[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-033":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-033","fire-106-1-alarm-evacuation-033",106,1,33,"針對某百貨公司美食街進行檢修，下列何項試驗必須使用加瓦斯試驗器，使兩個回路之任一檢知器（各回路一個）同時動作，以確認其性能是否異常？",{"A":16,"B":17,"C":18,"D":19},"瓦斯漏氣表示試驗","同時動作試驗","綜合動作試驗","檢知器性能檢查","B",null,[],false,"本題考點：瓦斯漏氣火警自動警報設備各項檢修試驗的操作方式辨識，依據《消防安全設備檢修及申報作業基準》。\n【正解理由】依《消防安全設備檢修及申報作業基準》關於瓦斯漏氣火警自動警報設備受信總機之性能檢查，同時動作試驗係以加瓦斯試驗器對「兩個回路各取一個檢知器」使其同時動作，確認受信總機在多回路併發時仍能正確顯示瓦斯漏氣、驅動警報裝置且不致失能或漏顯示。題幹「使兩個回路之任一檢知器(各回路一個)同時動作」正是此試驗的定義性操作，故選 B。\n【逐項排除】\n(A) 瓦斯漏氣表示試驗是操作受信總機之試驗裝置，逐回路確認表示燈與音響，不需加瓦斯試驗器，也非兩回路併行。\n(B) 正確，以加瓦斯試驗器使兩回路各一個檢知器同時動作者，即同時動作試驗。\n(C) 綜合動作試驗是在切換為緊急電源狀態下，對任一檢知器加氣驗證全系統端到端功能，重點在電源狀態而非兩回路併發。\n(D) 檢知器性能檢查係就每回路抽取五分之一以上之檢知器逐一加氣，確認個別檢知器動作與否，屬單一元件層次。\n【記憶點】兩回路各抓一個一起加氣，叫同時動作試驗。","受信總機的設計上，警報顯示與音響驅動共用同一組表示電路與電源，當多個回路在極短時間內先後動作時，若電源容量不足或電路互鎖設計不良，可能出現後動作回路無法顯示、或音響裝置因負載過大而停鳴的情形。實際瓦斯外洩往往是單一管線破損造成鄰近數區同時檢知，並非只有一個回路動作，因此檢修基準特別設計同時動作試驗，以兩回路併發作為最低驗證條件。\n三個名稱相近的試驗可用「操作對象／電源狀態／驗證重點」三欄來區分：瓦斯漏氣表示試驗操作的是受信總機的試驗開關，在常用電源下，驗證顯示與音響電路本身；同時動作試驗操作的是兩回路的檢知器，在常用電源下，驗證多回路併發的容量與互不干擾；綜合動作試驗操作的是任一檢知器，但須切換為緊急電源，驗證的是全系統在災害條件下的端到端可用性。三者一旦以這種對照方式記住，考題無論從哪個角度切入都能還原。\n加瓦斯試驗器是本設備專屬的檢查器材，內裝與檢知對象相符的試驗用氣體；檢知對象若為比空氣輕的天然氣，與比空氣重的液化石油氣，其試驗氣體與檢知器裝設位置均不同，不可混用。相對地，火警自動警報設備的探測器則使用加熱試驗器、加煙試驗器，依探測器種類選用，這是跨設備比較的常見考點。\n判定基準延伸：同時動作試驗時，受信總機應對兩回路均正確顯示且警報裝置持續鳴動；受信總機自檢知器動作至發出警報之時間應在 60 秒以內；檢知區域警報裝置音壓於距 1 公尺處 70 分貝以上。將試驗名稱、操作方式與判定數值三層一起掌握，本設備的檢修題型即可完整覆蓋。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-032","針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",32,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-034","在裝設定溫式感知線型探測器場所，進行回路合成阻抗試驗時，會使用下列何種檢查儀器？",34,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-035","執行檢修時，在室溫 15℃狀態下，使用加熱試驗器進行差動式局限型第二種探測器之性能檢查時，其動作時間應在多少秒內方為正常？",35,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-030","在某飯店檢查瓦斯漏氣火警自動警報設備時，何項試驗必須切換成緊急電源之狀態？",30,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-036","很多工程裝設局限型探測器時多緊鄰天花板上出風口，造成失效或延遲警報，因此，施工時依規定裝設位置應距該出風口多少公尺以上？",36,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-033",113,"某餐廳使用瓦斯燃料，其成分為甲烷（CH4）占 10%、乙烷（C2H6）占 40%、丙烷（C3H8）占 50%，設置有瓦斯漏氣火警自動警報設備。今針對瓦斯漏氣檢知器實施外觀與性能檢查，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-033",112,"依消防安全設備及必要檢修項目檢修基準，在火警自動警報設備性能綜合檢查時，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-033",111,"依消防安全設備測試報告書測試方法及判定要領，有關瓦斯漏氣火警自動警報設備檢知器之動作試驗，以加瓦斯試驗器將試驗瓦斯加進檢知器，測定至瓦斯漏氣表示為止之時間，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-033",110,"緩降機在進行綜合檢查之下降試驗時，以測量下降距離及下降時間計算出下降速度，平均下降速度何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-033",109,"有關緊急電源插座外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",1785129965543]