[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-026","fire-106-1-alarm-evacuation-026",106,1,26,"樓梯或斜坡通道以外之場所，廣播區域之殘響時間在 3 秒以上時，揚聲器之裝設需符合 r = 3 \u002F 4 QSα\u002Fπ (1 −α) 之計算公式，S 的定義為何？",{"A":16,"B":17,"C":18,"D":19},"受音點至揚聲器之距離","揚聲器指向係數","揚聲器音響功率","廣播區域內牆壁、樓地板及天花板面積之合計","D",null,[],false,"本題考點：緊急廣播設備揚聲器裝設位置之計算式，見《設置標準》第 133 條殘響時間 3 秒以上之特別規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 133 條，樓梯或斜坡通道以外之場所，廣播區域殘響時間在 3 秒以上者，受音點至揚聲器之距離 r 須符合 r = 3\u002F4 √(QSα\u002Fπ(1−α))。式中 r 為距離、Q 為指向係數、α 為平均吸音率,S 則是廣播區域內牆壁、樓地板及天花板面積之合計(平方公尺)。故選 D。\n【逐項排除】\n(A) 受音點至揚聲器之距離為式子左邊的 r,是本式待解之未知數，不是代入項 S。\n(B) 揚聲器指向係數以 Q 表示，係音能因指向性集中之無因次倍率，與面積無關。\n(C) 揚聲器音響功率屬音源輸出(瓦),本式未納入功率項，故不以 S 表示。\n(D) 正確,S 即廣播區域內牆壁、樓地板及天花板面積之合計，面積愈大可容許之 r 愈大。\n【演算步驟】設 Q = 2、S = 200 m²、α = 0.2:QSα = 2 × 200 m² × 0.2 = 80 m²;π(1−α) = 3.14 × 0.8 = 2.512;80 m² ÷ 2.512 = 31.85 m²;√31.85 m² = 5.64 m;r = 0.75 × 5.64 m ≈ 4.2 m。\n【記憶點】r 是距離、Q 管指向、α 是吸音率,S 就是牆、地板、天花板的總面積。","《各類場所消防安全設備設置標準》第 133 條原則要求緊急廣播設備之揚聲器裝設，使各廣播區域內任一點至揚聲器之水平距離在 10 公尺以下(L 級、M 級、S 級依樓地板面積分級),但當廣播區域殘響時間達 3 秒以上時，聲音在空間中反覆反射造成語音清晰度下降，單靠 10 公尺的幾何距離不足以確保聽得懂，因此另設 r = 3\u002F4 √(QSα\u002Fπ(1−α)) 之限制。此式源自建築音響學的臨界距離(critical distance)概念：音源在室內產生的直接音隨距離平方衰減，反射音則在空間中趨於均勻，兩者能量相等處即臨界距離 rc = (1\u002F4)√(QR\u002Fπ),其中 R = Sα\u002F(1−α) 稱為室常數(room constant)。法規把係數放寬為 3\u002F4,即容許受音點落在約三倍臨界距離內，兼顧清晰度與設備數量的合理性。\n單位與量的整理:S 以平方公尺計，取牆壁、樓地板、天花板三者面積合計，亦即整個廣播區域的內表面積;α 為各面材料吸音率以面積加權的平均值，介於 0 與 1 之間,α 愈接近 1 表示吸音愈好、殘響愈短;Q 為指向係數，理論上自由空間全指向為 1,貼牆設置約 2,牆角約 4~8。α 趨近 0 時分母 (1−α) 趨近 1、分子 Sα 趨近 0,r 隨之縮小，正好反映吸音差的空間必須把揚聲器裝得更密。\n易混淆對照：殘響時間 T 常以賽賓公式 T = 0.161V\u002F(Sα) 估算，單位為秒,V 為空間體積；賽賓公式算的是「時間」,本條算的是「距離」,兩式雖同樣使用 S 與 α,但問的量不同，考試常以此設陷阱。此外 L 級揚聲器音壓 92 分貝以上、M 級 87 分貝以上、S 級 84 分貝以上，是同條文另一組高頻考點，宜與本式一併記憶。相關考點還包括樓梯或斜坡通道採垂直距離每 15 公尺設一個 L 級揚聲器之規定，與本題「樓梯或斜坡通道以外」的前提恰成對照。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-025","依緊急照明燈認可基準規定，內置電池型緊急電源供電照明時間應維持 1.5 小時以上（供緊急照明燈總數）後，其蓄電池電壓不得小於蓄電池額定電壓多少百分比？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-027","避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-024","依各類場所消防安全設備設置標準規定，特別安全梯或緊急昇降機間排煙室之排煙設備設置排煙、進風風管時，下列何者有誤？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-028","大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-023","一大樓內部某樓層設有不得供避難、通行及搬運以外用途之防火構造架空走廊一座，該樓層可依法減設多少具避難器具？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-029","瓦斯濃度達到警報濃度值後，其濃度仍繼續存在，即發出警報，但瓦斯洩漏濃度越高，則警報延遲動作時間越短，此種檢知瓦斯之警報發出方式稱作何種型式？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-026",113,"依規定出口標示燈及避難方向指示燈，應保持不熄滅。惟為配合政府機關推動節能減碳措施，除上述燈具採用省電產品外，出口標示燈及走廊通道避難方向指示燈，符合下列何者規定，得予減光或消燈？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-026",112,"依各類場所消防安全設備設置標準規定，醫院在第 3 層樓可以使用下列何種避難器具？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-026",111,"因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-026",110,"對於單相交流 110 V 之緊急電源插座進行外觀及性能檢查時，下列何者與消防安全設備及必要檢修項目檢修基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-026",109,"有關緊急廣播設備配線之設置，除依屋內線路裝置規則外，下列何者與各類場所消防安全設備設置標準之規定不同？",1785129965504]