[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-039","fire-106-1-alarm-evacuation-039",106,1,39,"具有效採光，且直接面向室外之通道或走廊居室得免設緊急照明；所謂有效採光面積應達該居室樓地板面積多少比率方得免設？",{"A":16,"B":17,"C":18,"D":19},"2%","3%","5%","6%","C",null,[],false,"本題考點：緊急照明設備得免設之「有效採光面積」比率規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 178 條，具有效採光且直接面向室外之通道或走廊，及與外部有效採光面積達該居室樓地板面積二十分之一以上之居室，得免設緊急照明設備。二十分之一換算為百分比即為百分之五。其立法邏輯是：白晝有充足自然採光的空間，即使停電也能維持基本的辨識與避難能見度，故容許免設；比率若訂得太寬鬆，停電時仍會陷入黑暗，因此以樓地板面積的二十分之一為門檻，故選 C。\n【逐項排除】\n(A) 百分之二相當於五十分之一，遠低於條文所定的二十分之一，採光量不足以支撐停電時的避難辨識，非本條數值。\n(B) 百分之三約為三十三分之一，同樣未達二十分之一之門檻，是憑印象填答的常見錯誤數值。\n(C) 百分之五即二十分之一，正是條文所定的有效採光面積比率門檻，為正解。\n(D) 百分之六高於條文門檻，若採此標準會使部分本可免設的居室仍須設置，與條文明定的二十分之一不符。\n【記憶點】採光達樓地板面積二十分之一，也就是百分之五，居室免設緊急照明。","緊急照明設備的功能是在正常電源中斷時，於避難路徑上維持最低限度的照度，使人員得以辨識地面高低差、門扇位置與標示設備。我國法規對其照度要求以地面水平面照度計，並規定緊急電源須能持續供電一定時間，檢修時以照度計實測是否達標。\n\n免設規定的核心概念是「替代性」。當空間本身具備足夠的自然採光，或已有其他方式確保避難時的可視性，法規即允許不重複設置。條文所稱「有效採光」並非泛指有窗戶，而是指該開口確實能引入外部光線、且直接面向室外者；面向天井、內部走廊或被遮蔽的開口不計入。面積門檻定在樓地板面積二十分之一，與建築技術規則對居室採光的傳統比率概念相呼應，考生可把「二十分之一＝百分之五」當成跨法規共用的記憶錨點。\n\n須留意免設的適用對象有兩類且條件不同：一是直接面向室外且具有效採光之通道或走廊，二是有效採光面積達二十分之一之居室。另有經中央主管機關認可之其他免設情形。命題常把兩類混寫，或把比率換成三十分之一、十分之一測試記憶精度。\n\n延伸考點包括：緊急照明燈之構造與光源種類、緊急電源使用蓄電池設備時的容量與充電要求、與出口標示燈、避難方向指示燈在停電時的分工，以及檢修申報時緊急照明的照度測定與切換試驗方法。實測時通常在正常照明關閉、緊急電源投入的狀態下，於地面測定水平面照度，並確認持續供電時間符合規定；地下建築物、無開口樓層等避難條件較差的場所，其供電時間要求更長，理由是這類空間完全依賴人工照明，一旦停電即陷入全黑。把「免設條件」與「加嚴條件」對照著記，是掌握本條的最短路徑。※ 條號請以現行法規為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，避難指標設於出入口裝設應距樓地板面的高度要求為多少？",38,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-040","有關出口標示燈具閃滅或音聲引導功能者，依規定下列何者錯誤？",40,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-037","為避免探測死角，在安裝光電式分離型探測器時，其受光器及送光器應設在距其背部牆壁多少公分範圍內？",37,{"webId":41,"stem":42,"number":12,"year":43,"session":12},"fire-107-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，除供甲類場所、地下建築物、高層建築物或應設置偵煙式探測器之場所外，若要以自動撒水設備免設火警自動警報設備，有關密閉型撒水頭之規定，下列那一項正確？",107,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-036","很多工程裝設局限型探測器時多緊鄰天花板上出風口，造成失效或延遲警報，因此，施工時依規定裝設位置應距該出風口多少公尺以上？",36,{"webId":49,"stem":50,"number":51,"year":43,"session":12},"fire-107-1-alarm-evacuation-002","差動式分布型探測器為熱半導體式時，裝接於一個檢出器之感熱器數量，下列何者正確？",2,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-039",113,"某捷運高架車站，因地形環境因素致車站早晚霧氣瀰漫，為防止霧氣結露產生探測器誤動作，選設之探測器除考量防水性能外，試問下列何者探測器不適用？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-039",112,"依消防安全設備及必要檢修項目檢修基準，檢查一一九火災通報裝置性能時，有關通報裝置本體檢查，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-039",111,"民國 84 年取得使用執照之大樓，測試其火警地區音響裝置之音壓何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-039",110,"依消防安全設備及必要檢修項目檢修基準，火焰式探測器進行性能檢查時，使用火焰探測器用動作試驗器，探測器應在多少時間內動作？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-039",109,"有關緊急照明設備之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",1785129965585]