[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-015","fire-106-1-alarm-evacuation-015",106,1,15,"依緩降機認可基準規定，緩降機之最大使用載重，應在最大使用人數乘以 W 所得數值以上。下述 W 值何者正確？",{"A":16,"B":17,"C":18,"D":19},"500 NT","750 NT","800 NT","1000 NT","D",null,[],false,"本題考點：緩降機認可基準對最大使用載重的規定，考的是每一使用人數所對應的載重換算值。\n【正解理由】依《緩降機認可基準》有關最大使用載重之規定，緩降機之最大使用載重應在最大使用人數乘以一千牛頓所得數值以上；一千牛頓約相當於一百公斤重，係以單一使用者體重加裝備並含安全裕度所定之基準值，故選 D。\n【逐項排除】\n(A) 500 NT：五百牛頓約相當於五十公斤重，低於單一成人平均體重加裝備的設計值，不足以作為每人載重基準。\n(B) 750 NT：七百五十牛頓約七十五公斤重，雖接近成人體重，但未保留安全裕度，非認可基準所採數值。\n(C) 800 NT：八百牛頓約八十公斤重，同樣缺乏足夠裕度，且基準並未採用此一數值。\n(D) 1000 NT：與認可基準「最大使用載重應在最大使用人數乘以一千牛頓所得數值以上」相符，換算約每人一百公斤重，為正解。\n【記憶點】緩降機載重「每人一千牛頓」，取 100 公斤重×9.8 進位而來，約等於一百公斤重。","緩降機屬避難器具中的「繩索類」，由調速器、調速器連結部、繩索、緊結金屬配件及安全帶組成，靠調速器內部的離心制動或齒輪機構限制下降速度，使避難者以每秒十六公分至一百五十公分之間的速度安全著地。因為全程荷重都由繩索與調速器承受，載重規格就是產品安全的核心指標，認可基準因此規定最大使用載重須在最大使用人數乘以一千牛頓以上，並要求以該載重進行反覆下降試驗、最大使用載重下降試驗與強度試驗。\n\n單位換算是本題的隱藏考點。牛頓（N）為力的單位，一牛頓定義為使一公斤質量產生每秒平方一公尺加速度所需的力，即 1 N = 1 kg·m\u002Fs²。體重換算取重力加速度 g ≈ 9.8 m\u002Fs²，故 100 kg × 9.8 m\u002Fs² = 980 N ≈ 1000 N。認可基準取整數一千牛頓，等於把每位使用者的設計體重抓在一百公斤重，對台灣成人體重分布而言已含相當裕度，同時方便計算。反過來，若題目給的是公斤重，可用 1 kgf ≈ 9.8 N 換算回去。\n\n相關數值可一併整理：緩降機下降速度在每秒十六公分以上、一百五十公分以下；繩索長度應由固定部至地面或其他預定降落面之長度；操作面積零點五平方公尺以上且邊長六十公分以上；下降空間為以器具中心半徑零點五公尺之圓柱範圍。\n\n易混淆概念對照：緩降機與避難梯、救助袋雖同為避難器具，載重設計思維不同——緩降機為單人循環使用，載重以人數乘固定值計；避難梯屬結構性構件，以踏板與支柱的強度試驗規範；救助袋則以袋體抗拉強度與下滑速度為主要驗證項目。此外，緩降機依構造分為固定式與移動式，移動式須搭配支固定架，其固定部強度亦須能承受規定荷重，這是與設置標準第 160 條可互相串聯的考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-014","依各類場所消防安全設備檢修及申報作業基準規定，火警自動警報設備之受信總機前應確保多少公尺以上空間以進行檢查及操作使用？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-016","瓦斯漏氣火警自動警報設備裝置於瓦斯對空氣之比重未滿一之建築物室內時，檢知器設置位置應距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離多少以內？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-013","集合住宅計算收容人數以設置避難器具時，每戶收容人數以多少人計算？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-017","檢查緩降機性能時，有關常溫下降試驗之判定中，緩降機最大下降速度應在多少以內？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-012","依據緊急照明燈認可基準進行充電試驗時，蓄電池電壓降達額定電壓多少以內時，需能自動充電？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-018","依各類場所消防安全設備檢修及申報作業基準規定，火焰探測器以動作試驗器確認探測器之動作應在多少時間內方為合格？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-015",113,"瓦斯洩漏時檢知器設置位置將會影響其探測性能，依據消防安全設備及必要檢修項目檢修基準之規定，來判定瓦斯漏氣檢知器設置場所及設置位置，下列何者為適合的設置場所？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-015",112,"有關消防安全設備緊急電源容量，依據各類場所消防安全設備設置標準，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-015",111,"依各類場所消防安全設備設置標準規定，為確保排煙設備動作時，不受空調等通風換氣裝置影響排煙效果，下列何項排煙設備元件動作時應連動停止空氣調節及通風設備運轉？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-015",110,"對空氣管式之差動式分布型探測器進行空氣注入之性能檢查時，下列何種試驗無須量測探測器導通與否？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-015",109,"有關排煙設備之設置規定，下列敘述何者錯誤？",1785129965417]