[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-009","fire-106-1-fire-law-009",106,1,9,"依據各類場所消防安全設備設置標準規定，公共危險物品等場所之滅火設備分類，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"第一種滅火設備：指滅火器、水桶、水槽、乾燥砂、膨脹蛭石或膨脹珍珠岩","第二種滅火設備：指自動撒水設備","第三種滅火設備：指室內或室外消防栓設備","第四種滅火設備：指水霧、泡沫、二氧化碳或乾粉滅火設備","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》公共危險物品等場所之滅火設備第一種至第五種的分類內容。\n【正解理由】依《各類場所消防安全設備設置標準》關於公共危險物品等場所滅火設備之分類規定，第一種為室內或室外消防栓設備；第二種為自動撒水設備；第三種為水霧、泡沫、二氧化碳或乾粉滅火設備；第四種為大型滅火器；第五種為滅火器、水桶、水槽、乾燥砂、膨脹蛭石或膨脹珍珠岩。選項 B 所述第二種即自動撒水設備，與條文完全一致，故選 B。\n【逐項排除】\n(A) 錯誤。滅火器、水桶、水槽、乾燥砂、膨脹蛭石或膨脹珍珠岩屬第五種滅火設備，不是第一種。\n(B) 正確。第二種滅火設備即自動撒水設備，是五類中唯一的固定式撒水系統。\n(C) 錯誤。室內或室外消防栓設備為第一種滅火設備，選項誤植為第三種。\n(D) 錯誤。水霧、泡沫、二氧化碳或乾粉滅火設備屬第三種；第四種指的是大型滅火器。\n【記憶點】口訣「一栓、二撒、三霧泡二氧乾、四大型、五小型加砂石」,由固定式往簡易式排序。","這個五分類是公共危險物品場所專用的滅火設備編號體系，與一般場所依滅火設備、警報設備、避難逃生設備、消防搶救上之必要設備、其他的分類方式完全不同，是本章最容易與其他章節混淆之處。編號的排列邏輯其實有跡可循：號碼越小，設備越接近「固定式、大水量、需管路與水源」;號碼越大，設備越接近「移動式、小容量、可人力搬運」。第一種到第三種都是固定式系統，第四種與第五種則是滅火器級的移動設備，差別只在大型與小型。掌握這條軸線，即使一時想不起條文，也能靠設備性質推回編號。\n分類之所以重要，是因為場所分級後的設備配置直接引用這些編號。顯著滅火困難場所原則上應設置第一種、第二種或第三種滅火設備，並另設第四種及第五種；一般滅火困難場所設置第四種及第五種；其他場所則設第五種即可。也就是說，編號記錯的後果不是少寫一個名詞，而是整個場所的設備配置全盤錯誤，這正是命題者反覆在此設題的原因。\n第三種滅火設備內部還可再依火災類別細分適用：水霧對油類火災以冷卻與乳化作用抑制，對電氣設備因水滴微細、導電路徑不連續而具一定適用性；泡沫以覆蓋窒息與冷卻為主，是第四類公共危險物品油槽火災的主力；二氧化碳以稀釋氧濃度窒息滅火，適用電氣與精密設備但有人員窒息風險；乾粉以化學抑制打斷連鎖反應，滅火速度最快但無冷卻能力，易復燃。這一組對照是申論與選擇題共同的高頻考點。\n另可注意第五種中的乾燥砂、膨脹蛭石與膨脹珍珠岩，是專為禁水性物質與第三類公共危險物品準備的覆蓋式滅火材料，因為烷基鋁一類物質遇水會劇烈反應，只能以惰性固體覆蓋隔絕。看到選項出現這三樣東西，幾乎可以直接鎖定第五種。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-008","依據各類場所消防安全設備設置標準規定，對瓦斯漏氣檢知器設置，下列敘述何者正確？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-010","依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，公共危險物品之範圍及分類下列何者正確？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-007","依據各類場所消防安全設備設置標準規定，公共危險物品製造場所符合下列何者要件，則屬顯著滅火困難場所？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-011","依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，儲存公共危險物品之數量在管制量 20 倍以下者，建築物之一部分在符合相關規定下，得供作室內儲存場所使用，下列何種公共危險物品可儲存於上述之室內儲存場所？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-006","依據各類場所消防安全設備設置標準規定，集會堂使用之舞臺在設置自動撒水設備時，應選擇下列何者？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-012","依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列何種公共危險物品，不得儲放室外儲存場所？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-009",114,"依消防法、消防安全設備檢修及申報辦法規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-009",113,"有關消防幫浦性能應符合之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-009",112,"依消防安全設備檢修專業機構管理辦法之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-111-1-fire-law-009",111,"有關室內儲槽場所幫浦設備之設置規定，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-110-1-fire-law-009",110,"依消防設備師及消防設備士管理辦法規定，各級消防機關得檢查消防設備師及消防設備士之業務或令其報告、提出證明文件、表冊及有關資料。若某消防設備士拒絕提供前述資料，違反規定時，主管機關應如何處理？",1785129970759]