[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-012","fire-107-1-alarm-evacuation-012",107,1,12,"有關光電式分離型探測器光軸，下列設置規定何者正確？",{"A":16,"B":17,"C":18,"D":19},"探測器之光軸，指探測器受光面中心點與送光面中心點之連結線","設在與探測器光軸平行牆壁距離 30 公分以上之位置","探測器之光軸高度，在天花板等高度 60%以上之位置","探測器之光軸與警戒區任一點之水平距離，在 9 公尺以下","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 123 條光電式分離型探測器之設置規定與光軸定義。\n【正解理由】第 123 條第 2 項明定「前項探測器之光軸，指探測器受光面中心點與送光面中心點之連結線」，(A) 與條文逐字相符，故選 A。\n【逐項排除】\n(A) 光軸即受光面中心點與送光面中心點之連結線，這條連結線也是判斷光軸高度與水平距離的基準，敘述正確。\n(B) 條文第 2 款為「設在與探測器光軸平行牆壁距離六十公分以上之位置」，30 公分不足，牆面反射與污損會干擾受光量。\n(C) 條文第 5 款為「光軸高度在天花板等高度百分之八十以上之位置」，60% 過低，偏離煙層先蓄積的頂部區域。\n(D) 條文第 7 款為「光軸與警戒區任一點之水平距離，在七公尺以下」，9 公尺過寬，警戒區邊緣將形成偵測死角，煙可能繞過光路而不被檢出。\n【記憶點】分離型記「牆距六十公分、光軸八成高、水平七公尺」，光軸就是受光面與送光面兩個中心點的連線。","《各類場所消防安全設備設置標準》第 123 條共七款，構成光電式分離型探測器的完整設置規格，除光軸定義外還包括：受光面設在無日光照射之處（避免自然光造成受光量變動而誤動作或失效）；受光器及送光器設在距其背部牆壁一公尺範圍內；設在天花板等高度二十公尺以下之場所；光軸長度在該探測器之標稱監視距離以下。這些款項合起來界定出一條「看得準、不受干擾」的光路。\n與局限型的原理差異：局限型偵煙式探測器在一個點上檢測煙濃度，分離型則由送光器發射光束、受光器接收，煙進入光路使減光率達一定值時動作，屬線型偵測。因為偵測的是一整條線而非一個點，分離型適合挑高與大空間，第 112 條第 2 款也特別規定裝設光電式分離型探測器時，火警分區任一邊長得由五十公尺放寬為一百公尺以下。\n數值記憶：牆距六十公分以上、光軸高度為天花板等高度百分之八十以上、光軸與警戒區任一點水平距離七公尺以下、設置場所天花板等高度二十公尺以下，可串成「六十、八成、七、二十」。\n易混淆對照：第 122 條規範的是「偵煙式探測器除光電式分離型外」的裝置規定，探測器下端裝設在裝置面下方六十公分範圍內、裝設於距離牆壁或樑六十公分以上之位置；兩條的六十公分意義不同——第 122 條量的是點型探測器與牆或樑的距離，第 123 條量的是光軸與平行牆壁的距離。此外第 115 條規定天花板上設有出風口時，探測器應距離該出風口一點五公尺以上，但火焰式、差動式分布型及光電式分離型探測器不受此限——因為這三者偵測的是一個面或一條線，不像局限型那樣依賴單點的煙或熱蓄積。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-011","依各類場所消防安全設備設置標準規定，火警受信總機、中繼器及偵煙式探測器，有設定蓄積時間時，其蓄積時間之合計，每一火警分區在多少秒以下？",11,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-013","依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",13,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-010","依各類場所消防安全設備設置標準第 23 條規定，各類場所均應設置避難指標。但設有以下那一個設備時，在其有效範圍內，得免設置避難指標？",10,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",14,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-009","以下有關各類場所消防安全設備設置標準對火警分區的規定，何者錯誤？",9,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-015","有關緊急供電系統之電源，下列何者錯誤？",15,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-012",113,"當火警發信機兼作其他消防安全設備之啟動裝置者，有關火警自動警報設備之配線保護規定，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-012",112,"有關出口標示燈及避難方向指示燈，在沒有不易看清或識別該燈情形的條件，依據各類場所消防安全設備設置標準，下列有效範圍何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-012",111,"某餐廳廚房之瓦斯爐具使用天然氣作為燃料時，依法設有瓦斯漏氣火警自動警報設備，其瓦斯漏氣檢知器應設於距瓦斯爐具水平距離 X 公尺以內，且於該水平距離內之天花板無淨高 Y 公分以上之樑或類似構造體區隔之吸氣口 Z 公尺範圍內，試問Ｘ、Ｙ、Z 分別為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-012",110,"建築物某一樓層（A 區）通往直通樓梯（B 區）的出口標示燈（L）附有誘導音裝置，並設置有停止專用偵煙式探測器（D）及具有緊急廣播設備連動停止性能，在其性能試驗之連動停止試驗中，下列何者應判定不合格？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-012",109,"有關緊急電源插座之設置規定，下列敘述何者正確？",1785129965111]