[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-028","fire-106-1-alarm-evacuation-028",106,1,28,"大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",{"A":16,"B":17,"C":18,"D":19},"信號轉換","信號監控","信號傳遞","發出控制信號","B",null,[],false,"本題考點：火警自動警報設備中中繼器(中繼盤)在系統中所扮演的角色，屬於警報設備系統架構的概念題。\n【正解理由】中繼器介於探測器、發信機等末端裝置與受信總機之間，其功能定位在「訊號路徑上的轉接與加工」:把末端裝置送來的接點或類比訊號轉換成受信總機可讀的格式、把訊號中繼傳遞至較遠的受信總機以克服線路衰減，並在受信總機判定後對消防搶救上之必要設備或連動裝置發出控制信號。至於全系統的信號監控，是受信總機的職責——由受信總機持續監視各回路的斷線、短路與動作狀態並顯示警報，中繼器僅為受其管理的中間節點。題目問「不是」中繼器主要功能者，故選 B。\n【逐項排除】\n(A) 信號轉換是中繼器的核心功能，例如將探測器的接點動作轉為傳輸線上的編碼信號。\n(B) 信號監控屬受信總機的功能，由總機監視回路狀態並顯示，故為本題所要選出之非中繼器功能。\n(C) 信號傳遞正是「中繼」二字的字面意義，用以延伸傳輸距離、擴充回路容量。\n(D) 發出控制信號亦屬中繼器功能，可依受信總機指令驅動連動之設備。\n【記憶點】中繼器負責轉、傳、發，監控全系統的是受信總機。","火警自動警報設備的系統層級可拆成三段：末端偵測(探測器、手動報警機)、中間傳輸(中繼器、傳輸線路)、以及中央判定與顯示(受信總機、副受信總機)。中繼器在《消防安全設備檢修及申報作業基準》與相關認可基準中被明確定位為「接收探測器或發信機發出之信號，予以轉換、傳送至受信總機，或接收受信總機之信號而使消防安全設備動作之裝置」,這段定義正好涵蓋轉換、傳遞、發出控制信號三項，唯獨不含監控。\n為什麼中繼器會出現？早期 P 型系統採一回路一警戒區的並聯配線，建築物規模一大，配線量與回路數呈爆炸性成長。R 型(記錄式)系統改以中繼器將多個末端裝置的狀態編碼後，用少數幾對傳輸線送回受信總機，大幅減少幹線數量，並讓受信總機能顯示到「哪一個裝置」而非只有「哪一區」。因此中繼器的存在是為了解決大型建築物的配線經濟性與定位精度問題，這也是命題者以「大型建築物」開場的原因。\n易混淆概念對照:P 型受信總機以回路對應警戒區，靠共通線與表示線;R 型受信總機靠中繼器與固有信號，可顯示個別位址。副受信總機是受信總機的延伸顯示裝置，能顯示與操作，層級高於中繼器；而所謂中繼盤在現場常與電源供應箱整合，具備自身之緊急電源與保險絲，故檢修時須確認其電源指示與保險絲規格。\n檢修上的相關考點：中繼器的外觀檢查著重腐蝕、變形、標示；性能上則透過回路導通試驗確認其與末端裝置間線路無斷線，再以動作試驗確認信號可正確送達受信總機。命題另一常見角度是問「受信總機應能顯示何種狀態」,答案指向火警動作、斷線、電源異常等監控結果，再次印證監控功能歸屬受信總機，可與本題互為印證。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-027","避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-029","瓦斯濃度達到警報濃度值後，其濃度仍繼續存在，即發出警報，但瓦斯洩漏濃度越高，則警報延遲動作時間越短，此種檢知瓦斯之警報發出方式稱作何種型式？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-026","樓梯或斜坡通道以外之場所，廣播區域之殘響時間在 3 秒以上時，揚聲器之裝設需符合 r = 3 \u002F 4 QSα\u002Fπ (1 −α) 之計算公式，S 的定義為何？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-030","在某飯店檢查瓦斯漏氣火警自動警報設備時，何項試驗必須切換成緊急電源之狀態？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-025","依緊急照明燈認可基準規定，內置電池型緊急電源供電照明時間應維持 1.5 小時以上（供緊急照明燈總數）後，其蓄電池電壓不得小於蓄電池額定電壓多少百分比？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-028",113,"依消防安全設備及必要檢修項目檢修基準，針對防災監控系統綜合操作裝置進行性能檢查，有關消防搶救支援性能項目，於 LCD 螢幕應能針對下列各樓層平面圖，以簡明易操作之方式切換其表示。所敘述之樓層平面圖下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-028",112,"某一地下街其地下層設有瓦斯漏氣火警自動警報設備，其某一回路之檢知器數量有 40 個，依消防安全設備及必要檢修項目檢修基準使用「加瓦斯試驗器」進行加瓦斯測試，檢知器選取檢查數量為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-028",111,"非局限型探測器為有效偵知火災，下列何者為設置標準規定裝設於小空間內至少應有的長度或元件數量？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-028",110,"瓦斯漏氣火警自動警報設備進行性能檢查時，檢知區域警報裝置其音壓在距 1 公尺處應為多少分貝以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-028",109,"有關緊急廣播設備啟動裝置與緊急電話設置場所之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",1785129965515]