[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-025","fire-106-1-alarm-evacuation-025",106,1,25,"依緊急照明燈認可基準規定，內置電池型緊急電源供電照明時間應維持 1.5 小時以上（供緊急照明燈總數）後，其蓄電池電壓不得小於蓄電池額定電壓多少百分比？",{"A":16,"B":17,"C":18,"D":19},"87.5%","90%","92.5%","95%","A",null,[],false,"本題考點：緊急照明燈認可基準中，內置電池型燈具經規定放電時間後，蓄電池端電壓相對於額定電壓之最低比率。\n【正解理由】依《緊急照明燈認可基準》之充放電試驗（電池電壓試驗）規定，內置電池型緊急照明燈於緊急電源供電照明一點五小時後，其蓄電池電壓不得小於蓄電池額定電壓之百分之八十七點五。此比率係反映鎳鎘、鎳氫等蓄電池的放電特性——在額定容量放電終止時，端電壓約降至額定值的八成七左右仍屬正常，若低於此值即代表電池容量衰退或內阻上升，無法保證後續仍能維持法定照度，故選 A。\n【逐項排除】\n(A) 87.5%：與認可基準所定之電壓比率相符，換算即八分之七，正對應蓄電池放電終止電壓的傳統設定，為正解。\n(B) 90%：高於基準要求；以此為判定值將使多數性能正常的電池在放電末期被誤判為不合格，非基準所採。\n(C) 92.5%：標準更為嚴苛，與蓄電池放電曲線末段電壓明顯下墜的實際表現不符，屬遞增排列的干擾值。\n(D) 95%：放電達一點五小時後仍要求維持額定電壓九成五，在化學電池的實際放電特性上幾乎無法達成，明顯非判定值。\n【記憶點】緊急照明燈放電一點五小時，電壓要守住額定的八七點五趴——低於此即代表電池撐不住。","緊急照明設備的規範同樣分兩層：《各類場所消防安全設備設置標準》第 175 條至第 179 條規定應設場所、構造與照度，《緊急照明燈認可基準》規範產品性能。設置面的核心數值是照度——緊急照明燈在地面之水平面照度，使用白熾燈時應在十勒克斯以上，使用日光燈或其他光源時應在二勒克斯以上；其緊急電源應使用蓄電池設備，容量能使其持續動作三十分鐘以上，但在總樓地板面積達一定規模之大型場所、高層建築物、地下建築物等，則須提高至六十分鐘以上。\n認可基準所定的一點五小時放電試驗，時間長於設置標準的三十分鐘要求，這是產品端保留安全裕度的典型作法：出廠時以較嚴的條件驗證，確保燈具在使用數年、電池自然衰退後，仍能滿足現場所需的法定放電時間。百分之八十七點五這個看似零碎的數字，換算為分數即八分之七，源自蓄電池放電終止電壓的傳統設定——以鎳鎘電池單顆額定一點二伏特為例，八成七點五約為一點零五伏特，正是常見的放電終止電壓；串聯多顆時比率不變，故基準以百分比而非絕對電壓表示，才能適用於不同電壓規格的產品。\n除電壓試驗外，認可基準尚有多項檢查項目可一併整理：構造與外觀檢查（燈具外殼材質、標示、配線）、照度試驗（於規定距離與角度量測地面水平面照度）、絕緣電阻與耐電壓試驗、充電試驗（在額定電壓下充電二十四小時後應能達到規定放電性能）、以及溫升試驗。這些項目對應到現場的檢修基準，即為外觀檢查（燈具有無破損、光源有無閃爍、充電指示燈是否正常）與性能檢查（切斷常用電源後確認點燈、必要時實施放電試驗）。\n易混淆概念在於緊急照明燈與標示設備（出口標示燈、避難方向指示燈）的分工：緊急照明燈提供的是避難路徑上的「一般照明」，讓人看得見腳下與周遭；標示設備提供的是「方向資訊」，告訴人往哪裡走。兩者緊急電源時間規定不同（緊急照明燈三十分鐘、標示設備二十分鐘，大型場所均提高至六十分鐘），照度與亮度的量測方式也不同，考題極常互換數值設陷，記憶時務必分欄整理。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-024","依各類場所消防安全設備設置標準規定，特別安全梯或緊急昇降機間排煙室之排煙設備設置排煙、進風風管時，下列何者有誤？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-026","樓梯或斜坡通道以外之場所，廣播區域之殘響時間在 3 秒以上時，揚聲器之裝設需符合 r = 3 \u002F 4 QSα\u002Fπ (1 −α) 之計算公式，S 的定義為何？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-023","一大樓內部某樓層設有不得供避難、通行及搬運以外用途之防火構造架空走廊一座，該樓層可依法減設多少具避難器具？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-027","避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-022","依出口標示燈及避難方向指示燈認可基準規定，燈具附有起動器者，應在多少時間內點燈？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-028","大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",28,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-025",113,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-025",112,"有關發電機設備設置場所之外觀試驗，依據緊急電源（發電機設備）測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-025",111,"依 119 火災通報裝置認可基準規定，當常用電源停電，持續 X 分鐘待機狀態後，需保有 Y 分鐘以上可進行火災通報之電源容量；通話功能及回鈴應答試驗於 Z 秒內未收到回鈴信號，應可重複進行撥號。則 X、Y、Z 為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-025",110,"下列有關火警受信總機之裝置規定，何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-025",109,"有關火焰式探測器之設置，下列何者與各類場所消防安全設備設置標準之規定不同？",1785129965494]