[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-028","fire-106-1-water-chemical-028",106,1,28,"末端查驗管量測到的壓力為何？",{"A":16,"B":17,"C":18,"D":19},"全壓","動壓","靜壓","高壓","C",null,[],false,"本題考點：自動撒水設備末端查驗管所設壓力表，量測到的是何種壓力性質。\n【正解理由】依《各類場所消防安全設備設置標準》第 50 條，密閉式撒水設備應設末端查驗閥（管），管末端接裝限流孔與壓力表，用以確認最遠、最高處配管內是否維持規定之壓力。平時查驗管閉止、管內水未流動，壓力表所指示者即為靜止狀態下的水壓，也就是靜壓，故選 C。\n【逐項排除】\n(A) 全壓為靜壓與動壓之總和，須在水流動且以皮托管等方式同時取得速度水頭時才談得上，查驗管平時無流速可言。\n(B) 動壓由流速產生（與流速平方成正比），必須在水流出時才存在；末端查驗管平時關閉，測得的並非流動狀態下的壓力。\n(C) 正確。管路靜止、水不流動時，壓力表反映的是配管內水壓與高程水頭形成的靜壓，可據以確認最不利點是否仍達規定壓力。\n(D) 高壓並非流體力學上的壓力分類名稱，只是相對高低的形容，不是壓力表所測的壓力性質。\n【記憶點】末端查驗管平時不流動，測得的是靜壓；要看動壓得等水放出來。","壓力的分類是水系統各題型的共同底層概念。柏努利方程式把單位重量流體的能量分成三項：壓力水頭、速度水頭與位置水頭。靜壓對應壓力水頭，是流體靜止或與流線垂直方向所測得的壓力；動壓對應速度水頭，等於流速平方除以二倍重力加速度換算成的壓力；兩者相加為全壓（總水頭）。管路關閉、水不流動時速度為零，動壓自然消失，只剩靜壓，這就是本題的物理基礎。\n單位換算是這一族題型的必備工具：1 kgf\u002Fcm² 約等於 10 公尺水頭，約等於 0.098 MPa，實務上常近似取 0.1 MPa。撒水頭放水壓力要求在 1 kgf\u002Fcm² 以上、10 kgf\u002Fcm² 以下，換算即約 0.1 MPa 至 1 MPa，也就是約 10 至 100 公尺水頭。設置末端查驗管的用意，正是在系統最不利點（配管最遠或最高處）確認靜壓不致低於下限，以及在必要時模擬一個撒水頭放水的流量，檢視流水檢知裝置與警報是否正常動作。\n易混淆對照有兩組。其一是靜壓與放水壓力：查驗管平時讀到的是靜壓，真正開啟查驗閥放水時，壓力表讀值會下降到接近該點的放水壓力，兩者不可混為一談。其二是末端查驗管與流水檢知裝置：前者是查驗用的管路末端，後者是偵測水流並發出警報的元件，兩者搭配才能完成一次完整的動作確認。\n同一觀念的延伸考法包括限流孔孔徑應與最小放水量之撒水頭同等、查驗管應設於流水檢知裝置或壓力檢知裝置最遠支管末端、以及放水試驗時應確認壓力與流量是否符合設計值等敘述題。\n※ 撒水設備條文近年曾有修正，條號請以現行法規為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-027","依各類場所消防安全設備設置標準，連結送水管之出水口設置，下列敘述何者錯誤？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-029","10 型乾粉滅火器乾粉充填量約為多少公斤重？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-026","消防專用蓄水池至建築物各部分之水平距離，應在多少公尺以下？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-030","第一種感度之撒水頭其反應時間指數（RTI）應小於多少 (ms) ？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-025","某一防護對象物長寬高分別為 5 公尺、4 公尺及 1 公尺，若以高發泡局部放射泡沫滅火系統進行防護，依各類場所消防安全設備設置標準之規定，其防護面積應為多少平方公尺？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-031","B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-028",113,"下列場所之消防安全設備設置何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-028",112,"有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-028",111,"依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-028",110,"消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-028",109,"水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",1785129973549]