瓦斯漏氣發生之警報分區、設於瓦斯導管貫穿牆壁處之檢知器其警報分區應個別標示、主音響裝置之音色及音壓應有別於其他警報音響、一棟建築物內有二臺以上時該受信總機處設有能相互同時通話連絡之設備。可以看出兩種受信總機的規範骨架幾乎相同——位置要有人、高度合手、分區要標示——差別在瓦斯漏氣特別強調「音色要能分辨」，因為瓦斯漏氣與火災的應變方式完全不同。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-013","依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-015","有關緊急供電系統之電源，下列何者錯誤？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-012","有關光電式分離型探測器光軸，下列設置規定何者正確？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-016","避難器具之設置數量與場所之收容人數有很大的關係，依各類場所消防安全設備設置標準規定，有關醫療機構（醫院、診所）候診室之收容人數之計算，應以各候診室之樓地板面積和除多少平方公尺所得之數，做為候診室之收容人數？",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-011","依各類場所消防安全設備設置標準規定，火警受信總機、中繼器及偵煙式探測器，有設定蓄積時間時，其蓄積時間之合計，每一火警分區在多少秒以下？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-017","供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，若使用螺栓固定時，下列何者錯誤？",17,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-014",113,"某社區活動中心位於建築物第 2 層（非避難層），經檢討該活動中心為有開口樓層，依規定自活動中心任一點易於觀察識別其主要出入口，且與主要出入口之步行距離分別在 X 公尺以下，得免設出口標示燈；步行距離在 Y 公尺以下，得免設避難方向指示燈，則 X+Y=？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-014",112,"依各類場所消防安全設備設置標準規定，火警自動警報設備應採分區鳴動，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-014",111,"依各類場所消防安全設備設置標準規定，供失智照顧型長期照顧服務機構、老人福利機構（安養機構）、產後護理機構等避難弱勢場所之樓層，符合規定者得免設避難器具，下列何者非免設之必要條件？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-014",110,"對火警自動警報設備二信號式受信總機進行火災表示之性能檢查時，接到第 1 報火警信號但尚未接到第 2 報火警信號時，下列那二種裝置均不應動作？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-014",109,"某百貨商場之 5 樓樓地板面積為 2,100 平方公尺，依各類場所消防安全設備設置標準規定，該層樓至少應設置幾個防煙區劃？",1785129965124]