[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-032","fire-106-1-water-chemical-032",106,1,32,"二氧化碳全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有多少秒以上之遲延裝置？",{"A":16,"B":17,"C":18,"D":19},"10","20","30","60","B",null,[],false,"本題考點：二氧化碳滅火設備全區放射方式之安全裝置，其遲延裝置的最短法定秒數。\n【正解理由】依《各類場所消防安全設備設置標準》第 96 條，二氧化碳滅火設備採全區放射方式者，應設安全裝置：自啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟間，應設有 20 秒以上之遲延裝置，並於該時間內連動音響警報裝置，使防護區劃內人員得以避難，故選 B。二氧化碳以稀釋氧氣窒息滅火，對人員具有致命風險，遲延時間是保命設計。\n【逐項排除】\n(A) 10 秒不足以讓人員自防護區劃內辨識警報並完成避難，低於條文所定之下限。\n(B) 正確。20 秒以上之遲延，是條文明定供人員撤離與確認的最短緩衝時間。\n(C) 30 秒是局部放射方式滅火藥劑應放射完畢的時間規定，屬放射時間而非遲延時間，兩者常被互換設陷阱。\n(D) 60 秒為全區放射方式部分場所滅火藥劑放射完畢的時間量級，同樣屬放射時間，與啟動前的遲延裝置無關。\n【記憶點】二氧化碳全區放射「先響 20 秒再放藥劑」，遲延是給人跑，不是給藥劑放。","二氧化碳滅火設備的所有安全規定，都源於同一個事實：它靠降低防護區劃內氧氣濃度達到窒息滅火，而能讓火熄滅的濃度對人體同樣是致命的，且二氧化碳無色無味，人員不易察覺。因此條文圍繞「不讓人被關在裡面」設計了一整組措施：啟動後至容器閥開啟間設 20 秒以上遲延裝置並連動音響警報；防護區劃的開口部應能於藥劑放射前自動關閉；設有手動與自動切換裝置並在明顯處標示所在狀態；出入口與其附近標示放射中的警示燈與警告牌；以及儲存容器室、選擇閥與配管的相關安全要求。把這些條文當成一條「避難時間軸」來記，比逐條硬背有效。\n放射時間則屬另一組數值，最常與遲延時間混淆。全區放射方式依防護對象性質有不同的放射完畢時間要求，通信機器室等需快速抑制者時間較短，可燃性固體等深層火災則允許較長；局部放射方式則要求核算藥劑量於 30 秒內全部放射完畢，因為局部放射靠的是短時間高濃度覆蓋。建議記成三層：啟動前遲延 20 秒以上、局部放射 30 秒內放完、全區放射依用途另計。\n易混淆概念還有全區與局部之別：全區放射針對整個防護區劃、要求開口部可關閉並維持設計濃度；局部放射針對特定機具或液面，藥劑量按防護對象表面積或體積另行核算。此外，二氧化碳與惰性氣體、鹵化物滅火設備在藥劑量、放射時間與人員安全規定上各有差異，考題常刻意跨設備混用數值。\n數值由來上，二氧化碳滅火所需的設計濃度通常在三成上下甚至更高，而人在氧濃度被稀釋到相當程度時，數十秒內即可能失去行動能力，這是遲延時間必須以「秒」而非「分」為單位設計的原因：時間拉太長會讓火勢在藥劑抵達前擴大，太短則人來不及離開，20 秒是兩難之間的法定折衷點。\n※ 氣體系滅火設備條文近年曾有修正，條號請以現行法規為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-031","B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-033","二氧化碳局部放射方式依規定所核算之滅火藥劑量，應於多少秒內全部放射完畢？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-030","第一種感度之撒水頭其反應時間指數（RTI）應小於多少 (ms) ？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-034","第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-029","10 型乾粉滅火器乾粉充填量約為多少公斤重？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-035","乾式比濕式系統的撒水頭數量應追加百分之多少？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-032",113,"某電信機房使用二氧化碳滅火系統，其配管規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-032",112,"依各類場所消防安全設備設置標準規定，下列何者應設置消防專用蓄水池？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-032",111,"二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-032",110,"公共危險物品等場所消防設計及消防安全設備，有關設置冷卻撒水設備規定，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-032",109,"二氧化碳滅火設備採用移動放射方式時，每一具噴射瞄子所需滅火藥劑量在多少公斤以上？",1785129973569]