[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-011","fire-106-1-alarm-evacuation-011",106,1,11,"Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，不得超過 X 個。受信總機之探測器回路電阻，應在 Y 以下。下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"X：7，Y：50Ω","X：10，Y：75Ω","X：12，Y：65Ω","X：15，Y：75Ω","A",null,[],false,"本題考點：受信總機之裝置規定，考的是《各類場所消防安全設備設置標準》第 127 條所定公用線共用分區數上限與探測器回路電阻上限。\n【正解理由】依《各類場所消防安全設備設置標準》第 127 條，Ｐ型受信總機若以一條公用線同時服務多個火警分區以節省幹線，共用該線的分區數上限為七個；另受信總機之探測器回路電阻須在五十歐姆以下，以確保動作電流足以驅動機內繼電器。X 為七、Y 為五十歐姆，故選 A。\n【逐項排除】\n(A) X：7，Y：50Ω：兩項數值皆與條文相符，公用線七分區、回路電阻五十歐姆以下，為正解。\n(B) X：10，Y：75Ω：分區數十個超出法定上限，一旦公用線斷線將導致過多分區同時失效；七十五歐姆亦超過電阻上限。\n(C) X：12，Y：65Ω：十二個分區與六十五歐姆皆無條文依據，屬純干擾組合。\n(D) X：15，Y：75Ω：十五個分區明顯過多，違反限制共用線失效影響範圍的立法目的，電阻值亦不符。\n【記憶點】公用線「七分區」、回路電阻「五十歐姆」，兩個數字一起背。","Ｐ型受信總機採共用線（common line）配線，是為了節省幹線導體數量：若每一分區都拉一組獨立的往返線，十個分區就要二十條線；改以數個分區共用一條回線，只需十一條。代價是可靠度集中——共用線一旦斷線或短路，其所連接的所有分區同時喪失偵報功能。法規把共用分區數限制在七個以下，正是在配線經濟性與失效影響範圍之間取得平衡，讓單一線路故障最多只癱瘓七個分區。\n\n探測器回路電阻限制在五十歐姆以下，理由在於火警回路多採直流二十四伏特級電壓，探測器動作時以回路電流變化驅動受信總機內繼電器；導線過長或線徑過細會使回路電阻升高，壓降增大，動作電流不足即造成不動作或動作不確實。回路電阻與導線長度、線徑的關係為 R = ρL／A，導線加長一倍電阻加倍，線徑截面積加倍電阻減半，因此長距離配線必須加大線徑，這也是同一條文常延伸出的計算型考點。\n\n易混淆概念對照：Ｐ型受信總機以「回線」對應火警分區，靠回線編號辨識位置；Ｒ型受信總機則以中繼器把訊號編碼後以多工傳輸，可辨識到個別探測器位址，配線大幅簡化，故Ｒ型並無共用線分區數限制的問題。此外，Ｐ型又分第一級、第二級與第三級，回線數與所需附屬功能（如火警電話、地區音響裝置）不同，第二級以下回線數受限，這是本條相鄰條文的高頻考點。\n\n同一條文的其他考法還包括：受信總機應具有火警分區表示裝置、附設緊急電源、裝置於值日室等經常有人之處所（第 128 條），以及探測器回路採用串接方式時之導通試驗規定。建議把「七分區、五十歐姆、常時有人處所、附設緊急電源」四項一併記憶。\n\n※ 本題所引條號請以現行法規條次為準核對。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-010","緩降機設置周圍為避免有操作障礙，因此限制必要操作面積為 M 平方公尺以上（不含避難器具所占面積），但邊長應為 N 公分以上。下列何者正確？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-012","依據緊急照明燈認可基準進行充電試驗時，蓄電池電壓降達額定電壓多少以內時，需能自動充電？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-009","差動式分布型探測器為熱電偶式時，熱電偶應裝置在裝置面下方多少公分範圍內？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-013","集合住宅計算收容人數以設置避難器具時，每戶收容人數以多少人計算？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-008","天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍多少距離範圍內？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-014","依各類場所消防安全設備檢修及申報作業基準規定，火警自動警報設備之受信總機前應確保多少公尺以上空間以進行檢查及操作使用？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-011",113,"某一場所設有一 A 級出口標示燈，其縱向尺度為 0.8 公尺，且未顯示避難方向符號者，請問其步行距離應為多少公尺？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-011",112,"依據火警探測器認可基準之構造及材質規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-alarm-evacuation-011",111,"依各類場所消防安全設備設置標準規定，下列場所何者未強制要求設置 119 火災通報裝置？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-alarm-evacuation-011",110,"特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-alarm-evacuation-011",109,"避難器具設置數量需衡酌場所之收容人數，依各類場所消防安全設備設置標準規定，百貨商場供飲食或休息用場所之收容人數計算，應以該部分樓地板面積除多少？",1785129965385]