[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-014","fire-106-1-alarm-evacuation-014",106,1,14,"依各類場所消防安全設備檢修及申報作業基準規定，火警自動警報設備之受信總機前應確保多少公尺以上空間以進行檢查及操作使用？",{"A":16,"B":17,"C":18,"D":19},"0.5 公尺","1 公尺","1.5 公尺","2 公尺","B",null,[],false,"本題考點：火警自動警報設備之檢修規定，考的是《各類場所消防安全設備檢修及申報作業基準》對受信總機前方應保留操作空間的距離要求。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》有關火警自動警報設備受信總機之外觀檢查項目，受信總機前方應確保一公尺以上之空間，使檢查與操作得以順利進行；本題所問即為該淨空距離，故選 B。\n【逐項排除】\n(A) 0.5 公尺：零點五公尺不足以讓人員站立並開啟總機門板操作，未達基準所定的淨空要求。\n(B) 1 公尺：與作業基準所定「受信總機前應確保一公尺以上空間」相符，為正解。\n(C) 1.5 公尺：一點五公尺屬其他設備（如避難器具操作面積）常見數值，並非受信總機前方的檢查操作空間規定。\n(D) 2 公尺：二公尺遠超基準要求，一般值日室或防災中心亦難以普遍達成，作業基準並未採此數值。\n【記憶點】受信總機前留「一公尺」淨空，機箱門開得了、人站得下，外觀檢查的周圍狀況項目才判定合格。","《各類場所消防安全設備檢修及申報作業基準》是依《消防法》第 9 條授權訂定，將各類消防安全設備的檢修項目分為外觀檢查、性能檢查與綜合檢查三個層次。外觀檢查以目視確認設備是否存在、有無變形損傷、周圍是否被遮蔽或阻礙；性能檢查以實際操作或量測確認個別零組件是否正常；綜合檢查則以模擬火災訊號等方式，確認系統整體連動是否正確。\n\n受信總機的外觀檢查重點在「周圍狀況」與「外形」兩項。周圍狀況要求總機設於值日室等平時有人之處所、操作開關距離樓地板面之高度在一定範圍內、前方確保一公尺以上之操作與檢查空間；外形則檢查機箱有無變形、腐蝕、火警分區表示裝置是否清晰、標示是否脫落。這些要求與《各類場所消防安全設備設置標準》第 128 條的設置規定互為表裡：設置標準管「裝設時應如何」，檢修基準管「日後如何確認仍維持該狀態」。\n\n數值記憶對照上，警報系統常出現的距離值可整理為：受信總機前方淨空一公尺以上；操作開關距樓地板面高度在零點八公尺（座式操作者為零點六公尺）以上、一點五公尺以下；探測器裝置於天花板下方三十公分範圍內；偵煙式探測器距出風口一點五公尺以上、距回風口一公尺以內。把「一公尺」在不同情境的兩種用法（總機前淨空、回風口周圍）分開記，可避免張冠李戴。\n\n易混淆概念對照：受信總機、中繼器與火警發信機三者常被混談。受信總機接收訊號並顯示分區、啟動地區音響裝置；中繼器介於探測器與受信總機之間，負責訊號轉換與傳送，Ｒ型系統倚重之；火警發信機則供人員手動報警，依規定應與標示燈、地區音響裝置併設於樓梯或走廊等明顯易於操作之處。檢修基準對三者各有獨立的檢查項目與判定方法，作答時須看清題目問的是哪一個。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-013","集合住宅計算收容人數以設置避難器具時，每戶收容人數以多少人計算？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-015","依緩降機認可基準規定，緩降機之最大使用載重，應在最大使用人數乘以 W 所得數值以上。下述 W 值何者正確？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-012","依據緊急照明燈認可基準進行充電試驗時，蓄電池電壓降達額定電壓多少以內時，需能自動充電？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-016","瓦斯漏氣火警自動警報設備裝置於瓦斯對空氣之比重未滿一之建築物室內時，檢知器設置位置應距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離多少以內？",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-011","Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，不得超過 X 個。受信總機之探測器回路電阻，應在 Y 以下。下列何者正確？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-017","檢查緩降機性能時，有關常溫下降試驗之判定中，緩降機最大下降速度應在多少以內？",17,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-014",113,"某社區活動中心位於建築物第 2 層（非避難層），經檢討該活動中心為有開口樓層，依規定自活動中心任一點易於觀察識別其主要出入口，且與主要出入口之步行距離分別在 X 公尺以下，得免設出口標示燈；步行距離在 Y 公尺以下，得免設避難方向指示燈，則 X+Y=？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-014",112,"依各類場所消防安全設備設置標準規定，火警自動警報設備應採分區鳴動，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-014",111,"依各類場所消防安全設備設置標準規定，供失智照顧型長期照顧服務機構、老人福利機構（安養機構）、產後護理機構等避難弱勢場所之樓層，符合規定者得免設避難器具，下列何者非免設之必要條件？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-014",110,"對火警自動警報設備二信號式受信總機進行火災表示之性能檢查時，接到第 1 報火警信號但尚未接到第 2 報火警信號時，下列那二種裝置均不應動作？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-014",109,"某百貨商場之 5 樓樓地板面積為 2,100 平方公尺，依各類場所消防安全設備設置標準規定，該層樓至少應設置幾個防煙區劃？",1785129965410]