[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-010","fire-106-1-water-chemical-010",106,1,10,"一汽車修理廠欲採用移動式乾粉滅火設備，則其外牆開口面積（常時開放部分）須符合下列那一規定？",{"A":16,"B":17,"C":18,"D":19},"達該層樓地板面積 15%以上","達該層圍壁面積 10%以上","達該層防護區體積 10%以上","達該層牆壁總面積 15%以上","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》關於移動式乾粉滅火設備適用場所之限制，核心在外牆常時開放部分的開口面積比例。\n【正解理由】移動式滅火設備是由人員持軟管進入現場操作，藥劑放射時若煙與熱蓄積於室內、能見度惡化，操作人員將無法接近火點，故法規限定僅能設於通風良好、火災時濃煙不易滯留之場所。依《各類場所消防安全設備設置標準》關於移動式乾粉滅火設備之設置規定，該場所外牆常時開放部分之開口面積，須達該層樓地板面積 15% 以上，方得採用移動式，故選 A。\n【逐項排除】\n(A) 正確：以該層樓地板面積為基準，常時開放之外牆開口面積須達 15% 以上。\n(B) 達該層圍壁面積 10% 以上，基準面選成圍壁面積且比例為 10%，兩者皆與規定不符。\n(C) 達該層防護區體積 10% 以上，把面積與體積混為一談，量綱即不成立。\n(D) 達該層牆壁總面積 15% 以上，比例雖為 15%，但基準面應為樓地板面積而非牆壁總面積。\n【記憶點】移動式要通風，開口達樓地板面積 15% 才准用。","固定式與移動式的分野，是滅火設備體系裡最容易被忽略卻常被命題的結構性概念。固定式（含全區放射與局部放射）由探測、啟動裝置自動連動，人員不必進入火場；移動式則是把藥劑儲存容器、皮管與噴嘴設於現場，由人員手動拉管靠近火點射放，性質接近大型滅火器。正因為要靠人接近，法規才對「煙不會困住人」設下量化門檻——外牆常時開放部分達樓地板面積 15% 以上，等於保證該空間有足夠的自然排煙與通風開口，濃煙與滅火藥劑不至於在室內滯留。汽車修理廠、停車空間這類多為大開口、車輛頻繁進出的場所，正是移動式的典型適用對象。\n\n「常時開放」四個字是關鍵限定：可開啟但平時關閉的門窗不算，必須是隨時保持開放狀態的開口才能計入。這一點與全區放射方式的「開口部須能於放射前自動關閉」恰成相反邏輯——全區放射要密閉才能建立濃度，移動式反而要開放才能保護人員，兩者的設計哲學互為鏡像，把這組對比記起來，答題時就不會反向套用。\n\n移動式乾粉的其他規格也屬同一組考點：藥劑量與每分鐘噴射量依乾粉種類分列，第一種、第二種、第三種、第四種各有不同數值；皮管長度須能有效涵蓋防護對象各部分；儲存容器應設於火災時濃煙不易滯留、便於接近且無操作障礙之處，並標示「移動式乾粉滅火設備」字樣。二氧化碳與鹵化烴的移動式設備亦有平行規定，數值不同但架構相同。\n\n延伸而言，移動式因需人員操作，通常不設遲延裝置與自動關閉開口裝置，也不需計算防護區域體積係數，這使它在計算題中被排除在藥劑量公式之外，遇到題目出現「移動式」三字時，應立刻切換到另一套規範思路。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-009","如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-011","鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-008","乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-012","簡易自動滅火設備進行性能檢查時，其蓄壓式滅火藥劑量應與標示重量差異在何範圍以內？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-007","依各類場所消防安全設備設置標準，二氧化碳滅火設備之藥劑放射時間，下列何者正確？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-013","有關室內消防栓之放水壓力，下列何者錯誤？",13,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-010",113,"有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-010",112,"水霧滅火設備係利用特殊水霧噴頭，使水呈微粒霧狀及特定角度、形狀噴出，並均勻地覆蓋燃燒表面，達到滅火效果。下列何者非水霧滅火設備針對油類火災之滅火作用與原理？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-010",111,"樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-010",110,"實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-010",109,"全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",1785129973432]