[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-038","fire-106-1-water-chemical-038",106,1,38,"乾粉全區放射所核算之滅火藥劑量須於幾秒內放射完畢？",{"A":16,"B":17,"C":18,"D":19},"20","30","60","210","B",null,[],false,"本題考點：乾粉滅火設備全區放射方式的放射時間上限，屬設置標準明定的固定秒數。\n【正解理由】依《各類場所消防安全設備設置標準》第 99 條，乾粉滅火設備之加壓或蓄壓用氣體容器與放射規定中，全區放射方式或局部放射方式所核算之滅火藥劑量，須於三十秒內全部放射完畢，故選 B。\n【逐項排除】\n(A) 20：無此規定。20 秒過短，換算所得質量流率將使主管與支管管徑、加壓用氣體量不合理放大，條文未作此要求。\n(B) 30：正是條文明定的秒數。乾粉靠負觸媒作用抑制燃燒連鎖反應，粉體停止噴射即迅速沉降，必須在極短時間內於防護區劃內建立足夠粉體濃度，故訂三十秒。\n(C) 60：這是二氧化碳滅火設備全區放射方式的放射時間量級（一般一分鐘內），藥劑種類與滅火機制均與乾粉不同，屬跨設備誤植。\n(D) 210：即七分鐘，是二氧化碳設備防護電信機械室、總機室等深層火災之放射時間，對象與機制皆非乾粉。\n【記憶點】乾粉「三十秒放完」，二氧化碳一分鐘、深層火災七分鐘。","乾粉滅火設備的放射時間之所以訂得比氣體系統短，關鍵在滅火機制與藥劑行為。乾粉（第一種碳酸氫鈉、第二種碳酸氫鉀、第三種磷酸二氫銨、第四種碳酸氫鉀與尿素反應物）主要靠粉體表面吸附自由基、切斷燃燒連鎖反應的負觸媒作用，輔以吸熱分解與遮蔽輻射。粉體一旦停止噴射便迅速沉降，無法像氣體那樣長時間維持均勻濃度，因此必須在短時間內一次建立滅火濃度，三十秒是設計上兼顧管系可行性與滅火效果的分界。\n這個秒數同時決定了整套系統的水力（氣力）設計：藥劑量除以三十秒即為所需質量流率，再由此回推主管、支管管徑、噴頭孔徑與加壓用氣體量。加壓式須有加壓用氣體容器與定壓動作裝置，待容器內壓達設定值才開啟放出閥；蓄壓式則平時即與藥劑同槽蓄壓，容器內壓通常以壓力指示計監控。條文另定加壓用或蓄壓用氣體使用氮氣或二氧化碳，且蓄壓式應設指示壓力範圍的壓力表。\n易混淆數值對照整理：乾粉全區、局部放射 30 秒內放射完畢；二氧化碳全區放射一般於 1 分鐘內、深層火災（電信機械室等）於 7 分鐘內且 2 分鐘內達設計濃度 30%；泡沫則以放射時間與泡沫水溶液量共同界定。看到 210 秒要立刻聯想到二氧化碳的 7 分鐘，這是命題者最常安排的交叉誘答。\n相關考點連結：同一條文常延伸考乾粉各種類每立方公尺所需藥劑量、局部放射方式面積法與體積法的計算，以及乾粉與二氧化碳在通信機械室、汽車修理廠等場所的適用性比較。乾粉的種類記憶亦常入題：第一種主成分碳酸氫鈉（白色）、第二種碳酸氫鉀（紫色）、第三種磷酸二氫銨（粉紅色，適用 A、B、C 三類火災，故稱 ABC 乾粉）、第四種為碳酸氫鉀與尿素之反應物；其中僅第三種因受熱生成偏磷酸能在固體表面形成熔融被覆層，才對普通火災有效，其餘僅適用油類與電氣火災。這組顏色與適用類別的對照，配合三十秒的放射時間，是乾粉單元最常被一併命題的組合。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-037","消防幫浦之全閉揚程應為性能曲線上全揚程之百分之多少以下，方符合檢修基準要求？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-039","泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-036","低壓式二氧化碳噴頭之放射壓力為每平方公分多少公斤以上？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-040","有一長 15 公尺、寬 12 公尺及高 3 公尺之密閉空間裝置二氧化碳滅火設備，假設空氣中氧氣之體積百分率濃度為 21%，在溫度壓力固定下，欲使氧氣濃度降至 15%以下，需注入多少立方公尺之二氧化碳？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-035","乾式比濕式系統的撒水頭數量應追加百分之多少？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-107-1-water-chemical-001","撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",107,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-038",113,"依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-038",112,"依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-038",111,"一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-038",110,"依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-038",109,"消防專用蓄水池之設置規定，下列何者正確？",1785129973609]