[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-106-1-water-chemical-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-002","fire-106-1-water-chemical-002",106,1,2,"依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",{"A":16,"B":17,"C":18,"D":19},"樓地板面積 200 平方公尺之幼兒園","樓地板面積 45 平方公尺之變壓器室","總樓地板面積 120 平方公尺之診所","總樓地板面積 90 平方公尺之咖啡廳","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》滅火器的應設場所判準，考的是甲類場所全面設置、乙類場所以總樓地板面積門檻設置，以及電氣設備處所不論面積均須設置的分野。\n【正解理由】依《各類場所消防安全設備設置標準》第 14 條，滅火器應設於甲類場所(不論面積)、地下建築物、幼兒園，以及總樓地板面積達一定門檻(150 平方公尺)以上之乙類至戊類場所，另設有變壓器、配電盤等電氣設備之處所亦應設置。診所依第 12 條列屬乙類場所，總樓地板面積僅 120 平方公尺，未達門檻，故不需設置，故選 C。\n【逐項排除】\n(A) 幼兒園為條文明列應設滅火器之場所，不受面積限制,200 平方公尺自屬應設，不是答案。\n(B) 變壓器室屬設有變壓器、配電盤等電氣設備之處所，不論樓地板面積大小均應設置滅火器,45 平方公尺仍須設，不是答案。\n(C) 診所屬乙類場所，須總樓地板面積達門檻以上始應設置，本項僅 120 平方公尺未達標準，為不需設置者，即正確答案。\n(D) 咖啡廳屬供飲食之甲類場所，甲類不論面積一律應設滅火器,90 平方公尺仍須設置，不是答案。\n【記憶點】甲類與幼兒園不看坪數、電氣設備處所不看坪數，乙類以下才看面積門檻。","滅火器是設置標準中門檻最低、涵蓋面最廣的滅火設備，其立法邏輯在於「初期滅火靠人、靠手邊器材」。條文設計採三層結構：第一層是高危險、高人流的甲類場所(如飲食店、電影院、旅館、商場、醫院、老人福利機構等)與幼兒園、地下建築物，不論面積一律應設；第二層是乙類至戊類等使用強度較低的場所，以總樓地板面積達門檻為條件；第三層則是不看用途只看設備風險的特殊處所，例如設有變壓器、配電盤等電氣設備之處所，以及鍋爐房、廚房等使用火源處所，面積再小也要設。答對本題的關鍵，就是能立刻判斷各選項落在哪一層。\n\n場所分類的辨識訣竅：甲類的共同特徵是「不特定多數人聚集、避難困難或臥床」;醫院、療養院屬甲類，但診所因規模小、就診者多能自主避難而列乙類——這一組甲乙之分正是本題的核心陷阱，同樣的對比還有「補習班與學校」「旅館與宿舍」,都是命題熱點。\n\n數量計算的延伸考點：應設滅火器的場所還須依潛在火災性質核算最低滅火效能值，一般場所以樓地板面積每 100 平方公尺(含未滿)需 1 滅火效能值計，可燃物較多者加嚴；電影片映演場所放映室及電氣設備使用之處所，每 100 平方公尺(含未滿)另設一滅火器。滅火器並須固定放置於明顯易取之處，設於樓地板面上一定高度以下，並標明所在位置。\n\n概念對照：滅火器屬「滅火設備」中的人為操作器材，與自動撒水設備、水霧、泡沫、二氧化碳、乾粉等自動式滅火設備分屬不同層級；考題常把應設場所表與檢修申報頻率併問，判讀時務必先確認場所類別，再看面積門檻，最後才處理特殊處所的加設規定。",true,[28,31,35,40,43,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-106-1-water-chemical-001","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列何者錯誤？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-106-1-water-chemical-003","有關滅火器設置間距之規定，下列何者錯誤？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-114-1-water-chemical-004","依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",4,114,{"webId":41,"stem":42,"number":38,"year":11,"session":12},"fire-106-1-water-chemical-004","依滅火器認可基準，大型滅火器充填乾粉時，滅火藥劑量需在多少公斤以上？",{"webId":44,"stem":45,"number":46,"year":47,"session":12},"fire-113-1-water-chemical-040","有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",40,113,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-005","某一鍋爐房之長寬高分別為 8 m、5 m 及 4 m，若設置全區放射 CO2 滅火設備，其所有開口皆可在放射前自動關閉，試問所需 CO2 藥劑量至少應為多少公斤？",5,[53,56,60,64,68],{"webId":54,"year":47,"stem":55,"number":13},"fire-113-1-water-chemical-002","室內停車空間設置水霧滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":57,"year":58,"stem":59,"number":13},"fire-112-1-water-chemical-002",112,"依公共危險物品等場所設置之滅火設備分類，自動撒水設備係屬下列何種滅火設備？",{"webId":61,"year":62,"stem":63,"number":13},"fire-111-1-water-chemical-002",111,"有關室外消防栓與室內消防栓之瞄子放水壓力之敘述，下列何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-water-chemical-002",110,"連結送水管之中繼幫浦放水測試時，應從送水口以送水設計壓力送水，並以口徑 21 公厘瞄子在最頂層測試，其放水壓力不得小於 X kgf\u002Fcm2，且放水量不得小於 Y L\u002Fmin。X、Y 分別為何？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-water-chemical-002",109,"某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",1785129973376]