[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-034","fire-106-1-water-chemical-034",106,1,34,"第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",{"A":16,"B":17,"C":18,"D":19},"0.6","0.8","1","1.2","A",null,[],false,"本題考點：乾粉滅火設備採全區放射方式時，各種乾粉藥劑每單位體積所需之滅火藥劑量。\n【正解理由】依《各類場所消防安全設備設置標準》第 98 條所列全區放射方式滅火藥劑量表，第一種乾粉（碳酸氫鈉）每立方公尺防護區劃體積所需藥劑量為 0.6 公斤，第二種與第三種乾粉為 0.36 公斤，第四種乾粉為 0.24 公斤，故選 A。第一種乾粉滅火效能相對較低，故單位體積所需量最大。\n【逐項排除】\n(A) 正確。0.6 為第一種乾粉全區放射方式每立方公尺所需藥劑量，是四種乾粉中數值最高者。\n(B) 0.8 並非表列之乾粉單位藥劑量，屬把數值向上取整所設計的干擾項。\n(C) 1 為整數化的誤記，乾粉單位藥劑量均小於 1，與表列數值不符。\n(D) 1.2 剛好是 0.6 的兩倍，常見於將全區放射與開口部加算量重複計入的錯誤思路，非表列基準值。\n【記憶點】乾粉全區放射單位藥劑量由多到少：第一種 0.6、第二三種 0.36、第四種 0.24。","乾粉滅火設備的藥劑量計算採「防護區劃體積×單位體積藥劑量＋開口部面積×開口部加算量」的結構，本題問的是前一項的基準值。四種乾粉之所以數值不同，來自滅火效能的差異：第一種為碳酸氫鈉，受熱分解吸熱並釋出二氧化碳，同時粉粒抑制燃燒連鎖反應，效能為基準；第二種為碳酸氫鉀，鉀離子對連鎖反應的抑制效果優於鈉離子，用量因而可降低；第三種為磷酸二氫銨，即 ABC 乾粉，能在固體表面形成熔融被覆層，適用範圍最廣；第四種為碳酸氫鉀與尿素之反應物，效能最佳，用量最少。把「效能愈好、用量愈少」的邏輯記住，就不必硬背四個小數。\n開口部加算是同一條文的配套規定：全區放射方式的防護區劃，開口部原則上應於藥劑放射前自動關閉；未能自動關閉且面積在一定比例以下者，須按開口部面積乘以規定加算量補足藥劑量。若把加算量誤當成基準值的一部分，就會算出兩倍的錯誤答案，這正是本題干擾項的設計來源。\n另一組必須分辨的是全區與局部：局部放射方式的乾粉藥劑量以防護對象表面積或假想空間體積另行核算，係數與全區放射完全不同；而放射時間方面，乾粉滅火設備要求核算所得藥劑量須在規定時間內放射完畢，蓄壓式與加壓式的加壓氣體、定壓動作裝置與清洗裝置規定亦不相同。\n延伸考點包括：蓄壓式乾粉滅火設備壓力表的指示範圍與檢查、加壓用氣體採氮氣或二氧化碳時的用量規定、以及配管應為專用並防止藥劑沉積的構造要求。\n※ 乾粉滅火設備條文近年曾有修正，條號請以現行法規為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-033","二氧化碳局部放射方式依規定所核算之滅火藥劑量，應於多少秒內全部放射完畢？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-035","乾式比濕式系統的撒水頭數量應追加百分之多少？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-032","二氧化碳全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有多少秒以上之遲延裝置？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-036","低壓式二氧化碳噴頭之放射壓力為每平方公分多少公斤以上？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-031","B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-037","消防幫浦之全閉揚程應為性能曲線上全揚程之百分之多少以下，方符合檢修基準要求？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-034",113,"蓄壓式鹵化烴滅火藥劑儲存容器使用水平液面計之方法進行滅火藥劑量性能檢查，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-034",112,"有關自動撒水設備免設撒水頭處所得設置補助撒水栓之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-034",111,"第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-034",110,"依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-034",109,"乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",1785129973577]