[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-106-1-water-chemical-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-106-1-水與化學系統消防安全設備概要-001","fire-106-1-water-chemical-001",106,1,"依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列何者錯誤？",{"A":15,"B":16,"C":17,"D":18},"FM-200 應在 10 秒以內","IG-541 應在 60 秒以內","IG-55 應在 60 秒以內","Novec 1230 應在 30 秒以內","D",null,[],false,"本題考點：NFPA 2001 潔淨藥劑滅火系統的藥劑放射時間規定，考的是鹵化烷替代品與惰性氣體兩類藥劑放射時間標準的差異，且題目問的是「錯誤」者。\n【正解理由】依 NFPA 2001,一般場所之潔淨藥劑放射時間以達到設計濃度 95% 所需時間為判準，鹵化物類(halocarbon)藥劑因以液態儲存、汽化吸熱滅火，須在 10 秒內完成放射；惰性氣體類(inert gas)因以氣態高壓儲存、靠稀釋氧濃度滅火，放射時間放寬至 60 秒內。Novec 1230 屬鹵化物類，應在 10 秒以內而非 30 秒，敘述錯誤，故選 D。\n【逐項排除】\n(A) FM-200(HFC-227ea)為鹵化物類藥劑，放射時間 10 秒以內，敘述正確，不是本題要找的錯誤選項。\n(B) IG-541 為氮、氬、二氧化碳的混合惰性氣體，放射時間 60 秒以內，敘述正確。\n(C) IG-55 為氮與氬各半的惰性氣體，同屬惰性氣體類，放射時間 60 秒以內，敘述正確。\n(D) Novec 1230(FK-5-1-12)為氟化酮類，歸類為鹵化物藥劑，標準要求 10 秒以內，選項寫 30 秒與規定不符，即為錯誤敘述，是正確答案。\n【記憶點】鹵化物十秒、惰性氣體六十秒——名字帶 IG 的才是那個慢的。","潔淨藥劑滅火系統的規格差異，根源在滅火機制不同。鹵化物類藥劑以液態高壓儲存，放射後迅速汽化，靠汽化吸熱的物理冷卻加上抑制自由基連鎖反應的化學作用滅火，設計濃度通常僅 7%~9%,藥劑量少、管路短，因此規範要求 10 秒內放射完畢——放得慢會讓火勢在藥劑到位前持續成長，且分解產物氟化氫的生成量與暴露時間成正比，快速放射反而能降低毒性副產物。惰性氣體類則靠把氧濃度稀釋到約 12%~14% 使燃燒無法維持，設計濃度高達 35%~50%,需要大量氣體，若同樣要求 10 秒內灌入，防護區劃的洩壓開口與結構將承受不了瞬間壓力，故放寬為 60 秒，並強制設置洩壓口計算。\n\n藥劑辨識可整理成一張對照表:FM-200 即 HFC-227ea、FE-13 即 HFC-23、Novec 1230 即 FK-5-1-12,以上皆屬鹵化物;IG-01 為純氬、IG-100 為純氮、IG-55 為氮氬各半、IG-541 為氮 52%+氬 40%+二氧化碳 8%,以上皆屬惰性氣體，凡名稱以 IG 開頭者一律 60 秒。這組對照是本科最容易失分也最容易拿分的記憶題。\n\n沿革脈絡上，潔淨藥劑是為取代蒙特婁議定書下遭管制的海龍(Halon 1301、1211)而發展；海龍破壞臭氧層，國際自 1994 年起停產，我國亦配合列管，現行《各類場所消防安全設備設置標準》第 82 條以下對海龍與二氧化碳、乾粉滅火設備的放射時間另有規定，考題常將 NFPA 2001 與國內設置標準併問，務必分清楚適用對象。\n\n安全考點：惰性氣體系統放射後區劃內氧濃度顯著下降，鹵化物系統則須留意熱分解產生的氟化氫，兩者皆規定放射前的預警與延遲裝置，以及防護區劃的洩壓面積計算，屬同章節高頻連動考點。",true,[27,32,36,41,45,49],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-114-1-water-chemical-004","依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",4,114,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-002","依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",2,{"webId":37,"stem":38,"number":39,"year":40,"session":12},"fire-113-1-water-chemical-040","有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",40,113,{"webId":42,"stem":43,"number":44,"year":11,"session":12},"fire-106-1-water-chemical-003","有關滅火器設置間距之規定，下列何者錯誤？",3,{"webId":46,"stem":47,"number":48,"year":40,"session":12},"fire-113-1-water-chemical-039","某一工廠儲存鹼金屬過氧化物，滅火藥劑適用下列何者？",39,{"webId":50,"stem":51,"number":30,"year":11,"session":12},"fire-106-1-water-chemical-004","依滅火器認可基準，大型滅火器充填乾粉時，滅火藥劑量需在多少公斤以上？",[53,56,60,64,68],{"webId":54,"year":40,"stem":55,"number":12},"fire-113-1-water-chemical-001","有關消防安全設備水源容量之放水時間，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":57,"year":58,"stem":59,"number":12},"fire-112-1-water-chemical-001",112,"某一新建建築物設有室內消防栓設備，其加壓送水裝置全閉揚程為 60 公尺，今於上午 9 時施作消防立管管系加壓試驗，試驗壓力應大於 X kgf\u002Fcm2 以上之水壓，且須持續維持試驗壓力至 Y 時止均無漏水現象方為合格。其中 X 與 Y 分別為多少？",{"webId":61,"year":62,"stem":63,"number":12},"fire-111-1-water-chemical-001",111,"依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",{"webId":65,"year":66,"stem":67,"number":12},"fire-110-1-water-chemical-001",110,"公共危險物品等場所消防設計及消防安全設備，電氣設備使用之處所，每多少平方公尺（含未滿）應設置第五種滅火設備一具以上？",{"webId":69,"year":70,"stem":71,"number":12},"fire-109-1-water-chemical-001",109,"下列場所何者未達依法應設置滅火器之條件？",1785129973361]