[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-science-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-火災學概要-032","fire-106-1-fire-science-032",106,1,32,"火場能見度與煙霧消光係數有密切關係，若以煙霧的質量光學密度 Dm（m2\u002Fg）代表煙霧密度，假定在長 8m、寬 6m、高 3m 之實驗室燃燒 600g 之聚氯乙烯（PVC），其 Dm＝0.12 m2\u002Fg，試估算實驗室內發光避難指示燈之能見度為何？",{"A":16,"B":17,"C":18,"D":19},"10.44 m","5.22 m","2.61 m","6.96 m","D",null,[],false,"本題考點：以質量光學密度求煙層消光係數，再依能見度經驗式估算發光型標示的可視距離。\n【正解理由】依煙霧能見度理論，消光係數 K 由質量光學密度、燃燒質量與空間體積求得：K＝Dm×M\u002FV；再依 Jin 的能見度經驗式 V＝C\u002FK，其中發光型（自行發光）標示取係數 C＝8，反射型物體取 C＝2～4。本題空間體積 V＝8 m×6 m×3 m＝144 m³，K＝0.12 m²\u002Fg×600 g÷144 m³＝0.5 m⁻¹（此為以 10 為底的光學密度基準），換算成自然對數基準之消光係數 K′＝0.5×2.303＝1.1513 m⁻¹，代入 V＝8÷1.1513＝6.95 m，四捨五入為 6.96 m，故選 D。\n【逐項排除】\n(A) 10.44 m：相當於把能見度係數誤取為 12，高於發光型標示的 8，結果被高估。\n(B) 5.22 m：相當於係數取 6，介於反射型與發光型之間，並非題目所問的發光型標示。\n(C) 2.61 m：相當於係數取 3，那是反射型物體（如一般看板、牆面文字）的適用值，題目明示為「發光避難指示燈」，不適用。\n(D) 6.96 m：以發光型係數 8 除以消光係數 1.1513 m⁻¹ 所得，為正解。\n【記憶點】發光型除以 8、反射型除以 2～4，先算 K＝Dm·M\u002FV 再換底乘 2.303。","這題把兩個獨立的概念串在一起，任一環節搞混就會落入誘答。第一環是消光係數。煙對光的衰減服從朗伯－比爾定律 I\u002FI₀＝e^(－K·L)，K 即消光係數，單位 m⁻¹。實務量測常以光學密度 OD＝log₁₀(I₀\u002FI) 表示，而 Dm（質量光學密度，m²\u002Fg）是以 10 為底定義的材料常數，因此由 Dm 算得的 0.5 必須乘上 ln10＝2.303 才能與自然對數基準的 K 相容。這一步是本題最容易漏掉的關鍵；若忘記換底而直接以 8\u002F0.5＝16 m 作答，選項中根本沒有對應值，反而是自我檢核的提示。\n第二環是能見度係數。Jin 的實驗結論可寫成 V·K＝C：發光型標示 C≒8、反射型物體 C≒3（範圍 2～4）。差異來自光源本身是否發光——發光體逆著煙層仍能被辨識，反射體則需光線來回穿透兩次，故可視距離大致只有發光體的三分之一。國考題若把「發光避難指示燈」改成「牆上的文字」或「反光標示」，答案就要換係數重算，這正是本題四個選項的設計邏輯：同一個 K，四個不同的 C。\n值得補充的是刺激性煙的修正。Jin 另指出當煙具刺激性（如含氯化氫的 PVC 燃燒煙）時，人員因流淚、閉眼而使實際能見度低於理論值，修正式約為 V＝(0.133－1.47 log K)\u002FK，在 K 值較大時衰減更明顯。本題燃燒物正是聚氯乙烯，其熱裂解會產生大量氯化氫與濃黑煙，是火場中毒性與減光性都偏高的材料，這也是命題選用 PVC 的用意。\n易混淆數值對照：避難安全驗證常用的容許能見度基準，一般居室約 5 m、大空間或不熟悉環境的場所要求 10 m 以上；煙層下降至距樓地板 1.8 m（人員頭部高度）亦為判定基準之一。標示設備、避難指標與緊急照明的設置目的，即在於煙中仍能維持可辨識性。延伸考法包括：反算某能見度所對應的可容許燃燒質量、或結合火羽流捲吸求煙層下降時間，再判斷避難可用時間是否足夠。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-science-031","建築物火災時要防止火勢由外牆的窗戶向上延燒，下列改善措施何者錯誤？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-science-033","設有一儲存倉庫使用混凝土及磚塊所築成，該倉庫長 10 m、寬 7 m、高 3.5 m。可燃物（以木材為主）總重 2100 kg，總表面積為 300 m2，倉庫內有一開口寬 1.8 m、高 2 m，試問火災持續時間最長為多少？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-science-030","依照 McCaffrey 火羽流理論，下列何者正確？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-science-034","假設建築物外部風速為 20 m\u002Fs，風壓係數為 0.6，空氣密度為 1 kg\u002Fm3，其對建築物迎風面所產生的風壓約為多少？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-science-029","一般而言，區劃空間火災中引發閃燃時，樓地板最低輻射熱通量值約為何？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-science-035","五層樓的建築物，每層設有特別安全梯，樓梯採正壓且加壓壓力為 35 Pa，每層特別安全梯之前室採正壓且加壓壓力為 25 Pa，居室則未設煙控設計，居室避難到特別安全梯，需經過設有煙控之前室，且空間均為密閉構造，唯一開口為安全門，流動面積為 0.01 m2，試問每一排煙室設加壓煙控時，應送的風量為多少？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-science-032",113,"可燃物在大氣中僅因受熱致使溫度升高而引發燃燒的最低溫度稱為：",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-science-032",112,"將大塊的木頭切碎為小片的木屑時，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-science-032",111,"下列何者非油槽火災發生沸溢或濺溢的主要因素？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-science-032",110,"有關爆炸性物質之特性，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-science-032",109,"已知天花板噴流溫度攝氏 135℃，天花板噴流速度 1.8 m\u002Fs，環境初始溫度 20℃，感知撒水頭作動溫度攝氏 72℃，反應時間指數 67(m1\u002F2s1\u002F2)，感知撒水頭作動時間為下列何者？（提示： ln115=4.74, ln63=4.14）",1785129968114]