[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-106-1-警報與避難系統消防安全設備概要-001","fire-106-1-alarm-evacuation-001",106,1,"某一 KTV 視聽歌唱場所設於大樓地下層，依規定樓地板面積如合計超過多少，應設置瓦斯漏氣火警自動警報設備？",{"A":15,"B":16,"C":17,"D":18},"300 平方公尺","500 平方公尺","1000 平方公尺","1500 平方公尺","C",null,[],false,"本題考點：瓦斯漏氣火警自動警報設備的設置場所門檻，特別是地下層樓地板面積合計的數值。\n【正解理由】依《各類場所消防安全設備設置標準》第 21 條，使用瓦斯之場所應設瓦斯漏氣火警自動警報設備者包括：地下建築物、供甲類場所使用之地下層樓地板面積合計 1000 平方公尺以上者，以及地下層供甲類場所使用之樓地板面積合計 1000 平方公尺以上且其中甲類場所使用樓地板面積合計 500 平方公尺以上者。KTV 視聽歌唱場所屬甲類場所，設於大樓地下層時以 1000 平方公尺為判準，故選 C。\n【逐項排除】\n(A) 300：非本條門檻。300 平方公尺常見於其他設備（如部分場所火警自動警報設備）的面積級距，屬張冠李戴。\n(B) 500：此為同條中「其中甲類場所使用部分」的次要門檻，非地下層合計面積的主門檻，對象層次不同。\n(C) 1000：正是條文對地下層樓地板面積合計所定的數值，符合題意所問。\n(D) 1500：條文無此數字，過高將使多數地下層 KTV 免設，與立法目的相悖。\n【記憶點】瓦斯漏氣設備看地下層「合計一千、其中甲類五百」，兩層門檻分清楚。","瓦斯漏氣火警自動警報設備與火警自動警報設備是兩套獨立系統：後者偵測的是火災的熱與煙，前者偵測的是尚未起火的可燃性氣體。條文把設置門檻壓在地下層與地下建築物，理由很直接——瓦斯洩漏後的擴散行為受空間換氣影響極大，地下空間自然通風差，天然氣（主成分甲烷，比重小於空氣）會積在天花板附近，液化石油氣（主成分丙烷、丁烷，比重大於空氣）則沉在地板附近，兩者都容易在密閉的地下層累積到爆炸範圍。KTV 這類甲類場所又具備人員密集、包廂隔間多、逃生路徑不熟悉的特性，一旦引爆後果嚴重，故列為重點管制對象。\n設備構成三件套：檢知器、中繼器、受信總機，並以警報裝置（音響）與瓦斯漏氣表示燈告知位置。檢知器設置位置與氣體比重直接相關——比重小於空氣者裝於天花板面下方一定距離、且距瓦斯燃燒器具或導管貫穿處水平距離 8 公尺以內；比重大於空氣者裝於地板面上方一定高度、水平距離 4 公尺以內。這組「8 公尺與 4 公尺」是與本題同條文最常搭配出現的數值。\n易混淆概念對照：甲類場所指供公眾使用、危險度高的場所（電影院、KTV、舞廳、酒家、飯店餐廳、醫院等）；乙類以下則危險度遞減。判斷面積門檻時要先確定場所類別，再看是問「地下層合計面積」還是「其中甲類部分面積」，前者 1000、後者 500，混用即錯。\n相關考點連結：同一體系常一併考瓦斯漏氣受信總機的設置場所與操作開關高度、警報分區的劃定，以及檢知器不得設置的位置（如出風口 1.5 公尺內、換氣口附近）。",true,[27,32,36,41,45,49],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-114-1-alarm-evacuation-004","某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",4,114,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-002","對於消防安全設備緊急供電系統之配線之規定，下列何者正確？",2,{"webId":37,"stem":38,"number":39,"year":40,"session":12},"fire-113-1-alarm-evacuation-040","依據火警探測器認可基準，對於差動式探測器直線上升的動作試驗，自室溫狀態下以平均每分鐘 T℃直線升溫速度之水平氣流吹向時，應在 M 分鐘以內動作，下列敘述何者正確？",40,113,{"webId":42,"stem":43,"number":44,"year":11,"session":12},"fire-106-1-alarm-evacuation-003","裝設緊急廣播設備之建築物之規定，下列何者錯誤？",3,{"webId":46,"stem":47,"number":48,"year":40,"session":12},"fire-113-1-alarm-evacuation-039","某捷運高架車站，因地形環境因素致車站早晚霧氣瀰漫，為防止霧氣結露產生探測器誤動作，選設之探測器除考量防水性能外，試問下列何者探測器不適用？",39,{"webId":50,"stem":51,"number":30,"year":11,"session":12},"fire-106-1-alarm-evacuation-004","依各類場所消防安全設備檢修及申報作業基準規定，1 種光電式局限型偵煙探測器於使用加煙試驗器確認動作之時間，加煙後至動作應在多少時間內方為合格？",[53,56,60,64,68],{"webId":54,"year":40,"stem":55,"number":12},"fire-113-1-alarm-evacuation-001","為能有效排除火場中的濃煙，必須定期確保排煙設備之有效性，依據排煙設備檢修基準之要求，進行排煙設備的相關檢查時，下列敘述何者錯誤？",{"webId":57,"year":58,"stem":59,"number":12},"fire-112-1-alarm-evacuation-001",112,"依據配線檢修基準性能檢查之檢查方法，有關高壓回路電源回路間及電源回路與大地間之絕緣電阻值測定，下列敘述何者錯誤？",{"webId":61,"year":62,"stem":63,"number":12},"fire-111-1-alarm-evacuation-001",111,"依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":65,"year":66,"stem":67,"number":12},"fire-110-1-alarm-evacuation-001",110,"下列有關建築物火警分區之劃定，何者符合各類場所消防安全設備設置標準的規定？",{"webId":69,"year":70,"stem":71,"number":12},"fire-109-1-alarm-evacuation-001",109,"常開式之火警探測器信號回路，加設終端電阻之目的為何？",1785129965299]