[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-011","fire-107-1-alarm-evacuation-011",107,1,11,"依各類場所消防安全設備設置標準規定，火警受信總機、中繼器及偵煙式探測器，有設定蓄積時間時，其蓄積時間之合計，每一火警分區在多少秒以下？",{"A":16,"B":17,"C":18,"D":19},"50 秒","60 秒","70 秒","80 秒","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》關於火警受信總機裝置之規定中，蓄積時間合計之上限。\n【正解理由】依《各類場所消防安全設備設置標準》火警受信總機裝置之規定，受信總機、中繼器及偵煙式探測器有設定蓄積時間時，其蓄積時間之合計，每一火警分區在六十秒以下；使用其他探測器時，在二十秒以下。題目問的正是偵煙式探測器參與時的合計上限，即 60 秒，故選 B。\n【逐項排除】\n(A) 50 秒非法定數值，是把二十秒與六十秒折衷後產生的干擾項，蓄積時間並無此中間級距。\n(B) 60 秒即法條所定「合計在六十秒以下」之上限，受信總機、中繼器、偵煙式探測器三個環節各自設定的蓄積時間，加總後不得超過此值。\n(C) 70 秒已逾六十秒上限，蓄積過久將延誤警報發出、壓縮避難時間，法規無此數值。\n(D) 80 秒同樣逾越上限，且與非偵煙式探測器所適用之二十秒規定相去更遠。\n【記憶點】偵煙式參與時三段蓄積「加總」六十秒；換成其他探測器只剩二十秒。","蓄積機能的由來：偵煙式探測器對水蒸氣、香菸煙、粉塵與車輛廢氣十分敏感，若煙粒子一進入即輸出火災信號，將產生大量非火災報；非火災報頻繁的後果，是管理權人索性讓警報系統長期停用，真火災時反而全無警報。蓄積的作法，是探測器偵知煙後先不立即輸出，持續確認一段時間，確認煙持續存在才送出火災信號。\n為什麼管「合計」而非單一值：受信總機、中繼器與偵煙式探測器三個環節都可能各自設定蓄積時間，若逐段各設六十秒，總延遲將累積到三分鐘，避難時間被大幅侵蝕。因此法規以每一火警分區蓄積時間之合計六十秒以下為上限；使用其他探測器（定溫式、差動式等熱式）時則縮為二十秒以下——熱式探測器本須等熱量累積才動作，反應已較慢，再加長蓄積等於雙重延遲。\n配套限制：裝置蓄積式探測器或中繼器之火警分區，該分區在受信總機不得有雙信號功能。雙信號是第一信號先局部提示、第二信號才全區鳴動的機制，若與蓄積併用即形成兩層延遲，故明文禁止併用。\n易混淆對照：蓄積「時間」以秒計，探測區域的樑深則以公分計——《各類場所消防安全設備設置標準》第 119 條規定探測區域指探測器裝置面之四周以淨高四十公分以上之樑或類似構造體區劃包圍者，但差動式分布型及偵煙式探測器，其裝置面之四周淨高應為六十公分以上。同樣是六十，一個是秒、一個是公分。\n相關考點連結：本考點常與第 112 條火警分區劃定（每一分區不得超過一樓層、樓地板面積六百平方公尺以下、任一邊長五十公尺以下；上下二層樓地板面積之和在五百平方公尺以下者得二層共用一分區）併同出題，因為蓄積時間的管制單位正是「每一火警分區」，分區劃錯，蓄積時間的計算基準也跟著錯。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-010","依各類場所消防安全設備設置標準第 23 條規定，各類場所均應設置避難指標。但設有以下那一個設備時，在其有效範圍內，得免設置避難指標？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-012","有關光電式分離型探測器光軸，下列設置規定何者正確？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-009","以下有關各類場所消防安全設備設置標準對火警分區的規定，何者錯誤？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-013","依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-008","當差動式分布型探測器為空氣管式時，下列那一項的敘述不符合設置標準？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-011",113,"某一場所設有一 A 級出口標示燈，其縱向尺度為 0.8 公尺，且未顯示避難方向符號者，請問其步行距離應為多少公尺？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-011",112,"依據火警探測器認可基準之構造及材質規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-011",111,"依各類場所消防安全設備設置標準規定，下列場所何者未強制要求設置 119 火災通報裝置？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-011",110,"特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-011",109,"避難器具設置數量需衡酌場所之收容人數，依各類場所消防安全設備設置標準規定，百貨商場供飲食或休息用場所之收容人數計算，應以該部分樓地板面積除多少？",1785129965102]