[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-023":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-023","fire-106-1-alarm-evacuation-023",106,1,23,"一大樓內部某樓層設有不得供避難、通行及搬運以外用途之防火構造架空走廊一座，該樓層可依法減設多少具避難器具？",{"A":16,"B":17,"C":18,"D":19},"1具","2具","3具","4具","B",null,[],false,"本題考點：避難器具之減設規定，關鍵在防火構造架空走廊可折算的具數。\n【正解理由】依《各類場所消防安全設備設置標準》第 161 條之避難器具減設規定，主要構造為防火構造，且設有能通往其他建築物或同一建築物他區之架空走廊或連絡橋，該走廊或連絡橋並限於避難、通行及搬運以外之用途不得使用者，其應設避難器具數量得減設二具。理由在於此種架空走廊本身即為一條可靠的水平避難路徑，其避難效能相當於兩具避難器具所能疏散的人數，故立法上准予折抵二具。題幹所述構造與用途限制均與該款要件相符，故選 B。\n【逐項排除】\n(A) 1 具：折抵數過低，與條文所定之二具不符；一具之折抵通常對應於效能較弱之其他替代條件，不適用於本題所述之防火構造架空走廊。\n(B) 2 具：與第 161 條所定架空走廊之減設額度完全相符，為正解。\n(C) 3 具：條文並未給予架空走廊如此高之折抵；若可抵三具，等同認定其避難效能近乎一座直通樓梯，已超出立法者對水平避難路徑的評價。\n(D) 4 具：折抵幅度明顯逾越，此規模在減設條文各款中並無任何對應規定，屬純粹放大的干擾選項。\n【記憶點】防火構造架空走廊只准走人不准堆貨——符合就抵兩具避難器具。","避難器具的設置、減設與免設分別規定於《各類場所消防安全設備設置標準》第 157 條至第 162 條，是本科的高頻命題區。第 157 條依場所用途與各樓層收容人員數決定應設具數；第 158 條列出各樓層適用之器具種類（如緩降機適用二樓以上十樓以下，救助袋、避難橋、滑臺、避難梯各有不同適用樓層）；第 159 條至第 160 條規範設置開口部尺寸、操作面積、下降空間與下降空地；第 161 條處理減設；第 162 條處理免設。\n第 161 條的減設邏輯一致：凡是能提供替代避難路徑或降低避難需求的建築條件，就按其效能折抵具數。架空走廊或連絡橋之所以能抵二具，是因為它讓該樓層人員無需垂直下降即可水平移動至另一棟建築或另一防護區，避難速度與安全性都遠優於使用避難器具；但條文特別強調「不得供避難、通行及搬運以外用途」，這是防止走廊被堆置貨物或改作他用而失去通路功能——實務上架空走廊淪為倉儲空間正是火場中常見的避難失敗原因，故立法者把用途限制直接寫進要件。同樣地，主要構造須為防火構造，是避免走廊本身在火勢中先行崩塌。\n第 162 條的免設要件則更嚴，須同時滿足主要構造為防火構造、居室外牆有開口部或直通樓梯符合特定規格、收容人員未達一定數額等條件，考題常把「減設」與「免設」互換設陷。記憶時可抓住層次：條件較弱者減設、條件足以取代避難器具者免設。\n易混淆數值另可整理：避難器具之支固器具與建築物構造部分之連接須能承受最大使用載重；緩降機操作面積零點五平方公尺以上且邊長六十公分以上；救助袋操作面積為寬一點五公尺、長一點五公尺以上；下降空間與下降空地依器具種類各有半徑或尺寸規定。這些數值常與減設題併為綜合題出現。\n相關考點連結上，收容人員之計算方式（依《設置標準》第 20 條之場所用途別，以樓地板面積除以規定係數，或以固定座椅數、從業員數合計）是決定應設具數的前提，減設幾具的問題若把收容人員算錯，後續全盤皆錯，複習時宜與本條併同處理。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-022","依出口標示燈及避難方向指示燈認可基準規定，燈具附有起動器者，應在多少時間內點燈？",22,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-024","依各類場所消防安全設備設置標準規定，特別安全梯或緊急昇降機間排煙室之排煙設備設置排煙、進風風管時，下列何者有誤？",24,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-021","下列消防安全設備緊急供電系統之配線，何者需施予耐燃保護？",21,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-025","依緊急照明燈認可基準規定，內置電池型緊急電源供電照明時間應維持 1.5 小時以上（供緊急照明燈總數）後，其蓄電池電壓不得小於蓄電池額定電壓多少百分比？",25,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-020","差動式探測器之動作原理為感應火場中何種參數？",20,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-026","樓梯或斜坡通道以外之場所，廣播區域之殘響時間在 3 秒以上時，揚聲器之裝設需符合 r = 3 \u002F 4 QSα\u002Fπ (1 −α) 之計算公式，S 的定義為何？",26,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-023",113,"依各類場所消防安全設備設置標準規定，下列何場所或建築物未達應設置火警自動警報設備條件？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-023",112,"有關特別安全梯或緊急昇降機間排煙室之排煙設備，當設置直接面向戶外之窗戶時，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-023",111,"火焰探測器偵測火災為偵測火場的何種參數？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-023",110,"依各類場所消防安全設備設置標準，火警探測器之探測區域係指裝置面之四周以淨高 X 公分以上之樑或類似構造體區劃包圍者。偵煙式探測器，其裝置面之四周淨高應為 Y 公分，其中 X 及 Y 分別為：",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-023",109,"有關地下建築物總樓地板面積在幾平方公尺以上應設置無線電通信輔助設備，下列何者與各類場所消防安全設備設置標準之規定相同？",1785129965481]