[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-031","fire-106-1-water-chemical-031",106,1,31,"B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",{"A":16,"B":17,"C":18,"D":19},"1","2","3.2","6","D",null,[],false,"本題考點：滅火器 B 類（油類火災）滅火效能值數字與試驗油盤面積之換算關係。\n【正解理由】依滅火器認可基準之滅火效能值試驗方法，B 類火災之能力單位以標準油盤模型測試決定，其滅火效能值數字乘以 0.2 平方公尺即為該滅火器可撲滅之油盤面積。B-30 者代入得 30×0.2＝6 平方公尺，故選 D。這個係數來自試驗用第一模型油盤的規格設計，使能力值與可滅火面積維持線性對應。\n【逐項排除】\n(A) 1 平方公尺對應之滅火效能值約為 B-5，遠低於本題所給之 B-30。\n(B) 2 平方公尺對應約 B-10，是一般 10 型手提式乾粉滅火器常見的能力級距，並非 B-30。\n(C) 3.2 平方公尺並非 0.2 平方公尺之整數倍所得的常見對應值，屬以小數設計的干擾項。\n(D) 正確。30×0.2 平方公尺＝6 平方公尺，符合 B 類滅火效能值與油盤面積的換算規則。\n【記憶點】B 類效能值乘以 0.2 就是可滅的油盤面積：B-30 對應 6 平方公尺。","滅火效能值不是廠商自行標示的行銷數字，而是實際做火災模型試驗跑出來的結果。A 類火災以木材堆垛模型測試，能力值以能撲滅的模型數量計；B 類火災則以裝有一定深度可燃液體的方形油盤為模型，油盤面積按級距放大，滅火器須在規定時間內完全撲滅且不得復燃，才承認該級距。由於各級油盤面積按固定增量設計，換算上就形成「效能值數字×0.2 平方公尺」的線性關係，這正是考題可以直接心算的原因。C 類火災則不給數字，只標示是否適用電氣火災，因為電氣火災的關鍵是藥劑不導電，而非面積大小。\n這個換算在配置計算上很實用：場所依用途與樓地板面積算出所需滅火效能值總和後，再由各滅火器的標示能力值累加確認是否足夠，同時要確認各層任一點至滅火器的步行距離未超過上限，且不能只靠集中放置的少數大型滅火器充數。\n易混淆對照有三組。第一組是型別與效能值：10 型是瓶身規格，B-10 是滅火能力，數字相同但意義不同。第二組是 A、B、C 三類火災的判定：A 為普通火災、B 為油類火災、C 為電氣火災，另有金屬火災不以此標示。第三組是乾粉種類與適用類別：第一、二種乾粉適用 B、C，第三種磷酸二氫銨才兼顧 A 類。\n延伸考點包括各類場所所需滅火效能值的計算基準（依用途每一定平方公尺一個效能值）、滅火器設置高度與步行距離上限，以及不同藥劑對深層火災與復燃風險的差異。\n把換算反過來用也是常見題型：給定油盤面積求所需最低效能值，即面積除以 0.2。例如 4 平方公尺對應 B-20、10 平方公尺對應 B-50，心算時只要把面積乘以 5 即可，這是同一個係數的倒數形式，考場上比逐項試乘快。命題者偏好用 B-10、B-20、B-30 這類整十級距出題，正是因為換算後恰好落在 2、4、6 平方公尺的整數值，答案不會出現小數；一旦選項出現不是 0.2 倍數的數字，通常就是干擾項。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-030","第一種感度之撒水頭其反應時間指數（RTI）應小於多少 (ms) ？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-032","二氧化碳全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有多少秒以上之遲延裝置？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-029","10 型乾粉滅火器乾粉充填量約為多少公斤重？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-033","二氧化碳局部放射方式依規定所核算之滅火藥劑量，應於多少秒內全部放射完畢？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-028","末端查驗管量測到的壓力為何？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-034","第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-031",113,"依各類場所消防安全設備設置標準規定，二氧化碳滅火設備使用氣體啟動者，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-031",112,"消防幫浦之性能規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-031",110,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-031",109,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",1785129973567]