[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-040","fire-106-1-alarm-evacuation-040",106,1,40,"有關出口標示燈具閃滅或音聲引導功能者，依規定下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"設於主要出入口","與火警自動警報設備連動","由主要出入口往避難方向所設探測器動作時，該出入口之出口標示燈應停止閃滅及音聲引導","未達設置火警自動警報設備之規模時，得免與探測器連動","D",null,[],false,"本題考點：具閃滅或音聲引導功能之出口標示燈，其設置與連動之法定要件。\n【正解理由】依《各類場所消防安全設備設置標準》第 146 條之 7，具閃滅或音聲引導功能之出口標示燈，應設於主要出入口，且應與火警自動警報設備之探測器連動；並規定由主要出入口往避難方向所設之探測器動作時，該出入口之出口標示燈應停止閃滅及音聲引導，以免把人員導向已受火煙威脅的出口。條文並無「未達設置火警自動警報設備規模即得免連動」之免除規定，該敘述與條文不合，題目問「何者錯誤」，故選 D。\n【逐項排除】\n(A) 正確。閃滅與音聲引導的目的即在濃煙或視線不良時導引人員前往主要出入口，條文明定應設於主要出入口。\n(B) 正確。閃滅與音聲須由火災信號觸發才有意義，故條文要求與火警自動警報設備連動，平時不作動。\n(C) 正確。往該出入口避難方向的探測器動作，代表該路徑已有火煙，繼續閃滅與發聲將誘導人員走向危險，故應停止。\n(D) 錯誤。此類燈具的閃滅與音聲功能以與探測器連動為必要條件，條文未設規模門檻的免連動例外，敘述與法不符，為本題答案。\n【記憶點】閃滅與音聲一定要跟探測器連動，火在哪就不許往哪叫人。","閃滅與音聲引導型出口標示燈是為了解決純視覺標示在濃煙中失效的問題。火場煙層下降後，即使燈具亮著也可能因散射而難以定位；閃爍的明暗變化比恆亮更容易被周邊視覺捕捉，而語音或蜂鳴則完全不依賴視覺，對視障者與能見度趨近於零的環境特別有效。這類設備多要求設於場所的主要出入口，也就是避難流線的終點。\n\n設計上最關鍵的安全機制是「反向抑制」：當通往該出入口的避難路徑上探測器動作，代表該方向已有火煙，此時仍持續閃滅發聲，等同把人往火場方向招手。因此條文要求該出入口之出口標示燈應停止閃滅及音聲引導。這一機制與整體避難引導的邏輯一致——引導設備必須是「動態」的，能反映火勢位置，而非一律全開。\n\n易混淆概念對照：出口標示燈標示的是出口本身，避難方向指示燈標示的是前往出口的方向，避難指標則為非電源式的低位辨識標示；三者的設置高度、有效範圍與緊急電源要求各不相同。另需區辨閃滅音聲功能與一般出口標示燈的差別，後者僅需常時點燈並具緊急電源。\n\n延伸考法包括：標示設備之緊急電源供電時間與大規模場所的加長要求、出口標示燈依有效範圍區分之級別、以及火警自動警報設備警戒區域劃定與受信總機之連動回路設計。另一個常被忽略的層面是音聲引導的內容與音壓：語音須能在火場噪音中被聽辨，且引導語不得與緊急廣播設備的訊息互相干擾，因此兩套設備的作動邏輯需整合設計。命題時若出現「閃滅與音聲得單獨作動而不受探測器影響」「音聲引導應持續至火警解除」這類敘述，皆與條文的反向抑制精神相悖，可直接判為錯誤。※ 條號請以現行法規為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-039","具有效採光，且直接面向室外之通道或走廊居室得免設緊急照明；所謂有效採光面積應達該居室樓地板面積多少比率方得免設？",39,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-107-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，除供甲類場所、地下建築物、高層建築物或應設置偵煙式探測器之場所外，若要以自動撒水設備免設火警自動警報設備，有關密閉型撒水頭之規定，下列那一項正確？",107,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，避難指標設於出入口裝設應距樓地板面的高度要求為多少？",38,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-107-1-alarm-evacuation-002","差動式分布型探測器為熱半導體式時，裝接於一個檢出器之感熱器數量，下列何者正確？",2,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-037","為避免探測死角，在安裝光電式分離型探測器時，其受光器及送光器應設在距其背部牆壁多少公分範圍內？",37,{"webId":49,"stem":50,"number":51,"year":35,"session":12},"fire-107-1-alarm-evacuation-003","下列何者非屬定溫式探測器可裝設場所？",3,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-040",113,"依據火警探測器認可基準，對於差動式探測器直線上升的動作試驗，自室溫狀態下以平均每分鐘 T℃直線升溫速度之水平氣流吹向時，應在 M 分鐘以內動作，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-040",112,"依各類場所消防安全設備設置標準，醫院熱水室之場所適用選擇設置下列何種探測器？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-040",111,"光電式分離型探測器進行外觀試驗，以目視確認探測器光軸應平行牆壁距離 X 公分以上，且探測器之光軸高度應在天花板等高度 Y%以上之位置。而使用減光罩進行動作試驗，非蓄積型探測器之動作時間應在 Z 秒內。則 X、Y、Z 值，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-040",110,"避難器具之裝設規定，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-040",109,"有關火警自動警報設備受信總機周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",1785129965593]