[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-030":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-030","fire-106-1-water-chemical-030",106,1,30,"第一種感度之撒水頭其反應時間指數（RTI）應小於多少 (ms) ？",{"A":16,"B":17,"C":18,"D":19},"50","80","100","135","A",null,[],false,"本題考點：撒水頭感度分級所用的反應時間指數（RTI）數值界線。\n【正解理由】依撒水頭認可基準對感度之分級，反應時間指數 RTI 係以感熱元件在標準氣流條件下達到動作溫度所需時間換算而得，數值愈小代表感熱愈快。第一種感度（快速反應型）之 RTI 應小於 50，第二種感度則為 50 以上未滿 80 之範圍，故選 A。RTI 之正式單位為（公尺·秒）的二分之一次方，本題選項僅列數值。\n【逐項排除】\n(A) 正確。50 為第一種感度即快速反應型撒水頭的 RTI 上限，此類撒水頭多用於需及早抑制火勢的居室與住宅用途。\n(B) 80 為第二種感度的上限值，屬標準反應型的分界，不是第一種感度的界線。\n(C) 100 並非感度分級所採之界線數值，屬以整數設計的干擾項。\n(D) 135 是華氏標示常見的標定動作溫度數值印象，與 RTI 屬完全不同的物理量，不能互相套用。\n【記憶點】RTI 愈小反應愈快：第一種感度小於 50，第二種落在 50 以上未滿 80。","RTI（Response Time Index，反應時間指數）源自感熱元件的集總熱容分析：把感熱元件視為一個具有熱時間常數的物體，其升溫速率取決於周圍熱氣流的溫度與流速，推導後可得 RTI 等於熱時間常數乘以氣流速度的平方根，單位因而成為（公尺·秒）的二分之一次方。這個定義的好處是把元件本身的熱惰性抽離出來，成為與試驗氣流速度無關的固有參數，不同廠牌、不同型式的撒水頭得以在同一尺度上比較。RTI 愈小，代表感熱元件熱容小、散熱面積相對大，能更快追隨周圍氣溫上升而動作。\n感度與動作溫度是兩個獨立參數，最容易被混淆。動作溫度指的是感熱元件熔解或玻璃球破裂的標定溫度，常見有 72 度左右的標準型與更高溫的高溫型，通常依裝置場所平時最高周圍溫度選定；感度則是達到該溫度所需的快慢。同一個標定溫度可以有快速反應與標準反應兩種版本，設計時是兩個維度一起考慮。\n易混淆概念另有密閉式與開放式之別：密閉式撒水頭本身具感熱元件，才有 RTI 與動作溫度可言；開放式撒水頭無感熱元件，由探測器或感知撒水頭連動一齊放水，設於舞台等需大面積同時放水之處，自然不涉及感度分級。此外，密閉式又分濕式、乾式與預動式，管內是否常時充水影響放水延遲，這與撒水頭感度是兩個不同層次的反應時間。\n延伸考法包括：快速反應型撒水頭在住宅用途的適用、撒水頭裝置面下方的迴水板與樓板距離、以及有無妨礙感熱與放水之障礙物等設置要件。\n命題角度看，RTI 題型的陷阱幾乎都落在「單位」與「大小方向」兩處：RTI 的單位是（公尺·秒）的二分之一次方，不是毫秒，選項若寫成 ms 純屬形式上的簡寫，不影響數值判斷；而「數值愈小＝反應愈快」與一般人直覺的「數字大比較強」相反，作答時務必先在心裡把方向確定下來。另可一併記住感度與裝置高度、集熱板等設計手段的關係：當裝置面過高或熱氣流難以聚集時，選用低 RTI 的快速反應型有助縮短動作時間，這也是命題者喜歡把感度與設置條件綁在一起出情境題的原因。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-029","10 型乾粉滅火器乾粉充填量約為多少公斤重？",29,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-031","B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",31,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-028","末端查驗管量測到的壓力為何？",28,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-032","二氧化碳全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有多少秒以上之遲延裝置？",32,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-027","依各類場所消防安全設備設置標準，連結送水管之出水口設置，下列敘述何者錯誤？",27,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-033","二氧化碳局部放射方式依規定所核算之滅火藥劑量，應於多少秒內全部放射完畢？",33,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-030",113,"鹵化烴滅火設備全區放射綜合檢查時，檢查方法、判定方法及注意事項，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-030",112,"消防幫浦之防止水溫上升用排放裝置，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-030",111,"有關消防安全設備檢修完成標示附加位置，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-030",110,"公共危險物品等場所消防設計及消防安全設備，其他滅火困難場所，應設置第幾種滅火設備？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-030",109,"泡沫滅火設備計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之多少？",1785129973557]