[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-018":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-018","fire-106-1-water-chemical-018",106,1,18,"公共危險物品等場所設置自動撒水設備時，使用密閉式撒水頭其水源容量，應在設置 X 個撒水頭繼續放水 Y 分鐘之水量以上，其中 X、Y 分別為：",{"A":16,"B":17,"C":18,"D":19},"X=30，Y=30","X=30，Y=20","X=20，Y=20","X=20，Y=30","A",null,[],false,"本題考點：公共危險物品等場所設置自動撒水設備時，密閉式撒水頭之水源容量計算基準，即同時放水撒水頭個數與持續放水時間。\n【正解理由】依《各類場所消防安全設備設置標準》公共危險物品場所自動撒水設備專章之規定，使用密閉式撒水頭者，其水源容量應在設置三十個撒水頭繼續放水三十分鐘之水量以上；亦即 X = 30、Y = 30。此標準明顯高於一般場所(依樓層與用途多為十個至十五個、放水二十分鐘),原因在於公共危險物品的火載量與燃燒速率遠高於普通可燃物，故選 A。\n【逐項排除】\n(A) 正確，三十個撒水頭、三十分鐘，兩項數值皆與公共危險物品場所之加嚴基準相符。\n(B) 撒水頭個數 30 正確，但放水時間寫成二十分鐘，誤套一般場所的持續時間。\n(C) 兩項數值都退回一般場所的量級，二十個、二十分鐘皆低於本專章要求，水量嚴重不足。\n(D) 放水時間三十分鐘正確，但同時放水個數寫成二十個，水源容量只剩法定的三分之二。\n【記憶點】公共危險物品場所的密閉式撒水頭，個數與時間都是「三十」,雙三十一起記最不會錯。","公共危險物品等場所的消防安全設備，在設置標準中自成專章，原則是「同一種設備、更嚴的參數」。以自動撒水設備為例，一般場所的水源容量依用途與樓層，約為十個至十五個撒水頭放水二十分鐘；到了公共危險物品場所，直接拉高為三十個撒水頭放水三十分鐘。以標準撒水頭放水量每分鐘 80 公升粗估，三十個同時放水三十分鐘相當於 80 × 30 × 30 = 72,000 公升，即 72 立方公尺，是一般場所的數倍，這也是為什麼此類場所往往需要獨立的大型消防水池。\n\n加嚴的立法理由來自燃燒特性。第四類公共危險物品(易燃液體)一旦起火，火焰傳播速度快、熱釋放率高，且液面火災容易再引燃；撒水設備在此的角色除了滅火，更重要的是冷卻與抑制延燒，必須維持足夠長的放水時間直到消防人員到場處置。三十分鐘的設定，對應的正是這種「撐到外援」的思維，與室外消防栓的三十分鐘同源。\n\n易混淆點有二。其一是同專章中不同設備的參數並不一致：移動式泡沫滅火設備的水源容量是四具瞄子同時放水三十分鐘，水霧與固定式泡沫又另有規定，不可互相套用。其二是「三十個」指的是同時放水的撒水頭數量，不是場所實際設置的撒水頭總數；實際設置一百個撒水頭，水源仍以三十個計算，這與室外消防栓「二支」的邏輯完全相同——法規計算的是最不利的同時使用情境，而非全數動作。\n\n記憶上可以建立一組「三十家族」:公共危險物品場所密閉式撒水頭三十個、放水三十分鐘；移動式泡沫四具三十分鐘；室外消防栓二支三十分鐘。凡是牽涉公共危險物品或室外大空間，時間一律往三十分鐘靠；一般建築物室內設備才是二十分鐘。\n\n同一專章的延伸考點包括：設置自動撒水設備的公共危險物品場所類型與數量倍數門檻、開放式撒水設備的放水區域劃分，以及撒水頭放水壓力(1 kgf\u002Fcm² 以上)與放水量(80 公升\u002F分以上)的下限，這些常與水源容量搭配成綜合題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-017","有關撒水頭之設置，下列敘述何者錯誤？",17,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-019","進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",19,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-016","自動撒水設備竣工時進行加壓試驗，下列何者正確？",16,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-020","水霧滅火設備之加壓送水裝置使用消防幫浦時，其出水量及出水壓力，下列敘述何者錯誤？",20,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-015","某一高度危險工作場所，其建築物外面設有 4 具室外消防栓，則其水源容量至少應為多少？",15,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-021","裝置水霧滅火設備之室內停車空間，其排水設備應符合之規定，下列何者錯誤？",21,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-018",113,"有關泡沫滅火設備泡沫放射試驗判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-018",112,"乾粉滅火設備使用蓄壓用氣體容器，若氣體使用氮氣時，在溫度 35℃，大氣壓力（表壓力） 0 kg\u002Fcm2 狀態下，除加算清洗配管所需要量外，每一公斤乾粉藥劑需氮氣之量為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-018",111,"依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-018",110,"有關滅火器設置規定，下列何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-018",109,"移動式泡沫滅火設備進行綜合檢查作業時，發泡倍率應在幾倍以上？",1785129973476]