[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-032","fire-106-1-fire-law-032",106,1,32,"水霧滅火設備水源，應連結加壓送水裝置。其用於防護電氣設備者，出水壓力達每平方公分多少公斤以上？",{"A":16,"B":17,"C":18,"D":19},"0.5","1.5","2.5","3.5","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》中，水霧滅火設備加壓送水裝置之出水壓力規定，以及防護電氣設備時的特別要求。\n【正解理由】依《各類場所消防安全設備設置標準》關於水霧滅火設備之規定，加壓送水裝置之出水壓力，一般情形應在每平方公分2.7公斤以上，而用於防護電氣設備者，因須確保水滴粒徑細、霧化完全以維持足夠的電氣絕緣性，出水壓力提高至每平方公分3.5公斤以上。四個選項中僅3.5符合防護電氣設備之要求，故選 D。\n【逐項排除】\n(A) 錯誤。0.5 kgf\u002Fcm²遠低於任何水霧噴頭之有效霧化壓力，水流將呈柱狀而非霧狀，對電氣設備反而形成導電路徑。\n(B) 錯誤。1.5 kgf\u002Fcm²為部分撒水或連結送水系統常見的壓力量級，並非水霧設備之規定值。\n(C) 錯誤。2.5 kgf\u002Fcm²接近一般水霧設備2.7 kgf\u002Fcm²的門檻，屬刻意設計的誘答，且仍不足以滿足防護電氣設備之較高要求。\n(D) 正確。防護電氣設備者，出水壓力應在每平方公分3.5公斤以上。\n【記憶點】水霧壓力記「一般2.7、電氣3.5」——遇到電就要加壓。","水霧滅火設備的滅火機理有三：水滴汽化吸收大量潛熱而冷卻、蒸氣膨脹稀釋氧濃度而窒息、以及水霧對輻射熱的遮蔽。其中每一項都取決於水滴粒徑，而粒徑由噴頭孔口與放水壓力共同決定——壓力愈高、霧化愈細、比表面積愈大、汽化愈快。這解釋了為何法規要用「出水壓力」而非只用「放水量」來規範性能。\n\n防護電氣設備時壓力門檻提高到每平方公分3.5公斤，關鍵在於電氣絕緣。連續水柱是導體，霧化後的離散水滴之間有空氣間隙，導電性大幅下降，因此水霧才得以用於變壓器、油浸開關等場所；若壓力不足導致霧化不完全，水流連續化便可能造成短路或人員感電，這正是條文對電氣防護另設較高壓力的立法理由。同一條文另定水霧噴頭之放水量，以及放射區域、排水設備（防止含油污水擴散並避免積水導電）之要求，宜整組記憶。\n\n單位換算是本類題型的隱藏考點：1 kgf\u002Fcm²約等於0.098 MPa，也約等於10公尺水頭。故2.7 kgf\u002Fcm²約0.27 MPa、約27公尺水頭；3.5 kgf\u002Fcm²約0.34 MPa、約35公尺水頭。近年題目與法規逐步改採MPa表示，看到MPa數值時先乘以10即可粗略還原為舊制的kgf\u002Fcm²。\n\n易混淆概念對照：一是水霧與細水霧——後者粒徑更細、屬另一套技術規範；二是水霧與泡沫滅火設備——同樣可用於油類場所，但泡沫靠覆蓋隔絕，遇帶電設備並不適用；三是各系統壓力數值的橫向比較，撒水設備、泡沫設備與水霧設備的壓力門檻各不相同，切勿互套。\n\n相關考點連結：同一條文常延伸考水霧放射區域面積、水源容量之計算，以及防護電氣設備時噴頭與帶電體之距離要求。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-031","下列有關消防法施行細則第 15 條自衛消防編組規定之敘述，何者正確？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-033","建築物在五樓以上，且總樓地板面積在 3,000 平方公尺以上者，其火警自動警報設備鳴動方式之規定敘述，何者錯誤？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-030","下列有關百貨商場收容人員之計算規定之敘述，何者錯誤？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-034","各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後幾日內，向當地消防機關申報？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-029","下列有關簡易自動滅火設備規定之敘述，何者錯誤？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-035","下列有關建築物消防安全設備竣工查驗程序規定之敘述，何者錯誤？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-032",114,"依可燃性高壓氣體場所標示板規格及設置要點規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-032",113,"依建築技術規則建築設計施工編規定，有關耐燃合板、耐燃纖維板、耐燃塑膠板及石膏板等耐燃材料，係指耐燃幾級之材料？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-032",112,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-032",111,"供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-032",110,"裝置避難器具之固定部（係指裝設避難器具之樑、柱、樓板等堅固構造或經補強之部分）直接裝置在建築物主要構造部之施工方法，若以金屬膨脹錨定螺栓之施工方法，金屬膨脹錨定螺栓間之間隔，應為埋入深度之幾倍以上？",1785129970906]