[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-009","fire-106-1-water-chemical-009",106,1,9,"如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",{"A":16,"B":17,"C":18,"D":19},"5","10","15","20","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》中乾粉滅火設備配管之設置要求，特別是彎曲部分與其他部分之距離倍數，用意在防止乾粉與加壓氣體分離。\n【正解理由】乾粉在配管內是以加壓氣體帶動的氣固兩相流動，粉體密度遠大於氣體，一旦流經彎頭產生離心作用，粉粒會被甩向外側管壁而與載送氣體分層，造成放射量不足或阻塞。為此，《各類場所消防安全設備設置標準》關於乾粉滅火設備配管之規定明定，除另有防止乾粉與加壓氣體分離之有效措施外，配管任一部分與彎曲部分之距離，應在管徑 20 倍以上，以保留足夠直管長度讓兩相重新混合均勻，故選 D。\n【逐項排除】\n(A) 5 倍管徑的直管長度過短，粉氣分層尚未恢復即進入下一個管件，不符規定。\n(B) 10 倍管徑仍不足以讓氣固兩相重新均勻混合，非本條所定倍數。\n(C) 15 倍管徑是常見的干擾數值，接近但仍低於法定要求。\n(D) 正確：無其他防止分離措施時，應保持管徑 20 倍以上之距離。\n【記憶點】乾粉過彎會分家，彎後直管留 20 倍管徑。","這條規定是少見的、把流體力學現象直接寫進法規條文的例子。乾粉滅火設備的輸送本質是稀相氣力輸送：加壓用氣體（多為氮氣或二氧化碳）先進入儲存容器將粉體流化，再推送粉氣混合物經配管至噴頭。粉粒密度約為氣體的數百倍，通過彎頭時因慣性與離心力作用，粒子軌跡偏離流線而集中於彎頭外側，形成所謂粒子繩流；若緊接著就是分歧管、選擇閥或噴頭，各支管取得的粉氣比例會嚴重失衡，導致某些防護區域藥劑不足。保留管徑 20 倍以上的直管段，等於給兩相流一段重新混合的緩衝距離，這也是設計上「彎頭後不立即分歧」的通則來源。\n\n乾粉系統的其他配管要求同屬一組記憶：配管應採專用，管徑與長度應使各噴頭放射壓力與量符合規定；為避免殘留粉體吸濕結塊，系統應設清洗裝置，於放射後以氣體吹除管內殘粉；加壓式者須設定壓動作裝置，使容器內壓達到規定值後放出閥才開啟，確保粉體已充分流化才送出。\n\n加壓式與蓄壓式的差異也是常考對照：加壓式將加壓用氣體另置於加壓用氣體容器，動作時才導入儲存容器，平時儲存容器不承壓，維護上須確認加壓用氣體容器壓力；蓄壓式則平時即以氮氣加壓封存於同一容器內並附壓力指示計，性能檢查時看指針是否落在綠色範圍。兩者在檢修項目與故障型態上完全不同。\n\n延伸命題方向包括：各種乾粉每平方公尺或每立方公尺之藥劑量、移動式乾粉的噴射量與藥劑量、乾粉噴頭之放射壓力，以及全區與局部放射方式的藥劑量計算式。這些數值多以第一種至第四種乾粉分列，作答時先辨明藥劑種類再查數值，是避免張冠李戴的關鍵動作。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-008","乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-010","一汽車修理廠欲採用移動式乾粉滅火設備，則其外牆開口面積（常時開放部分）須符合下列那一規定？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-007","依各類場所消防安全設備設置標準，二氧化碳滅火設備之藥劑放射時間，下列何者正確？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-011","鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-006","全區放射二氧化碳滅火設備進行綜合檢查時，如為低壓式儲存系統，在放射試驗時需放射多少藥劑量？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-012","簡易自動滅火設備進行性能檢查時，其蓄壓式滅火藥劑量應與標示重量差異在何範圍以內？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-009",113,"高度危險工作場所設置室外消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-009",112,"室外儲槽儲存閃火點在 70℃以下之第四類公共危險物品之顯著滅火困難場所，應依規定檢討設置下列何種設備？①補助泡沫消防栓 ②泡沫射水槍滅火設備 ③連結送液口 ④冷卻撒水設備 ⑤固定式泡沫滅火設備",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-009",111,"泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-009",110,"依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-009",109,"進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",1785129973423]