[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-012","fire-106-1-water-chemical-012",106,1,12,"簡易自動滅火設備進行性能檢查時，其蓄壓式滅火藥劑量應與標示重量差異在何範圍以內？",{"A":16,"B":17,"C":18,"D":19},"3%","5%","10%","15%","A",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》中簡易自動滅火設備性能檢查，蓄壓式滅火藥劑量與標示重量的容許差異。\n【正解理由】簡易自動滅火設備主要設於營業用廚房的排油煙罩與煙道，以撲滅油鍋火災為目的，其藥劑量若短少將直接影響滅火效能。依《消防安全設備檢修及申報作業基準》有關簡易自動滅火設備性能檢查之規定，蓄壓式者應以秤重方式確認滅火藥劑量，其與容器上標示重量之差異應在 3% 以內，超出即判定不良而須處置。此值訂得比多數項目嚴格，是因本設備藥劑總量本就不大，數個百分點的短少在絕對量上即足以使噴頭放射不足，故選 A。\n【逐項排除】\n(A) 正確：蓄壓式滅火藥劑量以秤重確認，與標示重量之差異應在 3% 以內。\n(B) 5% 高於基準所定容許值，屬過寬的判定標準，會讓已短少的藥劑量被判為合格。\n(C) 10% 常被誤植自其他設備的藥劑量或水量容許範圍，與本項規定不符。\n(D) 15% 差異過大，若真容許此誤差，藥劑量將明顯不足以達成設計滅火效果。\n【記憶點】簡易自動滅火設備蓄壓式秤重，誤差不得超過 3%。","簡易自動滅火設備是專為商業廚房設計的小型固定式系統，防護對象是排油煙罩、濾網、煙道與油炸設備。廚房火災的特殊性在於食用油閃火點與著火點高、蓄熱量大，一旦起火極易復燃，且火勢會沿油污附著的煙道向上蔓延，因此這類系統多採用可與油脂皂化反應的滅火藥劑，藉由在油面形成皂化膜隔絕氧氣並同時冷卻，達到防止復燃的效果，這也是它不能用一般水系設備取代的原因。\n\n藥劑量以「秤重」判定而非目視，是因為蓄壓式容器封閉且藥劑多為液態，唯有總重量能反映實際存量；容許差異訂在 3%，比其他許多項目嚴格，理由在於本系統藥劑總量本就不大，百分之幾的短少在絕對量上就足以使某支噴頭放射不足。檢查時尚須確認容器有無變形、腐蝕，壓力指示值是否落在規定範圍，探測部（多為感知油煙罩溫度的機械式或熔絲式構件）動作溫度是否正常，以及與瓦斯遮斷裝置的連動是否確實——起火時若燃氣未同時遮斷，滅火後仍可能立即復燃，這條連動是本設備的靈魂。\n\n常見易混數值可放在一起對照記憶：簡易自動滅火設備蓄壓式藥劑量差異 3% 以內；乾粉滅火設備性能檢查於溫度 40℃ 以上或濕度 60% 以上時暫停；鹵化烴遲延裝置 20 秒以上。這幾個數值同屬檢修基準，卻分屬不同設備，命題者常在同一份試卷中連續設題，逐一建立「設備—項目—數值」三段式記憶最不易混淆。\n\n延伸考點包括：簡易自動滅火設備的設置場所要件、噴頭配置須涵蓋油炸設備表面與濾網、藥劑放射後應清洗管路以防殘留物固結，以及與排油煙設備停止機構的關聯，這些在綜合檢查項目中都會被一併驗證。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-011","鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",11,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-013","有關室內消防栓之放水壓力，下列何者錯誤？",13,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-010","一汽車修理廠欲採用移動式乾粉滅火設備，則其外牆開口面積（常時開放部分）須符合下列那一規定？",10,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-014","達顯著滅火困難之公共危險物品室外儲存場所，設置室外消防栓設備，其緊急電源應使用發電機設備或蓄電池設備，供電容量應供其有效動作至少多久以上？",14,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-009","如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",9,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-015","某一高度危險工作場所，其建築物外面設有 4 具室外消防栓，則其水源容量至少應為多少？",15,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-012",113,"自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-012",112,"依據滅火器認可基準規定，由滅火器所充填之滅火藥劑量判別，下列何者屬大型滅火器？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-012",111,"有關水霧滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-012",110,"進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-012",109,"消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",1785129973447]