[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-034","fire-106-1-alarm-evacuation-034",106,1,34,"在裝設定溫式感知線型探測器場所，進行回路合成阻抗試驗時，會使用下列何種檢查儀器？",{"A":16,"B":17,"C":18,"D":19},"三用電表","絕緣電阻計","接地電阻試驗器","儀表繼電器試驗器","A",null,[],false,"本題考點：定溫式感知線型探測器回路合成阻抗試驗所使用之檢查儀器，依據《消防安全設備檢修及申報作業基準》。\n【正解理由】定溫式感知線型探測器為長條狀的感知線，以兩條被熱熔性絕緣物隔開的鋼線構成，火災高溫使絕緣物熔化而短路動作；因線體長、串接距離遠，線路本身的電阻會影響動作信號能否被受信總機辨識，故檢修時須量測回路的合成阻抗值並與規定值比對。此項量測屬於低電壓下的電阻讀值，依檢修基準以三用電表(萬用電表)於受信總機端量測回路電阻即可判定，故選 A。\n【逐項排除】\n(A) 正確，三用電表具電阻檔，可直接讀取回路合成阻抗，是本試驗指定使用的儀器。\n(B) 絕緣電阻計施加數百伏特直流高壓，用於量測導線對地或線間的絕緣電阻(百萬歐姆級),若用於感知線回路將加壓於元件，量到的也不是合成阻抗。\n(C) 接地電阻試驗器量的是接地極與大地間的電阻，屬電氣接地系統的檢查，與探測器回路阻抗無關。\n(D) 儀表繼電器試驗器用於檢驗繼電器動作值與復歸值，對象是繼電器而非配線回路。\n【記憶點】量回路合成阻抗用三用電表；量絕緣才用絕緣電阻計。","定溫式感知線型探測器屬局限型以外的「線型」探測器，常設於電纜線槽、輸送帶、停車空間、隧道等長距離且局限型探測器不易涵蓋的場所。其構造是兩條鋼製導線各自包覆熱熔性絕緣物並互相絞繞，外覆保護被覆；當任一段落達到標稱動作溫度，絕緣物軟化熔融使兩線短路，受信總機偵測到回路電阻驟降而判定火警。因為它是「任一點動作即動作」,無法像局限型那樣逐個加熱試驗，檢修上改以量測回路合成阻抗與末端短路試驗來確認線路完整。\n合成阻抗之所以重要，在於感知線本身即帶有相當的直流電阻，再串上配線與末端電阻後，總值必須落在受信總機可辨識的區間：阻抗過高，短路動作時電流變化不足以觸發判定，可能漏報；阻抗過低或已短路，則會呈現常時動作而誤報。以三用電表在受信總機端拆下回路後量測，即可比對設計值判定。\n易混淆儀器對照表值得整批背下：三用電表量電壓、電流、電阻，用於回路合成阻抗、電源電壓確認；絕緣電阻計(高阻計)以直流 250 伏特或 500 伏特量絕緣電阻，火警自動警報設備配線之絕緣電阻判定一般為 0.1 MΩ 以上(電源回路對地則另有較高要求);接地電阻試驗器量接地極電阻；加熱試驗器、加煙試驗器分別用於差動式與偵煙式探測器之動作試驗；加瓦斯試驗器用於瓦斯漏氣檢知器。\n相關考點連結：線型探測器另有偵煙式分離型(以送光部與受光部間的減光率判定)與差動式分布型(空氣管式，以測試幫浦、流體壓力計進行空氣注入試驗與接點水高試驗),空氣管式的檢查器材是流體壓力計與測試幫浦，與感知線型的三用電表恰成對照，是同一組高頻命題素材。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-033","針對某百貨公司美食街進行檢修，下列何項試驗必須使用加瓦斯試驗器，使兩個回路之任一檢知器（各回路一個）同時動作，以確認其性能是否異常？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-035","執行檢修時，在室溫 15℃狀態下，使用加熱試驗器進行差動式局限型第二種探測器之性能檢查時，其動作時間應在多少秒內方為正常？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-032","針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-036","很多工程裝設局限型探測器時多緊鄰天花板上出風口，造成失效或延遲警報，因此，施工時依規定裝設位置應距該出風口多少公尺以上？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-037","為避免探測死角，在安裝光電式分離型探測器時，其受光器及送光器應設在距其背部牆壁多少公分範圍內？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-034",113,"依據消防安全設備及必要檢修項目檢修基準，針對 119 火災通報裝置本體實施性能檢查，其中以火警自動警報設備連動啟動將一區段蓄積語音送出後，再操作手動啟動裝置，應能再送出蓄積語音，此為下列何種檢查項目？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-034",112,"有關無線電通信輔助設備無線電接頭之外觀試驗，依據無線電通信輔助設備測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-034",111,"二氧化碳滅火系統全區放射的空間，以往造成人員死傷之動作噴發，與防護空間下列因素何者無關？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-034",110,"依消防安全設備及必要檢修項目檢修基準，救助袋進行開口部外觀檢查時，開口部面積之限制，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-034",109,"有關排煙設備綜合檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",1785129965556]