[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-005":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-005","fire-106-1-water-chemical-005",106,1,5,"某一鍋爐房之長寬高分別為 8 m、5 m 及 4 m，若設置全區放射 CO2 滅火設備，其所有開口皆可在放射前自動關閉，試問所需 CO2 藥劑量至少應為多少公斤？",{"A":16,"B":17,"C":18,"D":19},"160","144","135","128","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 82 條全區放射二氧化碳滅火設備的藥劑量計算，關鍵在「體積係數」與「滅火藥劑最低限度基本量」兩道關卡都要過。\n【正解理由】依《各類場所消防安全設備設置標準》第 82 條，電信機械室、總機室以外之一般防護區域，藥劑量依防護區域體積分級：未滿 50 立方公尺為每立方公尺 1.00 公斤、50 以上未滿 150 立方公尺為 0.90 公斤、150 以上未滿 1500 立方公尺為 0.80 公斤；同表另訂各級距最低限度基本量，150 以上未滿 1500 立方公尺者為 135 公斤。本鍋爐房體積 8 × 5 × 4 = 160 立方公尺，落在 0.80 公斤級距，換算得 128 公斤，低於最低限度 135 公斤，應取 135 公斤；開口既能於放射前自動關閉，不必追加開口部藥劑量，故選 C。\n【逐項排除】\n(A) 160 公斤是把體積數值直接當成公斤抄下，未乘任何藥劑量係數，無條文依據。\n(B) 144 公斤誤用 0.90 公斤／立方公尺（50 以上未滿 150 立方公尺之係數）乘以 160，體積級距套錯一格。\n(C) 正確：體積換算 128 公斤未達最低限度 135 公斤，依附表取 135 公斤。\n(D) 128 公斤只做完體積乘係數即交卷，漏掉最低限度那道關卡，為本題主要陷阱。\n【記憶點】二氧化碳藥劑量先乘係數、再比最低量，兩者取大的那個。","二氧化碳滅火設備屬窒息法滅火，全區放射的設計理念是在防護區域內迅速建立足以抑制燃燒的氧濃度下降環境，因此藥劑量規定不是憑經驗抓數字，而是由「防護區域體積 × 單位體積藥劑量」推導。體積越大，牆壁與天花板等界面造成的洩漏比例相對越小，單位體積所需藥劑量因此遞減，這就是附表係數從 1.00、0.90 一路降到 0.80、0.75 公斤／立方公尺的物理由來。但小體積區域若純按比例計算會得到過小的藥劑量，一旦有輕微洩漏或門窗未完全密閉，濃度就撐不住，所以立法另設「最低限度基本量」作為安全下限，本題 135 公斤即由此而來，也是命題者最愛設計的兩層陷阱。\n\n記憶對照可整理成兩欄：體積未滿 50 立方公尺／係數 1.00；50 以上未滿 150／0.90，最低量 50 公斤；150 以上未滿 1500／0.80，最低量 135 公斤；1500 以上／0.75，最低量 1200 公斤。另需留意電信機械室、總機室等以電子設備為主的空間，因需要更高設計濃度且不得損傷設備，單位體積藥劑量另有較高規定，與一般場所分屬不同計算路線，考題常把「鍋爐房」與「總機室」交錯出，判斷屬於哪一類是第一步。\n\n開口部處理是第二個常考點：防護區域若有無法於放射前自動關閉之開口，須就開口面積另按每平方公尺追加一定藥劑量，本題明示開口皆能自動關閉，這句話就是命題者給的免追加訊號；反過來若題目寫「有 2 平方公尺開口無法關閉」，就必須加算。第三個延伸考點是局部放射方式，其藥劑量改依防護對象表面積或假想防護空間體積計算，與全區放射公式完全不同，切勿混用。\n\n儲存方式上還有高壓式與低壓式之別：高壓式常溫下以約 150 kgf\u002Fcm² 級距充填，低壓式則以冷凍裝置維持約零下 18 度、約 21 kgf\u002Fcm² 儲存，兩者在容器閥、安全裝置與檢修項目上的規定不同，也是同一條文延伸出的常見題型。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-004","依滅火器認可基準，大型滅火器充填乾粉時，滅火藥劑量需在多少公斤以上？",4,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-006","全區放射二氧化碳滅火設備進行綜合檢查時，如為低壓式儲存系統，在放射試驗時需放射多少藥劑量？",6,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-003","有關滅火器設置間距之規定，下列何者錯誤？",3,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-007","依各類場所消防安全設備設置標準，二氧化碳滅火設備之藥劑放射時間，下列何者正確？",7,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-002","依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",2,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-008","乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",8,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-005",113,"廚房設置簡易自動滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-005",112,"有關補助撒水栓與第二種室內消防栓之比較，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-005",111,"有關移動式泡沫滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-005",110,"消防幫浦加壓送水裝置之啟動用水壓開關裝置，下列規定何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-005",109,"某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",1785129973404]