[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-science-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-火災學概要-035","fire-106-1-fire-science-035",106,1,35,"五層樓的建築物，每層設有特別安全梯，樓梯採正壓且加壓壓力為 35 Pa，每層特別安全梯之前室採正壓且加壓壓力為 25 Pa，居室則未設煙控設計，居室避難到特別安全梯，需經過設有煙控之前室，且空間均為密閉構造，唯一開口為安全門，流動面積為 0.01 m2，試問每一排煙室設加壓煙控時，應送的風量為多少？",{"A":16,"B":17,"C":18,"D":19},"1.55 m3\u002Fs","0.155 m3\u002Fs","0.0155 m3\u002Fs","1.55 × 10-3 m3\u002Fs","C",null,[],false,"本題考點：特別安全梯附室(排煙室)加壓防煙的送風量計算，考的是開口流量公式 Q = 0.827·A·√ΔP 與壓力單位換算。\n【正解理由】加壓防煙的送風量，等於維持設計壓差時由門縫或安全門流出的空氣量，依開口流量公式 Q = 0.827·A·√ΔP,以流動面積 0.01 m² 與樓梯間加壓壓力 35 Pa(換算約 3.57 mmAq)代入，得約 0.0156 m³\u002Fs,四捨五入即為 0.0155 m³\u002Fs 這一級數，故選 C。\n【逐項排除】\n(A) 1.55 m³\u002Fs 大 100 倍，相當於把流動面積誤取為整片門扇的 1 m²。\n(B) 0.155 m³\u002Fs 大一個數量級，常見於壓力未換算單位即開根號所致。\n(C) 以題給面積與加壓壓力代入開口流量公式，結果落在 1.55×10⁻² m³\u002Fs,與題目條件相符，為正確答案。\n(D) 1.55×10⁻³ m³\u002Fs 小一個數量級，相當於流動面積誤取 0.001 m²,與題給不符。\n【演算步驟】公式 Q = 0.827·A·√ΔP;壓力換算 35 Pa ÷ 9.8 ≈ 3.57 mmAq;開根號 √3.57 ≈ 1.89;代入 Q = 0.827 × 0.01 m² × 1.89 ≈ 0.0156 m³\u002Fs ≈ 1.55×10⁻² m³\u002Fs。\n【記憶點】送風量看面積成正比、看壓差開根號——面積差一個零，答案就差一個數量級。","加壓防煙(pressurization smoke control)的基本邏輯是：在避難路徑上製造比火災室更高的壓力，讓空氣由安全側流向火災側，煙就進不來。本題的路徑是「居室(未加壓)→附室 25 Pa →特別安全梯 35 Pa」,壓力由內而外逐級升高，形成階梯式壓差，這是《各類場所消防安全設備設置標準》中特別安全梯附室排煙室設計的核心概念，也是日本、NFPA 92 系列共通的作法。\n\n公式來源：開口流量式由柏努利方程式配合流量係數推導而來,Q = C·A·√(2ΔP\u002Fρ);把空氣密度 ρ ≈ 1.2 kg\u002Fm³ 與流量係數 C ≈ 0.65~0.7 代入，常數項即收斂為 0.827(部分教材寫 0.839,係流量係數取值不同),因此考場上兩個常數都可能出現，計算結果差異不到 2%,不影響選項判讀。單位換算必須熟練:1 mmAq ≈ 9.8 Pa、1 kgf\u002Fcm² ≈ 98 kPa ≈ 10 m 水頭、1 atm ≈ 101.3 kPa;煙控題的壓差習慣以 Pa 表示，水系統題則以 kgf\u002Fcm² 或 MPa 表示。\n\n數值記憶對照：加壓空間與相鄰空間的設計壓差，一般規範取 25~50 Pa;過低擋不住煙，過高則門推不開，故另有「開門力不得過大」的限制，常與門扇開啟力計算題(F = Fdc + Kd·W·A·ΔP\u002F(2(W−d)))成套出現。門開啟瞬間的通過風速另有 0.7~1.0 m\u002Fs 的要求，這是加壓送風機需具備「洩壓裝置」或變頻控制的原因。\n\n易混淆概念：加壓防煙屬「防煙」,靠壓差把煙擋在外；機械排煙屬「排煙」,靠風機把煙抽出去，兩者計算基準完全不同，前者算漏氣量、後者算煙層生成量。相關考點還包括中性帶、煙囪效應與外部風壓對加壓效果的干擾。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-science-034","假設建築物外部風速為 20 m\u002Fs，風壓係數為 0.6，空氣密度為 1 kg\u002Fm3，其對建築物迎風面所產生的風壓約為多少？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-science-036","在一大氣壓力狀態下，假設空氣中氧（O2）之重量占整體空氣的 23%，試問 1 kg 之硫（S）完全燃燒，約需多少公斤之空氣？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-science-033","設有一儲存倉庫使用混凝土及磚塊所築成，該倉庫長 10 m、寬 7 m、高 3.5 m。可燃物（以木材為主）總重 2100 kg，總表面積為 300 m2，倉庫內有一開口寬 1.8 m、高 2 m，試問火災持續時間最長為多少？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-science-037","已知門扇高 2.13 m、寬 0.91 m，把手安置在靠近邊緣 0.076 m 處，兩邊壓為 75 Pa，壓力係數 Kd=0.91，克服門自鎖力為 53 N，求最少需多少力才能打開該門？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-science-032","火場能見度與煙霧消光係數有密切關係，若以煙霧的質量光學密度 Dm（m2\u002Fg）代表煙霧密度，假定在長 8m、寬 6m、高 3m 之實驗室燃燒 600g 之聚氯乙烯（PVC），其 Dm＝0.12 m2\u002Fg，試估算實驗室內發光避難指示燈之能見度為何？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-science-038","一般研究建築物室內火災行為特性時，將室內所產生的煙與熱，區分成上層區（熱區）及下層區（冷區），進而研究的模式稱為：",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-science-035",113,"某鑄造工廠因高溫鋁水洩漏，遇水引發爆炸，此為何種爆炸？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-science-035",112,"相較於氣體爆炸，一般的粉塵爆炸具有下列那種性質？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-science-035",111,"下列何者為乾粉最主要滅火原理？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-science-035",110,"面對廚房油鍋起火燃燒，下列何項應對動作的風險最大？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-science-035",109,"有關引火性液體的敘述，下列何者正確？",1785129968125]